background image

6

6 Technical data

Operating voltage [V] .......................................................................................9,6 ... 32 DC

1)

Analogue output .................................................................................................. 4 ... 20 mA

Load [Ω] ...................................................................max. (UB - 9.6) x 50; 720 at UB = 24 V
Step response time analogue output [ms] ...........................................................................3

Characteristics deviation [%] ................................................. < ± 0.25 (BFSL) / < ± 0.5 (LS)

Repeatability [%]............................................................................................................< 0.1

Long-term stability  [% of value of measuring range / 6 months]..............................< ± 0.05

Temperature coefficients (TEMPCO) in the compensated temperature range 0 ... 80°C 

(in% of the span/10K)

2)

PA3220...PA3227

PA3228

greatest TEMPCO of the zero point

0.1

0.2

greatest TEMPCO of the span

0.2

0.3

Housing material............stainless steel (316S12); FPM (Viton); PA; EPDM/X (Santoprene) 

Materials (wetted parts) .............................stainless steel (303S22); ceramics; FPM (Viton) 

Operating temperature [°C] .................................................................................. -25 ... +80

Medium temperature [°C] ................................................................................... -25 ... +90

2)

Storage temperature [°C].................................................................................... -40 ... +100

Protection PA3220 ... PA3222 .........................................................................IP 68 / IP 69K

Protection PA3223 ... PA3228 ...................................................................................... IP 65

Protection class ..................................................................................................................III

Insulation resistance [MΩ] .........................................................................> 100 (500 V DC)

Shock resistance [g] ..............................................................50 (DIN / IEC 68-2-27, 11 ms)

Vibration resistance [g] .................................................20 (DIN / IEC 68-2-6, 10 - 2000 Hz)

EMC

EN 61000-4-2 ESD: ................................................................................. 4 kV CD / 8 kV AD

EN 61000-4-3 HF radiated: ....................................................................................... 30 V/m

EN 61000-4-4 Burst: ...................................................................................................... 2 kV

EN 61000-4-6 HF conducted: ........................................................................................ 10 V

radiation of interference  .....according to the automotive directive 2004/104/EC / CISPR25

noise immunity...............according to the automotive directive 2004/104/EC / ISO 11452-2

HF radiated .............................................................................................................. 100 V/m 

pulse resistance....................................................according to ISO7637-2 / severity level 3

1)

 to EN50178, SELV, PELV

2)

 -40...90°C upon request

BFSL = Best Fit Straight Line / LS = Limit Value Setting

More information at www.ifm.com

Summary of Contents for PA32xx Series

Page 1: ...Installation Instructions Electronic pressure sensor PA32xx 704091 01 08 2010 UK ...

Page 2: ...es 25 bar only after contacting the manufacturer ifm For units with cULus approval and the scope of validity cULus The device shall be supplied from an isolating transformer having a secondary Listed fuse rated as noted in the following table Overcurrent protection Control circuit wire size Maximum protective device rating Ampere AWG mm2 26 0 13 1 24 0 20 2 22 0 32 3 20 0 52 5 18 0 82 7 16 1 3 10 ...

Page 3: ...4 5 10 145 30 450 PA3228 0 0 25 0 3 63 10 145 30 450 MPa bar 10 kPa bar 100 Static and dynamic overpressures exceeding the indicated overload pressure are to be avoided by taking appropriate measures The indicated bursting pressure must not be exceeded Even if the bur sting pressure is exceeded only for a short time the unit can be destroyed NOTE Risk of injury Use in gases at pressures 25 bar onl...

Page 4: ...ten firmly 4 Electrical connection The unit must only be connected by an electrician The national and international regulations for the installation of electrical equipment must be observed Voltage supply to EN50178 SELV PELV Disconnect power Connect the unit as follows Core colours of ifm sockets 1 BN brown 2 WH white 3 BU blue 4 BK black n c not connected ...

Page 5: ...5 UK 5 Scale drawing PA3221 PA3228 PA3220 Dimensions are in millimeters ...

Page 6: ...ton Operating temperature C 25 80 Medium temperature C 25 902 Storage temperature C 40 100 Protection PA3220 PA3222 IP 68 IP 69K Protection PA3223 PA3228 IP 65 Protection class III Insulation resistance MΩ 100 500 V DC Shock resistance g 50 DIN IEC 68 2 27 11 ms Vibration resistance g 20 DIN IEC 68 2 6 10 2000 Hz EMC EN 61000 4 2 ESD 4 kV CD 8 kV AD EN 61000 4 3 HF radiated 30 V m EN 61000 4 4 Bur...