9.2 Scaling of the analogue value for temperature
► Select [ASP1] and set the value at which 4 mA is provided�
► Select [AEP1] and set the value at which 20 mA is provided�
9.3 Scaling of the analogue value for volumetric flow
► Select [ASP2] and set the value at which 4 mA is provided�
► Select [AEP2] and set the value at which 20 mA is provided�
9.4 User settings (optional)
9.4.1 Determine the standard unit of measurement for volumetric flow
► Select [Uni�F] and set the unit of measurement::
[Lmin], [m3h], [GPm] or [GPh]�
9.4.2 Determine the standard unit of measurement for temperature
► Select [Uni�T] and set the unit of measurement: [°C] or [°F]�
9.4.3 Configuration of the standard display
► Select [SELd] and determine the standard process category�
[FLOW] = display shows the current volumetric flow value in the stand-
ard unit of measurement�
[TOTL] = display indicates the current meter count in l, m
3
or 1000 m
3
�
[TEMP] = display indicates the current medium temperature in °C�
► Select [diS] and determine the update rate and orientation of the display:
[d1] = update of the measured values every 500 ms�
[d2] = update of the measured values every 1000 ms�
[d3] = update of the measured values every 2000 ms�
[rd1], [rd2], [rd3] = display as for d1, d2, d3; rotated by 180°�
[OFF] = the display is switched off in the operating mode�
9.4.4 Calibration of the curve of measured values for volumetric flow
► Select [CGA] and set the value between 60 % und 140 % einstellen
(100 % = factory preset)�
9.4.5 Calibration reset
► [Select [CAr]�
► Press [Set] and keep it pressed until [----] is displayed�
► Press [Mode/Enter] briefly�
> Value is reset (CGA = 100)�