Scaling of the analogue value for temperature
9.4.2
Select [SEL2] and set [TEMP]�
►
Select [OU2 ] and set the function:
►
[I] = current signal proportional to temperature (4…20 mA);
-
[U] = voltage signal proportional to temperature (0…10 V)�
-
Select [ASP] and set the value at which the minimum output value is
►
provided�
Select [AEP] and set the value at which the maximum output value is
►
provided�
User settings (optional)
9.5
Determine the standard unit of measurement for volumetric flow
9.5.1
Select [Uni] and set the unit of measurement: [Lmin] or [m3h]�
►
The setting only has an effect on the volumetric flow value� The counter
values (consumed quantity) are automatically displayed in the unit of meas-
urement providing the highest accuracy�
Configuration of the standard display
9.5.2
Select [SELd] and determine the standard process category�
►
[FLOW] = display shows the current volumetric flow value in the stand-
-
ard unit of measurement�
[TOTL] = display indicates the current meter count in l, m
-
3
or 1000 m
3
�
[TEMP] = display indicates the current medium temperature in °C�
-
Select [diS] and determine the update rate and orientation of the display:
►
[d1] = update of the measured values every 500 ms�
-
[d2] = update of the measured values every 1000 ms�
-
[d3] = update of the measured values every 2000 ms�
-
[rd1], [rd2], [rd3] = display as for d1, d2, d3; rotated by 180°�
-
[OFF] = the display is switched off in the operating mode�
-
Setting the output logic
9.5.3
Select [P-n] and set [PnP] or [nPn]�
►
Setting the start-up delay
9.5.4
Select [dSt] and set the numerical value in seconds�
►
Setting the damping of the measured values
9.5.5
Select [dAP] and the damping constant in seconds (t value 63 %)�
►