DN4034 Installation Manual 

 

 

 

 

Product Description 

The DN4034 is a DIN-rail mountable power supply for three-phase mains systems, which provides a 
floating, stabilized and galvanically separated SELV/PELV output voltage. 
 

Intended Use

 

This device is designed for installation in an enclosure and is intended for commercial use, such as in 
industrial control, process control, monitoring and measurement equipment or the like.  
Do not use this device in equipment, where malfunctioning may cause severe personal injury or 
threaten human life without additional appropriate safety devices, that are suited for the end-
application. 
If this device is used in a manner outside of its specification, the protection provided by the device may 
be impaired. 
 

Installation Instructions 

Install device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to 
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 
Ensure that all strands of a stranded wire enter the terminal connection. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost is allowed. 
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide 
protection against spilled liquids. 
The device is designed for overvoltage category II zones. Below 2000m altitude the device is tested 
for impulse withstand voltages up to 4kV, which corresponds to OVC III according to IEC 60664-1. 
The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use 
without a proper PE (Protective Earth) connection. 
The device is suitable to be supplied from TN, TT or IT mains networks. The continuous voltage 
between the input terminal and the PE potential must not exceed 400Vac. The device is not designed 
to be used on corner grounded delta systems. 
A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in 
output current is required. 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 16A (IEC) and 15A (UL) without 
additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 6A 
B- or 3A C-Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 
 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads, including unlimited inductive and capacitive loads. 
Do not apply return voltages from the load to the output terminals higher than 34V. 
The output voltage can be adjusted with a small flat-blade screwdriver behind the flap on the front. 
The green DC-OK LED reports an output voltage above 90% of the adjusted voltage of a running 
device. 
The DC-OK relay monitors the output voltage and the contact is closed when the DC-OK LED is on. 
Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads. 
The red overload LED is on when the output voltage falls below 90% of the adjusted value or in case 
of a short circuit in the output or too high temperature. Input voltage is required. 
The device is equipped with an over-temperature protection. In case of a high temperature, the output 
shuts down and starts automatically again after cooling off. 
The device is designed to deliver 30A output current for up to 4s with nominal output voltage. 
Devices can be paralleled to increase the output power. The ambient temperature is not allowed to 
60°C. The output voltage shall be adjusted to the same value (±100mV) with the same load 
conditions on all devices, or the devices can be left with the factory settings. If more than three 
devices are connected in parallel, a diode, fuse or circuit breaker with a rating of 25A is required on 
each output. 
Same devices can be connected in series for higher output voltages. It is allowed to connect as many 
devices in series as needed, providing the sum of the output voltage does not exceed 150Vdc. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 35V. The output 
shuts down and automatically attempts to restart. 
 

 

Technical Data

 

All values are typical figures specified at 3x 400Vac 50Hz input voltage, 
symmetrical phase voltages, 24V, 20A output load, 25°C ambient 
temperature and after a 5 minutes run-in time unless otherwise noted. 

Output voltage 

DC 24V 

Nominal 

Adjustment range 

24 – 28Vdc 

Factory setting 24.1V 

Output current 

Continuous: 

 

20 – 17.5A 

Below +60°C ambient 

 

15 – 13.1A 

At +70°C ambient 

 

Short-term, up to 4s: 

 

30 – 26.0A 

Below +70°C ambient 

 

Derate linearly b60°C and +70°C 

Input voltage AC 

3AC 380 - 480V 

±15% 

Mains frequency 

50 – 60Hz 

±6% 

Input current AC 

0.79 / 0.65A 

At 3x400 / 480Vac 

Power factor 

0.94 / 0.95 

At 3x400 / 480Vac 

Input inrush current 

3 / 3A peak 

At 3x400 / 480Vac, 
temp. independent 

Efficiency 

95.0 / 94.8% 

At 3x400 / 480Vac 

Losses 

25.3 / 26.4W 

At 3x400 / 480Vac 

Hold-up time 

22 / 22ms 

At 3x400 / 480Vac 

Temperature range 

-25 to +70°C 

 

Max. wire size (litz wire) 

4mm² 

 

Wire size AWG 

AWG 20-10 

 

Max. wire diameter 

2.8mm 

 

Wire stripping length 

10mm / 0.4inch 

 

Size 

(wxhxd)

 

65x124x132.5mm  Without DIN-rail 

Weight 

920g / 2.0lb 

 

 
 

Functional Diagram 

L2
L3

L1

+

+

-

-

Output

Over-

Voltage

Protection

PFC

Converter

Voltage

Regulator

Power

Converter

Output

Filter

Output

Power

Manager

Temper-

ature

Shut-

down

Input Filter
Input Rectifier
Inrush Current
Limiter

V

OUT

DC-OK

Contact

DC-OK

LED

DC-ok

Relay

13
14

Overload

LED

 

 
 

Output Characteristic 

Output voltage

35A

24V

Output current

12V

0V

5A

15A

20A

25A

0A

Adjustment range

28V

10A

30A

B

A

A: continuous

B: for 4s

 

 
 

Temperature Range 

Allowed output current at 24V

Ambient temperature

0A

-25

A: continuous

B: short term (typ. 4s)

30A

0

+70°C

15A

B

20A

+60

A

 

 