DX1063
Universal display
24
End value
displayed value
Start value
Frequency
end
Frequency
start
input frequency [Hz]
Fig. 46: Application [Frequency start] / [Frequency end]
u
Optionally select [Value offset] and set the value for the display offset:
•
-1999…9999
u
Select [Linearization points] and set the desired number of linearization points:
•
0…9
For the number of linearization points configured under [Linearization points], configure [Display
P#x(Y)] and [Frequency P#x(X)] respectively:
u
Select [Display P#x(Y)] and set the display value for the corresponding frequency value of the
relevant linearization point:
•
-1999…9999
u
Select [Frequency P#x(X)] and set the frequency value for the corresponding display value of the
relevant linearization point:
•
0000…9999 Hz
9.1.5 RPM/Speed
The unit displays the measured speed.
Parameter setting:
ü
[Input type] [RPM/Speed] is selected.
u
Select [Input signal] and set the type of input signal:
•
TTL
•
NPN
•
PNP
•
NAMUR
u
Select [Filter] and set the desired input filter to avoid interference signals:
•
2 Hz
•
5 Hz
•
10 Hz
•
20 Hz
•
50 Hz
•
100 Hz
•
200 Hz
•
500 Hz
•
No