Adjustment of the valve positions of valves with 3 operating positions
25
1
Press the Pos.
pushbutton for min. 2s.
All LEDs
flash
2x
simultaneously.
The unit is in the programming
mode.Then only the LED "
closed
" is lit.
The unit is now ready for the adjustment
of the
closed
position.
2
Put the valve into the
closed
Pos. and press
the Teach button.
The LED "closed" goes out
and the LED "
seat
" lights.
The unit has stored the closed position
and is now ready for the adjustment
of the position
seat lift (seat)
.
3
Put the valve into the
position
seat lift
and
press the Teach button.
The LED "seat" goes out
and the LED "
open
" lights.
The unit has stored the position seat lift
and is now ready for the adjustment
of the
open
position.
4
Put the valve into the
open
position and
press the Teach button.
The LED "open" goes out
and the LED "
closed
" lights again.
The unit has now stored all positions.
5
Press the Pos.
pushbutton for
min. 5s.
After 5s the LED
"open" flashes at
about 2Hz.
After releasing all stored measured values
are checked. If no errors are detected
all
LEDs
flash
2x
simultaneously. The unit
automatically quits the programming
mode and immediately passes into the
operating mode.
If, however, an error is found during the
check the LED "
closed
"
flashes
at about
8Hz. Acknowledge the error message by
pressing the Pos. button and repeat the
adjustment.
Summary of Contents for efector180 IX5010
Page 4: ...Nicht zulässige Formen und Abmaße des Targets 4 Ø24mm 5mm Ø24mm 10mm Ø24mm 10mm Ø24mm 10mm ...
Page 18: ...Non permissible shapes of the target 18 Ø24mm 5mm Ø24mm 10mm Ø24mm 10mm Ø24mm 10mm ...
Page 32: ...Formes et dimensions non permises de la cible 32 Ø24mm 5mm Ø24mm 10mm Ø24mm 10mm Ø24mm 10mm ...