SmartPLC SafeLine with PROFIBUS slave interface
155
10.1.7
Interfaces
42307
Inputs (local I/O interface)
Number
4 (two channels, safe)
8 (one channel, non safe)
Circuits
DC PNP (type 2 to IEC 61131-2)
Sensor supply
to SELV/PELV
Voltage range [V]
24 DC (18...32 DC)
Input current [mA]
7
Outputs (local I/O interface)
Number
2 (two channels, safe)
4 (one channel, safe)
4 (one channel, non safe)
Circuits
Transistor PNP
Voltage range [V]
24 DC (18...32 DC)
External supply
to SELV/PELV
Max. current load per output [mA]
500
Max. inductance [mH]
400
Max. switching frequency [Hz]
25
Utilisation category
DC-13
Electrically isolated
yes
Short-circuit proof
yes
42307
EtherNet configuration interface
Connection
2x RJ45
Transmission
10/100 Mbits/s
Protocol
HTTP, FTP, Telnet
42307
Profibus fieldbus interface
Connection
Sub-D socket, 9-pole
Transmission rate
9.6 kbaud ... 12 Mbaud
Profibus frame length
IN = 244 Bytes
OUT = 244 Bytes
Protocol
Profibus DP (DPV0 + DPV1), EN50170
Services and data
Acyclic Profibus services including AS-i command channel
Profibus I&M data (Identification and Maintenance)
GSD file
42307
SD card slot
Media
SD memory cards (max. 32 Gbytes)
Format
SDHC format is supported
Supported file formats
FAT32
>
10.1.8
AS-interface
42241
AS-interface
Number of AS-i master
2