15

UK

•  Change from menu level 1 to menu level 2

 

► Press [Mode/Enter] until [EF] is 

displayed�

 

► Press [Set] briefly�

 

> The first parameter of the sub-menu 

is displayed (here: [HI�F])�

•  Locking / unlocking

The unit can be locked electronically to prevent unintentional wrong settings�

 

► Make sure that the unit is in the 

normal operating mode�

 

► Press [Mode/Enter] + [Set] for 10 s�

 

> [Loc] is displayed�

During operation: [Loc] is briefly displayed if you try to change parameter values�

 

► Press [Mode/Enter] + [Set] for 10 s�

 

> [uLoc] is displayed�

When delivered: unlocked�

•  Time out:

If during parameter setting no pushbutton is pressed for 15 s, the unit exits the param-

eter setting mode� The parameter value is not changed�

For medium temperatures over 50 °C (122 °F) some parts of the housing 

can heat up to over 65 °C (140 °F)� 

In this case do not press the pushbuttons manually; instead use an object�

Summary of Contents for efector 300 SU9004

Page 1: ...Operating instructions Ultrasonic flow rate sensor SU9004 704645 01 09 2010 UK...

Page 2: ...7 Operating and display elements 11 8 Menu 12 8 1 Menu structure 12 8 2 Explanation of the menu 13 9 Parameter setting 14 9 1 General parameter setting 14 9 2 Scaling of the analogue value for tempera...

Page 3: ...eading the min max values for temperature 17 9 5 3 Reset all parameters to the factory setting 18 10 Operation 18 10 1 Read the set parameters 18 10 2 Changing the display unit in the Run mode 18 10 3...

Page 4: ...electrical connection set up operation and mainte nance of the unit must be carried out by qualified personnel authorised by the plant operator In all applications test the compatibility of the produc...

Page 5: ...c flow monitoring The flow rate is monitored by an ultrasonic meter the measured signals by the electronics An analogue signal proportional to the volumetric flow 4 20 mA is provided on output 2 For t...

Page 6: ...omer specific calibration This calibration changes the slope of the curve of measured values for volumetric flow It influences the display and the outputs A operating value for display and output sign...

Page 7: ...he unit so that the measuring pipe is always completely filled Arrange for inlet and outlet pipe lengths Disturbances caused by bends valves reductions etc are compensated for It applies in particular...

Page 8: ...tion locations Directly in front of a falling pipe In a falling pipe F flow direction At the highest point of the pipe system Directly in front of the spout of a pipe F flow direction On the suction s...

Page 9: ...e to be ordered sepa rately as accessories Order no E40205 2 adapters G 1 for 1 pipes stainless steel 2 seals 1 Screw the adapter B into the pipe A 2 Place the seals C and install the unit according t...

Page 10: ...unit must be connected by a qualified electrician The national and international regulations for the installation of electrical equipment must be adhered to Voltage supply to EN50178 SELV PELV Discon...

Page 11: ...ium temperature in F LED 7 LED 8 not used 9 Alphanumeric display 4 digits indication of the current volumetric flow if SELd FLOW is set indication of the current medium temperature if SELd TEMP is set...

Page 12: ...12 8 Menu 8 1 Menu structure Mode Enter Set In the Run mode different display units are accessible depending on the setting of the parameters SELd Uni F and Uni T 10 2...

Page 13: ...ve of measured values for volumetric flow CAr Calibration reset FOU1 Behaviour of output 1 in case of an internal fault FOU2 Behaviour of output 2 in case of an internal fault dAP Measured value dampi...

Page 14: ...eter flashes for 5 s After 5 s The setting value is changed incremental by press ing briefly or scrolling by holding pressed Numerical values are incremented continuously If the value is to be reduced...

Page 15: ...ress Mode Enter Set for 10 s Loc is displayed During operation Loc is briefly displayed if you try to change parameter values Press Mode Enter Set for 10 s uLoc is displayed When delivered unlocked Ti...

Page 16: ...SELd and determine the standard process category FLOW display shows the current volumetric flow value in the stand ard unit of measurement TOTL display indicates the current meter count in l m3 or 10...

Page 17: ...Water GLYC Glycol solutions OIL Oils 9 5 Service Funktionen 9 5 1 Reading the min max values for volumetric flow Select HI F or LO F and press Set briefly HI F maximum value LO F minimum value Delete...

Page 18: ...uring the power on delay time 10 1 Read the set parameters Press Mode Enter until the requested parameter is displayed Press Set briefly The unit displays the corresponding parameter value After about...

Page 19: ...e displayed IOE Flow sensor faulty Loc Setting pushbuttons locked parameter change rejected VMR final value of the measuring range 10 4 General operating conditions Avoid deposits accumulated gas and...

Page 20: ...e in millimeters 12 Technical data Applications liquids water glycol solutions oils Operating voltage V 19 30 DC1 Current consumption mA 100 24 V Analogue output 4 20 mA measuring range scaleable Max...

Page 21: ...3487 Response time ms 250 dAP 0 Damping flow signal dAP s 0 0 1 0 Start up delay s 0 50 Accuracy water 3 MV 0 2 MVR glycol solutions 35 8 MV 0 5 MVR oils viscosity 68 mm s at 40 C 8 MV 0 5 MVR Repeat...

Page 22: ...DIN IEC 68 2 27 11ms Vibration resistance g 5 DIN IEC 68 2 6 55 2000 Hz EMC IEC 1000 4 2 ESD 4 8 KV IEC 1000 4 3 HF radiated 10 V m IEC 1000 4 4 Burst 2 KV IEC 1000 4 5 Surge 0 5 1 KV IEC 1000 4 6 HF...

Page 23: ...UK 13 Factory setting Factory setting User setting ASP1 10 0 AEP1 80 0 ASP2 0 0 AEP2 200 0 CGA 100 FOU1 OFF FOU2 OFF dAP 0 6 diS d2 Uni F Lmin Uni T C SELd FLOW MEDI H2O More information at www ifm c...