39
ifm
Device Manual IO-Link Master with PROFINET interface CabinetLine 8 Ports IP 20 (AL1900)
05 / 2018
Configuration
PROFINET
>
8.2.4
Configure IO-Link ports
17306
In STEP 7, the following assignment of the PROFINET slots to the IO-Link ports of the device applies:
Slot
Subslot
IO Link port of AL1900
1
2
X01
3
X02
...
...
9
X08
Each sub-slot can be configured for cyclic transmission of process data with a PROFINET module.
The selected PROFINET module determines the operation type of the IO-link interface and the
configurable parameters.
Overview of the available PROFINET modules:
→
PROFINET modules
(
To add a PROFINET module to a sub-slot:
1 Open device editor
►
In "HW Config": Click on IO-Link master.
>
The device editor shows the current configuration of the IO-Link master.
2 Add PROFINET module
►
Open hardware catalogue.
►
Drag and drop the required PROFINET module of the IO-Link master from the hardware catalogue to the slot.
>
The device editor shows the slot with the selected PROFINET module.
3 Set parameters of the PROFINET module
►
Double click on the added slot.
>
Window [Properties] appears.
►
Select [Paramerters] tab.
>
The page shows the current parameter settings of the IO-Link ports.
►
Set the parameters as required (marked with X in table):
Operating mode of the IO-Link
ports
Available parameters
Fail Safe
Mode
Pattern
Value
Validation /
Data
storage
Vendor
ID (VID)
Device ID
Port cycle
time
IO-Link
Events
DI: Digital input
--
--
--
--
--
--
X
DO: Digital output
X
--
--
--
--
--
X
IO-Link: Input
--
--
X
X
X
X
X
IO-Link: Output
X
X
X
X
X
X
X
IO-Link: Input and output
X
X
X
X
X
X
X
Further information about the parameters of the PROFINET modules:
→
Parameters of the
IO-Link ports
(
►
Click on [OK] to save the changes.
>
Changed settings are applied.
>