prox.pad Installation/Programming Manual
2.5.3 Wiring the AUX Relay for Use as Propped Door
The Propped Door Relay output function informs personnel that the door is being held open, or “propped” open, after a valid entry.
The Aux relay is rated to handle one amp of current at 12 VDC, and turns ON or OFF one leg of the power to a warning device.
(Warning device not included with the IEI unit.) To incorporate this feature, follow the steps below; see Figure 11.
1. Turn OFF power to the prox.pad unit, and then unlatch the keypad from the plastic housing.
2. Locate connector P2 (the 6-pin connector) on the main circuit board.
3. Connect the 6-conductor harness to connector P2. (The 2-pin jumper on pins 5 and 6 of connector P2 must be removed first.)
4. Connect the green wire to V+ on the sounder.
5. Connect the blue wire to V+on the power supply.
6. Connect V- from the power supply to V- on the sounder. The gray wire is not used.
NOTE:
To use the default 30-second Propped Door Relay time, no programming is necessary. To change this default (from 30 to 990
seconds), enter the appropriate programming after the unit is installed successfully; for details, see section 2.7.4b.
NOTE: PROGRAMMING FOR PROPPED DOOR -
To program for Propped Door, enter the following on the keypad:
15 # 3 # 0
# **
Page 30 of 86 Document # 6055676, Rev 2.2, D4b
Figure 11: Wiring the Aux Relay for Propped Door Alarm