46
ifm
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1300)
05 / 2018
Configuration
IoT Core
8.3.6
Read / write cyclic process data
10994
Cyclic process data of the IO-Link ports X01...X04 is saved in the
iolinkmaster/port[n]
substructure. The user can access the following data points:
Name
Description
Access
iolinkmaster/port[n]/pin2in
Digital input signal to pin 2 of the IO-Link port n
r
iolinkmaster/port[n]/iolinkdevice/pdin
IO-Link input signal at pin 4 of the IO-Link port n
r
iolinkmaster/port[n]/iolinkdevice/pdout
IO-Link output signal at pin 4 of the IO-Link port n
rw*
n ... 1...4
r = read only
rw ... read and write
* ... only available if PROFINET PLC is separated from the device
>
8.3.7
Read diagnostic data
16571
Diagnostic data is saved in the
processdatamaster
substructure. The user can access the following
data points:
Name
Description
Access
processdatamaster/temperature
Temperature of the IO-Link master (value in °C)
r
processdatamaster/voltage
Voltage applied (value in V)
r
processdatamaster/current
Current (value in A)
r
processdatamaster/supervisionstatus
Diagnostic information of the device supply
0 = no error
1 = short circuit
2 = overload
3 = undervoltage
r
r = read only
>
8.3.8
Control IO-Link master
17963
The device can be controlled via the following services:
Service
Description
Access
firmware/version
Firmware version of the IO-Link master
r
firmware/reboot
Reboot IO-Link master
rw
firmware/signal
Identify IO-Link master
rw
firmware/factoryreset
Reset IO-Link master to factory settings
rw
r ... read only
rw ... read and write