background image

6

 The circuit breaker allows voltage supply from the power source both from 

the side of terminals 1, 3, 5 and from the side of terminals 2, 4, 6.

The circuit breaker is a repairable product. It is necessary to periodically 

(at least once a year) check the tightness of the connection screws. After each 
disconnection of the short-circuit current, it is necessary to inspect the circuit 
breaker and, in addition, it is recommended to perform the "on-off" operation 
8–10 times without current, then simulate the automatic operation of the circuit 
breaker by pressing the "Test" button.

In case of circuit breaker failure or failure detection, contact the 

organizations specified below.

Connection of both copper and aluminum conductors is allowed. It is 
recommended to use lugs together with flexible conductors (not included in the 
delivery set). The dimensions of the connected lugs and busbars should 
correspond to those presented in figures 5, 6, 7 and tables 6, 7, 9. The size of the 
core to be crimped (crimped) with the help of the lug should be selected taking 
into account the requirements of BCH 13983.

The normal operating position of the circuit breaker in space is on a vertical 

plane with terminals 1, 3, 5 upwards; installation on a vertical plane with the 
rotation of terminals 1, 3, 5 to the left or right by 90

°

 is allowed.

The circuit breaker should not be disposed as household waste. For 

disposal, transfer to a specialized recycling company.

Basic insulation is a precautionary measure for basic protection against 

electric shock, and no protection against damage is provided.

Transportation of the circuit breaker is allowed by any kind of covered 

transport in the manufacturer's package, which protects the packed circuit 
breaker from mechanical damages, pollution and moisture ingress at 
temperatures from minus 40 

°

C to plus 60 

°

C.

The control handle of the circuit breaker has three positions: "ON", "OFF", 

middle position. At the first turn-on and after the protective shutdown (including 
when the shunt and undervoltage release trips), to close the main contact group 
of the circuit-breaker, it is necessary to move the handle from the middle position, 
first to the "OFF" position, then to the "ON" position.

At the end of its service life, the circuit breaker should be disposed of.

 The circuit breaker design contains an in-service inspection device 

 the 

"Test" button, when pressing, the main contact group is reset (in this case, the 
control handle of the circuit breaker will take the middle position).

Transportation, storage and disposal

 The interphase baffles included in the delivery set should be installed in the 

corresponding grooves during the installation of external conductors.

Storage of the circuit breaker is carried out in the manufacturer's package in 

rooms with natural ventilation at an ambient temperature of from 

40 

°

C to +60 

°

and relative humidity up to 50

 

% at a temperature of +40 

°

C, it is allowed to store 

the circuit breaker at a relative humidity of 90

 

% and a temperature of plus 20 

°

C.

K

ARA

T

Summary of Contents for BA88-31

Page 1: ...17516 1 IEC 60947 2 50 40 90 20 IP30 14254 IEC 60529 IP00 2000 5000 1 004 2011 037 2016 IEC 60947 2 IEC 60947 7 3 3 15150 40 60 88 MASTER IEK 30 690 50 IEC 60947 1 A B 3 IEC 60947 1 1 88 MASTER RU KAR...

Page 2: ...2 10 IR 3 4 1 20 2 5 2 7 88 3 5 1 5 6 40 C 2 4 6 5 6 7 6 7 9 13983 KARAT...

Page 3: ...3 10434 17441 1 3 5 1 3 5 90 1 3 5 2 4 6 23216 4 2 15150 8 10 40 C 60 C KARAT...

Page 4: ...aker can be operated under the following conditions operating temperature range from minus 40 to plus 60 environment condition group according to IEC 60947 1 A B utilization category according to IEC...

Page 5: ...uit diagram of the circuit breaker is shown in figure 6 The circuit breaker is installed on a metal panel with a thickness of at least 1 5 mm or an insulating panel with a thickness of at least 6 mm a...

Page 6: ...fer to a specialized recycling company Basic insulation is a precautionary measure for basic protection against electric shock and no protection against damage is provided Transportation of the circui...

Page 7: ...arameter denomination Value Base altitude m 2000 3000 4000 5000 Correction factor of operating current 1 0 94 0 88 0 83 Table 2 Parameter denomination Value for circuit breaker of following type 88 31...

Page 8: ...8 8 8 10 10 Weight kg maximum 0 78 1 4 1 71 5 48 9 9 Continuation of table 2 Table 3 Test current Tripping or non tripping time depending on the setting of thermal releases Requited result I 63 R I 63...

Page 9: ...nductors set 1 1 1 1 1 Fasteners for mounting on a mounting plate set 1 1 1 1 1 Denomination 88 31 88 32 88 35 88 37 88 40 Mounting plate of plug in type 1 125 1 250 1 400 630 1 630 800 Mechanical int...

Page 10: ...7 35 24 35 98 69 4 5 88 37 257 465 224 194 150 48 33 44 150 99 8 88 40 281 496 243 243 210 70 45 70 155 103 7 1 Figure 1 Overall and mounting dimensions of circuit breakers b a L D1 D2 W H c a For cen...

Page 11: ...the rated current on the ambient temperature Rated current Environmental temperature C 0 25 0 25 32 125 88 31 88 32 88 35 Rated current Environmental temperature C Rated current Environmental temperat...

Page 12: ...ng time sec 88 35 Time current characteristics of A88 35 circuit breakers Operating time sec 88 37 Time current characteristics of A88 37 circuit breakers Operating time sec 88 40 ime current characte...

Page 13: ...agnetic release B C H H H 1 3 2 1 Non insulated connection 2 Insulated cable 3 Cable lugs D KARAT Minimum distance between the centers of two horizontally mounted switches Minimum distance of installa...

Page 14: ...ion in a metal grounded shield Installation in an isolated shield mm D mm mm mm mm mm mm mm 88 31 25 20 20 25 10 20 100 110 88 32 35 20 35 25 10 20 100 110 88 35 45 25 45 35 10 25 160 120 88 37 45 25...