1 Functions and features
The unit detects the system temperature in machines and installations.
2 Function
The unit generates 2 output signals: 1 x NO + 1 x NC with separately adjustable
switch points [SET1] and [SET2].
OUT1
With rising temperature OUT1 closes when the set value [SET1] is reached.
With falling temperature OUT1 opens, when the value [SET1] minus 2 K is
reached.
OUT2
With rising temperature OUT2 opens when the set value [SET2] is reached.
With falling temperature OUT2 closes, when the value [SET2] minus 5 K is
reached.
Measuring range: 0 ... 100 °C / 32 ... 212 °F.
•
Measuring element: Pt 1000 according to DIN EN 60751, class B.
•
3 Mounting
Make sure that there is no medium flowing through the system before
mounting and removing the unit.
Insert the unit in a G½ process connection.
►
Tighten firmly.
►
4 Electrical connection
The unit must be connected by a qualified electrician.
The national and international regulations for the installation of electrical
equipment must be adhered to.
Operating voltage „supply class 2“ to cULus.
Disconnect power.
►
Connect the unit as indicated on the type label.
►