device manual AS-i DP-Gateway
The first module for example defines the number of binary I/O data bytes of single or A slaves of AS-i
master 1 in the AS-i DP -Gateway which are to be transferred to the Profibus master via Profibus DP.
The maximum data length of all 11 modules must not exceed 156 input bytes and 156 output bytes.
For the advanced Profibus DP user it is also possible to use other length codes than those given as
long as the respective maximum lengths of the modules are not exceeded.
When using the single master AC1325, modules which refer to master 2 are to be configured using
spaces as placeholders.
Configuration
example
AC1335
Configuration example AC1326
Module1:
Content
:
binary inputs and outputs of Single- or A-slaves of AS-i master 1
Length
:
0..16 Byte I/O (=0 if not used)
Byte No.
Bits 4..7
Bits 0..3
1 flags
master
1
Slave1(a)
2 Slave2(a)
Slave3(a)
..
15 Slave28(a)
Slave29(a)
16 Slave30(a)
Slave31(a)
5-16