background image

3

UK

3  Functions and features

•  Maximum number of modules per master: 62
•  AS-Interface version 3.0, downward compatible
•  4 inputs / 4 outputs / AS-i profile S-7.A.7 / extended addressing mode: yes
•  The unit can only be operated in conjunction with a version 3.0 master (master 

profile M4).

4  Installation

 

► Disconnect the system from power before installation.

 

► For installation choose a flat mounting surface.
The entire bottom of the module must lie flat on the mounting surface.

 

► Fix the module onto the mounting surface using M4 screws and washers. 

5  Electrical connection

 

► Disconnect the installation from power and connect the unit.
To ensure the protection rating: 

 

► Connect the plugs of the sensors to the M8 sockets.

 

► Tighten firmly, recommended tightening torque 0.3...0.5 Nm.

 

► Cover the sockets that are not in use with the enclosed protective caps.

5.1  Pin connection

Socket M12

1: AS-i +
2: AUX -
3: AS-i -
4: AUX +

4
1

2

3

Input M8

1: sensor
3: sensor supply -
4: data input

Output M8

3: external voltage E-
4: switching output

Reviews: