background image

13

UK

After LED 0 has been reached the cycle of the flashing LED starts again at 

LED 9; the continuously lit LED (tens digit) moves one position to the left (when 

setting is made with 

)�

        

        

5 s after the last press of the pushbutton the display returns to the tem-

perature and switch point display mode (step 1)� After another 5 s the unit 

returns to the operating mode with the newly set value�

7.6  Low-flow adjustment (optional)

If the unit is used in media other than water, you should additionally adapt the unit 

to the minimum flow� 

The following adjustment must only be carried out after the high-flow 

adjustment�

Proceed as follows:

 

► Let the minimum flow circulate in the installation or ensure flow standstill�

 

► Press 

 and keep it pressed�

 

> LED 0 lights, after approx� 5 s it flashes�

 

► Release the button� The unit adopts the new value and returns to the operating 

mode�

7.7  Configuration of the switching outputs (optional)

The unit is delivered as normally open� If necessary you can change the outputs to 

normally closed function� The setting applies to both outputs�

 

► Press 

 for at least 15 s�

 

> LED 0 lights, after approx� 5 s it flashes�

 

> After 10 s the current setting is displayed: LEDs 5���9 light orange (= outputs 

normally open)�

 

> After approx� 15 s LEDs 0���4 flash orange� 

 

► Release the button� The outputs are changed to normally closed function�
For a new changeover: repeat the operation�

Summary of Contents for SI5007

Page 1: ...Operating instructions Flow monitor SI5007 80000396 00 07 2014 UK ...

Page 2: ...ink 9 7 1 1 General information 9 7 1 2 Device specific information 10 7 1 3 Parameter setting tools 10 7 1 4 Adjustable parameters 10 7 2 Set up and settings for water 10 7 3 Change switch point SP1 for flow optional 11 7 4 High flow adjustment optional 11 7 5 Set switch point SP2 for temperature 12 7 6 Low flow adjustment optional 13 7 7 Configuration of the switching outputs optional 13 7 8 Res...

Page 3: ...ta 17 1 Preliminary note 1 1 Explanation of symbols Instructions Reaction result Cross reference Important note Non compliance can result in malfunction or interference Information Supplementary note LED lights green LED lights orange LED lights red LED flashes ...

Page 4: ... whether the measurement devices are suitable for the respective application lies with the operator The manufacturer assumes no liability for consequences of misuse by the operator Improper installation and use of the devices result in a loss of the warranty claims 3 Functions and features 3 1 Applications The unit monitors the flow and the temperature of liquid and gaseous media 3 2 Operating pri...

Page 5: ...witch point quick reaction with rising flow High switch point quick reaction with falling flow 3 3 Operating principle temperature monitoring The unit detects the current medium temperature and switches output OUT2 output OUT2 closed if medium temperature switch point SP2 output open if medium temperature SP2 This applies to the unit on delivery output normally open If necessary you can change the...

Page 6: ...on location General The sensor tip is to be completely sur rounded by the medium Immersion depth of the sensor mini mum 12 mm Recommended For horizontal pipes mounting from the side For vertical pipes mounting in the rising pipe Conditional Horizontal pipe mounting from the bot tom if the pipe is free from build up Horizontal pipe mounting from the top if the pipe is completely filled with medium ...

Page 7: ...rces of interference 4 3 Installation procedure Ensure that the system is free of pressure during installation Ensure that no media can leak at the mounting location during installa tion Grease the threads of the process connection 1 adapter 2 and nut 3 Note No grease must be applied to the sensor tip A Screw suitable adapter into the process connection Place the flow monitor onto the adapter and ...

Page 8: ...ation of electrical equipment must be adhered to Voltage supply according to EN 50178 SELV PELV Disconnect power Connect the unit as follows 2 L L 4 1 3 OUT1 OUT2 4 2 Pin 1 Ub Pin 2 OUT2 PNP switching signal for temperature monitoring Programming wire for remote setting Pin 3 Ub Pin 4 OUT1 PNP switching signal for flow monitoring IO Link ...

Page 9: ... tion If you change parameters during operation this will influence the function Ensure that there will be no malfunctions in your plant 7 1 IO Link 7 1 1 General information This unit has an IO Link communication interface which requires an IO Link capa ble module IO Link master for operation The IO Link interface enables direct access to the process and diagnostic data and provides the possibili...

Page 10: ...tput configuration OUT2 temperature Set_High Reading of the maximum flow 100 Set_Low Reading of the minimum flow 0 dS1 dr1 Switch on delay switch off delay for OUT1 dS2 dr2 Switch on delay switch off delay for OUT2 Loc Locks sensor operation to prevent unintentional maladjustment Can be reset on the unit 7 2 Set up and settings for water For media other than water 7 6 Low flow adjustment optional ...

Page 11: ... time of the unit is requested low switch point fast re sponse with rising flow high switch point fast response with falling flow Proceed as follows Press the button briefly The switch point LED flashes Press or as often as required Each press of the pushbutton shifts the LED by one position in the indicated direction If no pushbutton is pressed for 2 s the unit returns to the operating mode with ...

Page 12: ...ch point LED green if OUT OFF LED orange if OUT ON Briefly press again within 5 s The current setting of the switch point is indicated in steps of 1 C and can be changed Lit LED tens digit 10 times X C flash ing LED units digit X C Here 51 C LED green if OUT OFF LED orange if OUT ON In addition the current temperature is indicated in steps of 10 C by red LEDs Press or as often as required Each pre...

Page 13: ...er the high flow adjustment Proceed as follows Let the minimum flow circulate in the installation or ensure flow standstill Press and keep it pressed LED 0 lights after approx 5 s it flashes Release the button The unit adopts the new value and returns to the operating mode 7 7 Configuration of the switching outputs optional The unit is delivered as normally open If necessary you can change the out...

Page 14: ...low LED 7 switch point SP2 temperature LED 0 4 C output function NO not locked 7 9 Lock unlock the unit The unit can be locked electronically to prevent unintentional settings Press both setting buttons simultaneously for 10 s in the operating mode The indication goes out the unit locks or unlocks On delivery not locked 7 10 Switch on switch off delay The unit features an internal switch on switch...

Page 15: ...g of the switch point SP2 in steps of 10 C for approx 5 s Row of LEDs red current temperature T in C LED 0 0 1 0 2 0 3 0 9 T 0 9 10 19 20 29 30 39 90 99 LED green or orange current switch point SP2 in C LED 0 1 2 3 4 5 6 7 8 9 SP2 2 4 5 14 15 24 25 34 35 44 45 54 55 64 65 74 75 80 LED green if OUT OFF LED orange if OUT ON 8 2 Operating indicators Green LED bar current flow within the display range...

Page 16: ...y OFF LEDs go off when a button is pressed The active LEDs go off briefly when a button is pressed if an IO Link communication is active temporary locking or the sensor is permanently locked 7 9 After approx 0 6 seconds the last operating state is displayed 9 Troubleshooting If high flow adjustment 7 3 or low flow adjustment 7 6 is not possible all LEDs flash red The unit then returns to the opera...

Page 17: ... the sensor tip for build up from time to time Clean it using a soft cloth Stubborn build up e g lime can be removed using a common vinegar cleaning agent 11 Technical data Technical data and scale drawing at www ifm com More information at www ifm com ...

Reviews: