Device Manual IO-Link Master with PROFINET interface CabinetLine 8 Ports IP 20 (AL1900)
05 / 2018
Mounting
Install the device
5
Mounting
Install the device .....................................................................................................................................13
22016
>
5.1
Install the device
16676
► Disconnect power before installation.
The device contains components that can be damaged or destroyed by electrostatic
discharge.
► When handling the device, observe the necessary safety precautions against electrostatic
discharge (ESD).
► Only operate the device when mounted on a grounded DIN rail.
► Install the device in a control cabinet of protection rating IP 54 or higher. The control cabinet has
to be installed in accordance with local and national regulations.
► Fix the device vertically onto a 35 mm raised rail.
► Leave enough space between the unit and the top or bottom of the control cabinet as well as to
adjacent devices to enable air circulation and to avoid inadmissible heating.