• The sensor
detects
the
level of media
in vessels within the active
zone,
• shows the current level on its
display
• and generates
2 output signals
according to the set output con-
figuration.
The area between the bottom of the vessel and the lower face of the
measuring probe can be entered as offset value. Thus the display and
the switch points refer to the real vessel level.
Measuring range
Offset
Seite 19
ENGLISH
hysteresis function / N.O. (
Hno
)
analog 4 ... 20 mA (
I
)
analog 0 ... 10 V (
U
)
hysteresis function / N.C. (
Hnc
)
window function / N.O. (
Fno
)
window function / N.C. (
Fnc
)
output 1
output 2
A
L
I
min
OFS
max
min
max
measur
ed /
display
value
LK3024
LK3023
LK3022
cm
26.4
47.2
72.8
10.4
18.6
28.7
L = probe length
inch
cm
19.5
39.0
58.5
7.7
15.4
23.0
A = active zone/ measuring range
inch
cm
5.3
5.3
10.2
2.0
2.0
4.0
I
= inactive zone
inch
cm
1.5*
3.0*
4.0*
0.6*
1.2*
1.6*
min = lowest measured value
inch
cm
21.0*
42.0*
62.0*
8.3*
16.6*
24.4*
max = highest measured value
inch
cm
0 ... 78.0
0 ... 57.0
0 ... 186
0 ... 30.7
0 ... 22.5
0 ... 73.2
OFS = offset
inch
*With offset > 0 the OFS value is added to these values.
factory setting: OFS = 0
Function and features