IO-Link Master with IoT Interface CabinetLine 8 Ports IP 20
15
>
6.3
IO-Link ports
52232
The IO-Link ports of the device meet the requirements of the IO-Link specification 1.0 to 1.1.2.
► Please note the information concerning IO-Link wiring!
WARNING!
Supply of energy to the IO-Link ports of the IO-Link master
>
Risk of fire!
► Prevent supply and feedback of energy to the IO-Link ports.
► Before set-up check the correct connection of the supply cables.
>
6.3.1
Operation as IO-Link port class A
52233
Wiring information:
The connected IO-Link devices must be supplied exclusively via the IO-Link master.
The additional digital inputs of the IO-Link ports X01...X08 (clamp 2) have a type 2 behaviour
according to the standard EN61131-2. The connected electronics must be electrically suited for
this.
► Connect IO-Link devices to the ports X01...X08.
Maximum cable length per IO-Link port: 20 m
► To connect the devices, only use cables with protection rating IP 20
or higher.