IO-Link Master with AS-Interface Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
24
>
9.2
Addressing the AS-i slave of the AC6000
51979
The user can use the following options when addressing the basic AS-i slave:
•
AS-i master:
→
Addressing via AS-i master
(
→
•
AS-interface addressing unit AC1154:
→
Addressing with addressing unit
(
→
Depending on the set ID1 code, the AC6000 takes up a space of up to 5 connected AS-i
addresses in the AS-i network. (
→
Adjusting the gateway profile
(
→
The following restrictions apply for the addressing:
ID1 code basic AS-i slave
additional AS-i slaves
valid address range of the basic AS-i slaves
0xF
0
1...31
0xB, 0xD
1
1...30
0x1, 0x2, 0x3, 0xA, 0xC
2
1...29
0x8, 0x9
3
1...28
0x4, 0x5, 0x6, 0x7
4
1...27
►
Take the valid address range into consideration when addressing the basic AS-i slave!
>
9.2.1
Addressing via AS-i master
59308
Functions for addressing:
→
User documentation of the AS-i master
►
Connect AC6000 with the AS-i network.
>
AS-i master shows configuration error.
►
Assign an free address to the AC6000 with functions of the AS-i master.
►
Re-configure the AS-i network.
>
AC6000 has a valid AS-i address.
>
AS-i master switches to operating mode "Protected mode".
>
Cyclic process data is transferred between the AS-i master and AC6000.