DI604A
Compact speed monitor M18
8
4.3 Two-point mode
SP2 SP1
H
SSC
0
PDV
OFF
ON
Fig. 5: Normally open = low active
SP2:
Switch-off point
SP1:
Switch-on point
If a set rotational speed is not reached, the transistor output will signal this as non-conducting.
H
SSC
0
PDV
SP2 SP1
ON
OFF
Fig. 6: Normally closed = high active
SP2:
Switch-on point
SP1:
Switch-off point
If a set rotational speed is not reached, the transistor output will signal this as conducting.
Imp./min.
3000
2500
2000
1500
1000
500
0
1
0
1
0
OUT
2
3
4
1
OUT
SP1
SP2
t
1:
Power-on delay time
2:
Start-up delay
3:
Normally open = low active
4:
Normally closed = high active
It is also possible to configure SP1 as the lower switch point and SP2 as the upper switch point.
The lower switch point must be at least 10% lower than the higher switch point.
4.4 IO-Link mode
IO-Link allows the configuration of internal parameters such as switching threshold, start-up delay and
switching behaviour (normally closed/normally open) as well as reading the current measured values.
Furthermore IO-Link protects against signal faults and measured value losses as well as tampering
with the sensor. IO-Link facilitates the identification of connected devices in the system and provides
diagnostic functions.