3

UK

2 Function and features

The pressure sensor detects the system pressure and converts it into an analog 

output signal. 
•  4 ... 20 mA

2.1 Applications

•  Type of pressure: relative pressure  

Order no.

Measuring range

Permissible

overload pressure

Bursting

pressure

bar

PSI

bar

PSI

bar

PSI

PA3220

0...400

0...5 800

600

8 700

1 000

14 500

PA3221

0...250

0...3 625

400

5 800

850

12 300

PA3222

0...100

0...1 450

300

4 350

650

9 400

PA3223

0...25

0...363

150

2 175

350

5 075

PA3224

0...10

0...145

75

1 087

150

2 175

PA3226

0..2.5

0...36.3

20

290

50

725

PA3227

0...1

0...14.5

10

145

30

450

PA3228

0...0.25

0...3.63

10

145

30

450

MPa = bar ÷ 10 / kPa = bar × 100

Static and dynamic overpressures exceeding the indicated overload 

pressure are to be avoided by taking appropriate measures.

The indicated bursting pressure must not be exceeded. Even if the bur-

sting pressure is exceeded only for a short time, the unit can be destroyed. 

NOTE: Risk of injury!

Use in gases at pressures > 25 bar only after contacting the manufacturer ifm.

High-pressure units (400 bar) are supplied with an integrated damping device to 

avoid any risk of injury in case of bursting when bursting pressure is exceeded.

When the damping device is removed it can become unusable.

If you have any questions, please contact ifm electronic‘s sales specialists.

Summary of Contents for PA32xx Series

Page 1: ...Installation Instructions Electronic pressure sensor PA32xx 704091 01 08 2010 UK ...

Page 2: ...es 25 bar only after contacting the manufacturer ifm For units with cULus approval and the scope of validity cULus The device shall be supplied from an isolating transformer having a secondary Listed fuse rated as noted in the following table Overcurrent protection Control circuit wire size Maximum protective device rating Ampere AWG mm2 26 0 13 1 24 0 20 2 22 0 32 3 20 0 52 5 18 0 82 7 16 1 3 10 ...

Page 3: ...4 5 10 145 30 450 PA3228 0 0 25 0 3 63 10 145 30 450 MPa bar 10 kPa bar 100 Static and dynamic overpressures exceeding the indicated overload pressure are to be avoided by taking appropriate measures The indicated bursting pressure must not be exceeded Even if the bur sting pressure is exceeded only for a short time the unit can be destroyed NOTE Risk of injury Use in gases at pressures 25 bar onl...

Page 4: ...ten firmly 4 Electrical connection The unit must only be connected by an electrician The national and international regulations for the installation of electrical equipment must be observed Voltage supply to EN50178 SELV PELV Disconnect power Connect the unit as follows Core colours of ifm sockets 1 BN brown 2 WH white 3 BU blue 4 BK black n c not connected ...

Page 5: ...5 UK 5 Scale drawing PA3221 PA3228 PA3220 Dimensions are in millimeters ...

Page 6: ...ton Operating temperature C 25 80 Medium temperature C 25 902 Storage temperature C 40 100 Protection PA3220 PA3222 IP 68 IP 69K Protection PA3223 PA3228 IP 65 Protection class III Insulation resistance MΩ 100 500 V DC Shock resistance g 50 DIN IEC 68 2 27 11 ms Vibration resistance g 20 DIN IEC 68 2 6 10 2000 Hz EMC EN 61000 4 2 ESD 4 kV CD 8 kV AD EN 61000 4 3 HF radiated 30 V m EN 61000 4 4 Bur...

Reviews: