IO-Link Master with AS-Interface Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
25
>
9.2.2
Addressing with addressing unit
59309
Detailed information about AS-Interface addressing unit AC1154:
→
If the AC1154 is used for the addressing, the AC6000 must be supplied with the AUX supply
voltage. For this purpose, ifm offers the Y cable EVC844 as an accessory (
→
Accessories
(
→
►
Connect the AC1154 with the ASi OUT (X22) port using the Y cable EVC844.
►
Connect the Y cable EVC844 to 24 V DC (20...30 V SELV/PELV)
►
Make sure the Y cable is properly connected!
►
Connect AC6000 with the addressing unit.
►
Assign a free AS-i address to the AC6000.
►
Connect the addressed AC6000 with the AS-i network.
>
AS-i master shows configuration error.
►
Re-configure the AS-i network.
>
AC6000 has a valid AS-i address.
>
AS-i master switches to operating mode "Protected mode".
>