www.ies-synergy.com
Installation Manual
DIM016055-EN
30
The connecting point of the unit shall be protected by
a tripolar main circuit breaker 80A (MCB curve C or
equivalent) and an RCD type B having a rated residual
operating current not exceeding 30mA
Wiring should be at minimum 4x16mm² with a min-
imum temperature rating of 70°C copper wire. Ca-
ble external diameter must be between 18mm and
25mm. Make sure than the ground conductor is lon-
ger than the phases conductors.
1. Remove 15mm of insulation from the end to the
power cable to be connected to the internal circuit
breaker
2. Connect ground wire to the AC input configuration
board
- position 1
3. Connect each phase to the AC input configuration
board
- position 2
3- phase P1/P2/P3 + GND 3x208-240V
AC
5B
The connecting point of the unit shall be protected by
a tetrapolar main circuit breaker 50A (MCB curve C or
equivalent) and an RCD type A having a rated residual
operating current not exceeding 30mA.
Wiring should be at minimum 5x16mm² with a min-
imum temperature rating of 70°C copper wire. Ca-
ble external diameter must be between 18mm and
25mm. Make sure than the ground conductor is lon-
ger than the phases conductors.
1. Remove 15mm of insulation from the end to the
power cable to be connected to the internal circuit
breaker
2. Connect ground wire to the AC input configuration
board
- position 1
3. Connect neutral to the AC input configuration
board
- position 2
4. Connect each phase to the AC input configuration
board
- position 3
3-phase P1/P2/P3 + N + GND 3x380-480V
AC
5A
Summary of Contents for Wallbox G3
Page 1: ...Installation Manual for Wallbox G3 www ies synergy com DIM016055 EN_V002 ...
Page 37: ...www ies synergy com Installation Manual DIM016055 EN 37 Notes ...
Page 38: ...www ies synergy com Installation Manual DIM016055 EN 38 Notes ...
Page 39: ...www ies synergy com Installation Manual DIM016055 EN 39 Notes ...