36
ifm
Device Manual IO-Link Master with PROFINET interface CabinetLine 8 Ports IP 20 (AL1900)
05 / 2018
Configuration
PROFINET
>
8.2.2
Add the IO-Link master to the PROFINET network
22406
The configuration of the PROFINET parameters is done via the PROFINET projection software.
The PROFINET parameters define which data is transmitted between AL1900 and the higher-level
PROFINET controller.
Requirements:
>
PROFINET has read and write permission on the AL1900 (→
IoT: Configure access rights
>
The GSD file of the AL1900 is installed (→
Install GSD file
1 Create/open project
►
Create new PROFINET project.
OR
Open an existing PROFINET project.
►
Configure PROFINET connection.
2 Add the IO-Link master to project
►
Open STEP-7 application "HW Config".
>
Program window shows the hardware structure of the project.
►
Open hardware catalogue.
►
Move the [AL1900] node via drag&drop from the hardware catalogue to the PROFINET connection.
>
STEP 7 shows the device as PROFINET bus participant.