Adjustment of the valve positions of valves with 2 operating positions
24
1
Press the Pos. pushbut-
ton for at least 2s.
All LEDs
flash
2x
simultaneously.
The unit is in the programming mode.
Then only the LED "
closed
" is lit.
The unit is now ready for the adjustment
of the
closed
position.
2
Close
the valve and
press the Teach button.
The LED "closed" goes out
and the LED "
seat
" lights.
The unit has stored the closed position
and is now ready for the adjustment of
the position
seat lift (seat)
.
3
Press the Pos. button
once, thus skipping the
current program step.
This is necessary
because your valve
does
not
have the
position "seat lift".
The LED "
open
" lights.
The unit is now ready for the
adjustment of the
open
position.
4
Put the valve into the
open
position and
press the Teach button.
The LED "open" goes out
and the LED "
closed
" lights again.
The unit has stored all positions now.
5
Press the Pos. pushbut-
ton for at least 5s.
After 5s the LED
"open" flashes at
about 2 Hz.
After releasing all stored measured values
are checked. If no errors are detected
all
LEDs
flash
2x
simultaneously. The unit
automatically quits the programming
mode and immediately passes into the
operating mode.
If, however, an error is found during the
check the LED "
closed
"
flashes
at about
8Hz. Acknowledge the error message by
pressing the Pos. button and repeat the