Configure IO-Link ports
16454
Parameters of the IO-Link ports of the IO-Link master are saved in the
iolinkmaster/port[n]
substructure. There are the following data points for each IO-Link-Port X01...X04 :
Name
Description
Access
iolinkmaster/port[n]/senddatatosmob
Send process data to LR SMARTOBSERVER
rw
iolinkmaster/port[n]/mastercycletime_preset
Cycle time of the data transfer at the IO-Link port (value in
microseconds)
rw
iolinkmaster/port[n]/mastercycletime_actual
Current cycle time of the data transfer at the IO-Link port
(value in microseconds)
r
iolinkmaster/port[n]/portevent
Activity indication
rw
iolinkmaster/port[n]/mode
Operating mode of the IO-Link port
rw*
iolinkmaster/port[n]/comspeed
Data transfer rate of the IO-Link port
rw
iolinkmaster/port[n]/validation_datastorage_mode
Response of the IO-Link port when a new IO-Link device is
connected
rw*
iolinkmaster/port[n]/validation_vendorid
IO-Link ID of the manufacturer that is to be validated
rw*
iolinkmaster/port[n]/validation_deviceid
IO-Link ID of the device that is to be validated
rw*
n ... 1...4)
r = read only
rw ... read and write
* ... only available if PROFINET PLC is separated from the device
>
8.3.4
Configure IO-Link devices
11002
The ifm IoT Core supports the configuration of the connected IO-Link devices. A parameter is
accessed via IO-Link index and subindex (
→ IO Device Description (IODD) of the device)
The user can use the following services:
Service
Description
Access
iolinkmaster/port[n]/iolinkdevice/iolreadacyclic
Acyclic reading of a parameter of an IO-Link device
r
iolinkmaster/port[n]/iolinkdevice/iolwriteacyclic
Acyclic writing of a parameter of an IO-Link device
rw
n ... 1...4
r = read only
rw ... read and write
>
8.3.5
Set application identification
16580
The application name of the IO-Link master is saved in the
devicetag
substructure. The user can
access the following data points:
Name
Description
Access
devicetag/applicationtag
Name of the IO-Link master in the fieldbus project
(application tag)
rw
rw ... read and write
>