11 Standards
The following standards and directives have been applied:
• Machinery Directive 2006/42/EC
• EN ISO 13849-1: 2008
• EN ISO 13850: 2008
• AS/NSZ 4024.1 - 2014
• IEC / EN 60947-5-1: 2004: +A1: 2009
• IEC / EN 60947-5-5: 1998 + A11: 2013
• UL 508
The device must be supplied from an electrically isolated source having a secondary
UL-listed fuse rated as noted in the following table.
Overcurrent protection
Wire cross section control circuit
Maximum nominal current of the protective
equipment
ampere
Evaluation unit
(mm
2
)
26
(0.13)
1
24
(0.20)
2
22
(0.32)
3
20
(0.52)
5
18
(0.82)
7
16
(1.3)
10
Hints for AS4024.3610-3614
Information with regard to AS4024-2014:
1) Perpendicular force to operate the switches midway between eyebolt
Supports: Check <70N. rope deflection <300mm
2) Axial force - direct along rope axis: <230N (Typical 125N).
Typical parameters for successful operation of a system is less than 70N pulling force
with less than 150mm deflection of rope between eyebolt supports. This can normally
be achieved with rope switches set to the mid position between the green arrows in
the viewing window. If required, depending upon the necessary checks along the
active length of coverage, the tension can be increased further beyond the mid
position to ensure a tripping pulling force of less than 70N.