2

1 Functions and features

The unit detects the system temperature in machines and  installations.

2 Function

The unit generates 2 output signals: 1 x NO + 1 x NC with separately adjustable 

switch points [SET1] and [SET2].

OUT1

With rising temperature OUT1 closes when the set value [SET1] is reached.
With falling temperature OUT1 opens, when the value [SET1] minus 2 K is 

reached.

OUT2

With rising temperature OUT2 opens when the set value [SET2] is reached.
With falling temperature OUT2 closes, when the value [SET2] minus 5 K is 

reached.

Measuring range: 0 ... 100 °C / 32 ... 212 °F.

• 

Measuring element:  Pt 1000 according to DIN EN 60751, class B.

• 

3 Mounting

Make sure that there is no medium flowing through the system before 

mounting and removing the unit.

Insert the unit in a G½ process connection.

 

Tighten firmly.

 

4 Electrical connection

The unit must be connected by a qualified electrician.

The national and international regulations for the installation of electrical 

equipment must be adhered to.

Operating voltage „supply class 2“ to cULus.

Disconnect power.

 

Connect the unit as indicated on the type label.

 