22
Settings for quantity monitoring using the preset meter
9.3.2
Select [OU1] and set [ImP]�
►
Select [ImPS] and set the volumetric flow quantity at which output 1
►
switches (→ 9.7).
Select [ImPR] and set [no]: pulse repetition is not active� The output
►
switches ON if the value set in [ImPS] is reached� It remains switched
until the meter is reset�
Settings for meter reset controlled by the program
9.3.3
Select [rTO] and continue with a) or b)�
►
a) Reset the meter manually: press [Set] until [rES�T] is displayed�
Press [Mode/Enter] briefly�
b) Enter the value for time-controlled reset: Press [Set] until the re-
quested value is displayed (intervals from 1 hour to 8 weeks)�
Press [Mode/Enter] briefly�
►
Switch off the meter reset
9.3.4
Select [rTO] and set [OFF]� The meter is only reset after overflow
►
(= factory setting)�
Settings for meter reset by an external signal
9.3.5
Select [OU2] and then [InD]�
►
Select [Din2] and set the reset signal:
►
[Hi] = reset for high signal,
-
[Lo] = reset for low signal,
-
[+EDG] = reset for rising edge,
-
[-EDG] = reset for falling edge�
-
Settings for temperature monitoring
9.4
Settings for limit value monitoring with OUT2
9.4.1
Select [SEL2] and set [TEMP]�
►
Select [OU2] and set the switching function:
►
[Hno] = hysteresis function/normally open,
-
[Hnc] = hysteresis function/normally closed,
-
[Fno] = window function/normally open,
-
[Fnc] = window function/normally closed�
-
Select [SP2] and set the value at which the output switches�
►
Select [rP2] and set the value at which the output switches back�
►