Operating instructions

Converter 2 x 0...10 V / IO-Link

DP1222

80272878 / 01   02 / 2022

GB

Summary of Contents for DP1222

Page 1: ...Operating instructions Converter 2 x 0 10 V IO Link DP1222 80272878 01 02 2022 GB ...

Page 2: ...the connector 12 6 2 Removing the connector 12 6 3 Cable length 12 7 Operating and display elements 13 7 1 LEDs 13 7 1 1 Visualisation of the voltage value at the input 13 8 Parameter setting 14 8 1 Parameters via IO Link 14 8 1 1 Application specific tag 14 8 1 2 Function Tag 14 8 1 3 Location Tag 14 8 1 4 internal_temperature operating temperature microcontroller 14 8 1 5 operation_hours operati...

Page 3: ...on the unit packaging or at www ifm com 1 1 Symbols used Requirement Instructions Reaction result Designation of keys buttons or indications Cross reference Important note Non compliance may result in malfunction or interference Information Supplementary note 1 2 Warnings used CAUTION Warning of personal injury w Slight reversible injuries may result ...

Page 4: ...t and keep it during the entire service life The product must be suitable for the corresponding applications and environmental conditions without any restrictions Only use the product for its intended purpose Ò Intended use If the operating instructions or the technical data are not adhered to personal injury and or damage to property may occur The manufacturer assumes no liability or warranty for...

Page 5: ...nverter A maximum of 11 V may be applied to each input Otherwise the accuracy of the respective other channel will be negatively affected If the LED IN1 IN2 flashes and the IO Link event Process value above valid range 0x8C10 is present the accuracy of the other channel can no longer be guaranteed The unit is not suited for environments with particular requirements on mechanical stability e g shoc...

Page 6: ...ort all functionalities described in the instructions Application To ensure compatibility if sensors are replaced IODD designation DP1222 IO Link device ID 613d 00 02 65 h Operating mode 2 default Description Operating mode on delivery Application Standard application IODD designation DP1222_Status_B IO Link device ID 1428 d 00 05 94 h 4 2 Application as an IO Link device 4 2 1 General information...

Page 7: ... the IO Link device and detailed information about process data structure diagnostic information and parameter addresses at www ifm com 4 3 Function diagrams 4 3 1 Single point mode SP1 SP1 H SP1 H OFF ON SSC Fig 3 NO IO Link parameter LoGc high active SP1 Switch off point SP1 H Trigger point overvoltage If a set voltage is not reached this is signalled as low by a bit in the input process data SP...

Page 8: ...it in the input process data In operating mode 1 this function is not available 4 3 3 Two point mode SP2 SP1 SP2 H OFF ON SSC SP1 Fig 7 NO IO Link parameter LoGc no high active SP1 Trigger point overvoltage SP2 Switch off point If a set voltage is not reached this is signalled as low by a bit in the input process data SP2 SP1 SP2 H ON SSC SP1 OFF Fig 8 NC IO Link parameter LoGc nc low active SP1 T...

Page 9: ...Converter 2 x 0 10 V IO Link DP1222 9 In operating mode 1 this function is not available ...

Page 10: ...d the unit are protected from mechanical stress such as shock and vibration u If necessary fix the unit with a clamp use M4 screw or cable tie Fig 9 Mounting clip Fig 10 Mounting clip with attached unit The mounting clip is not supplied with the unit More information about available accessories at www ifm com ...

Page 11: ...ply the unit via a limited energy circuit according to IEC 61010 1 or class 2 according to UL1310 For use in USA and Canada For connecting the unit and the IO Link devices use UL certified cables of category CYJV 2 7 8 having suitable ratings u Disconnect power u Connect the unit as follows 2 1 4 3 2 1 3 1 2 4 5 Fig 11 Electrical connection 1 4 pole M12 male connector IO Link side Pin 1 L supply v...

Page 12: ...Minimum tightening torque 0 6 Nm tightening by hand Maximum tightening torque 1 5 Nm using a torque wrench If used in harsh environments w Further tighten the coupling nut by another notch using a torque wrench across the flats 14 6 2 Removing the connector u Press the connector against the unit and simultaneously loosen the coupling nut 6 3 Cable length With IO Link communication 20 m on the mast...

Page 13: ...green on Voltage supply OK Unit in operating mode flashing 5 Hz Device supply undervoltage off Voltage supply off II IN2 yellow on Analogue value in the standard range 0 100 0 10 V flashing 2 Hz Analogue value in the range 100 10 V Error signals and diagnostics Ò Troubleshooting Via IO Link an error signal is transmitted if value 11 V 7 1 1 Visualisation of the voltage value at the input 0 10 11 V...

Page 14: ...on description max 32 characters long Value can be freely defined by the customer 8 1 4 internal_temperature operating temperature microcontroller Reads the data from the internal temperature sensor of the microcontroller In operating mode 1 this parameter is not available 8 1 5 operation_hours operating hours Only counts full operating hours Operating times of less than one full hour are not save...

Page 15: ... not available 8 1 9 SP2 switch point 2 Threshold for the lower switch point It always applies SP2 SP1 In operating mode 1 this parameter is not available 8 1 10 HyS switch points hysteresis Setting of the hysteresis with respect to switch points SP1 and SP2 Function diagrams Ò 7 Only active in the switch point modes Single point mode and Window mode In operating mode 1 this parameter is not avail...

Page 16: ...DP1222 Converter 2 x 0 10 V IO Link 16 9 Operation The unit provides the IO Link process data according to the analogue input signals ...

Page 17: ...2 17 10 Troubleshooting LED Status Error Troubleshooting Power flashing 5 Hz Supply voltage too low Check correct the supply voltage Ò Electrical connection off No supply voltage Check correct the supply voltage Ò Electrical connection ...

Page 18: ... voltage supply u Clean the unit from dirt using a soft chemically untreated and dry micro fibre cloth The operation of the unit is maintenance free Only the manufacturer is allowed to repair the unit u After use dispose of the device in an environmentally friendly way in accordance with the applicable national regulations ...

Page 19: ...Gc Switch point logic Low active High active Low active SSC1 SP1 Switch point 1 2 1 SSC1 SP2 Switch point 2 2 SSC1 HyS Switch point hysteresis 2 SSC2 ModE Switch point mode Two point Deactivated Single point Window Two point SSC2 LoGc Switch point logic Low active High active Low active SSC2 SP1 Switch point 1 2 1 SSC2 SP2 Switch point 2 2 SSC2 HyS Switch point hysteresis 2 Not available in operat...