S

emi-Automatic 

P

riming 

V

alve

11

replace these components when the valve is
disassembled.  If the brass seat on the valve
body is damaged the Hale SPV must be
replaced.

12. During re-assembly of the valve use thread

locking compound (Loctite #290 or equal) to
lock threads in place.

13. Apply a light coating of thread sealing

compound and install the service elbow and
vacuum hose connection fitting into the
valve body.

14. Insert the new valve into the valve body from

the side that attaches to the pump or
universal adapter.

15. Place the small end of the compression

spring over the boss in the valve body
around the valve.

WARNING:

  Parts under spring tension can

become projectiles and cause serious injury.
When removing or installing these parts
make sure they are restrained and spring
tension is released slowly.

16. With the Hale SPV on a stable surface,

place the diaphragm plate over the spring
and press down to compress spring.  While
holding diaphragm plate down with spring
compressed, install #10-24 x 

1

/

2

 inch long

screw into the valve.

17. Place a new diaphragm on the valve body

and align screw holes.

18. Place the diaphragm cover over diaphragm

aligning matchmarks ensuring the cover
drain hole will be in the correct position
when the valve is installed on the pump.

19. Install the 5/16-18 x 

3

/

4

 inch long cap screws

to hold the cover in place.

20. Apply a light coating of grease to the seal

ring then place strainer and new seal ring
into valve body.  Install seal ring, strainer
and valve assembly on pump (or universal
adapter) over studs.  Secure in place using

7

/

16

-14 nuts.  Tighten nuts.

21. Connect the 

3

/

4

 inch (19 mm) ID vacuum

hose from the priming pump to the hose
connection fitting on the Hale SPV
assembly.

22. Test operation of the Hale SPV.  Conduct

vacuum and hydrostatic tests in accordance
with department procedures.

Summary of Contents for HALE SPV

Page 1: ...rtant to follow the instructions on care and operation Proper use and good preventive maintenance will lengthen the life of your unit ALWAYS INCLUDE THE UNIT SERIAL NUMBER IN CORRESPONDENCE Hale Produ...

Page 2: ......

Page 3: ...o copies of the Hale SPV manual to the end user of the equipment For additional manuals contact Hale Products Inc at 610 825 6300 Ask for Manual P N 029 0020 33 0 TABLE OF CONTENTS SECTION PAGE 1 SAFE...

Page 4: ......

Page 5: ...stallation service or repair WARNING Check all hoses for weak or worn conditions after each use Ensure that all connections and fittings are tight and secure WARNING Use only pipe hose and fittings fr...

Page 6: ...button is released Once push button is released the priming pump stops running allowing the Hale SPV to close for normal pump operation The Hale Semi Automatic Priming Valve Hale SPV shown in figure 1...

Page 7: ...mp body Components that are included with this option and shipped with the midship pump are the Push button Switch Panel Placard and Installation Manual When completing the apparatus installation of t...

Page 8: ...the gearbox All that remains after the midship pump is mounted on the apparatus frame is to install the panel placard and push button on the pump operator panel and make the electrical connections fro...

Page 9: ...hole in the panel 3 Remove the push button switch from the packaging and install the locknut on the mounting neck 4 Refering to figure 3 Insert the push button switch through the 0 64 inch 16 mm diam...

Page 10: ...card push button switch Use material thickness and fastening devices that leave a flat surface 6 Connect electrical leads to the momentary contact push button 7 Locate the priming valve flange on the...

Page 11: ...hose connection on the Hale SPV to the priming pump connection Use hose with 3 4 inch 19 mm inside diameter that is rated for 29 in 737 mm Hg vacuum Aeroquip 2556 12 or equal Make sure the hose is rou...

Page 12: ...hole on the diaphragam cover will be in the down Hale SPV Installation with Universal Mounting Adapter When installing the Hale SPV assembly with a universal mounting adapter use the following proced...

Page 13: ...on rated for 29 in 737 mm Hg vacuum 8 Attach 3 4 inch 19 mm ID vacuum hose from the hose connection on the Hale SPV to the priming pump connection Use hose with 3 4 inch 19 mm inside diameter that is...

Page 14: ...service with a minimum of preventive maintenance Performance degradation can result from a ruptured diaphragm or worn seat on the valve A Hale SPV repair kit that contains a manual seal ring valve and...

Page 15: ...With the Hale SPV on a stable surface place the diaphragm plate over the spring and press down to compress spring While holding diaphragm plate down with spring compressed install 10 24 x 1 2 inch lo...

Page 16: ...0231 00 0 DIAPHRAGM COVER PAINTED 1 EA 8 046 0121 00 0 DIAPHRAGM 5 3 8 IN DIA 1 EA 9 018 1004 32 0 SCREW 10 24 X 1 2 IN LG 1 EA 10 005 0021 00 0 SPV DIAPHRAGM PLATE 1 EA 11 042 0081 00 0 VALVE RETURN...

Page 17: ...e pump and disassembled REPAIR KIT PART NUMBER 546 1680 00 0 The repair kit contains the following components Refer to the exploded view on the previous page for parts identification ITEM PART NUMBER...

Page 18: ...UALITY COURSE OF DEALING USAGE OF TRADE OR PATENT INFRINGEMENT FOR A PRODUCT MANUFACTURED TO ORIGINAL BUYER S DESIGN AND SPECIFICATIONS EXCLUSIVE REMEDIES If Buyer promptly notifies HALE upon discover...

Reviews: