Safety Interlock Switch with Guard Locking

 

 

 
 
 
                 
      

Conforming to Standard: 

EN1088, IEC 60947-5-1, UL508 

Safety Classification and Reliability Data: 

 Mechanical Reliability B10d 

ISO 13849-1 

EN 62061 

Safety Data - Annual Usage  

PFHd 

Proof Test Interval (Life) 

MTTFd 

 
2.5 x 10

6

 operations at 100mA load 

up to PLe / Cat.4 depending upon system architecture 
up to SIL3 depending upon system architecture 
8 cycles per hour / 24 hours per day / 365 days  
3.44 x 10

-8 

  35 years 
356 years 

Solenoid Voltage (by part number)  

24V ac/dc  or 110V. ac  or  230V. ac   +/- 10%   (12W.) 

LED 2  Supply Voltage 

24V dc   +/- 10% 

Safety Contacts 11/12   21/22 

 

Utilization Category  AC15  A300   3A. 
Thermal Current (Ith)    5A 

                            Auxiliary Contact 33/34 (selectable with LED2) 

230V.ac/dc   0.5A. maximum. 

                                                                 Auxiliary Contact 43/44 

230V.ac/dc   0.5A. maximum. 

Rated Insulation Voltage  

600VAC  

Rated Impulse Withstand Volt  

2500VAC  

Travel for Positive Opening  

10mm 

Man. Actuation Frequency  

2 cycle/sec  

Actuator entry minimum radius 

175mm  Standard    100mm Flexible 

Case Material  

Glass Filled Polyester or Stainless Steel 316 

Actuator Material  

Stainless Steel 316 

Enclosure Protection 

IP67 (Plastic)  IP69K (Stainless Steel) 

Operating Temperature  

-25°C to 55°C 

Holding Force 

1400N. (Max.). 

Vibration 

 

IEC 68-2-6, 10-55Hz+1Hz, 
Excursion: 0.35mm, 1 octave/min 

Conduit Entry 

Various    (See Sales Part Numbers) 

Fixing 

4 x M5 

The guard is locked closed until the solenoid is energized. The solenoid can only be energized when the 
auxiliary contacts (A) of contactors K1 and K2 are closed. 
When the lock release button is pushed the locking mechanism is released and the switch contacts 11-12 and 
21-22 are opened. These contacts are in series with contactor coils of K1 and K2 and will prevent re-start whilst 
the guard is open. 
If after pressing the Stop button either contactor K1 or K2 stays closed the motor will stop but the solenoid 
cannot be energized or the guard opened. 
 
LED 1 provides visual indication of solenoid power applied. 
LED 2 provides visual indication of guard locked and machine able to start.  
 
System is shown with machine stopped, guard closed and locked, and the solenoid able to be energised.

  

 

Application Example: Dual Channel non monitored. 

The above system can be enhanced by alternatively connecting the switch 
circuits 11-12 and 21-22 to an SCR-3 Safety Relay to monitor for wiring short 
circuits.  
This provides Dual Channel monitoring and a check of the contactor feedback 
circuits through the auxiliary contacts (A) of K1 and K2. 
The SCR-3 monitors the switch and the contactors K1 and K2 and provides it’s 
own self-monitoring via force guided internal relays.  
 
System is shown with machine stopped, guard closed and locked, and the 
solenoid able to be energised.

  

 

        

Application Example: Dual Channel monitored. 

IDEM SAFETY SWITCHES Ltd., 2 Ormside Close, Hindley Industrial Estate, Hindley Green, Wigan, WN2 4HR   UK.    Tel: +44 (0)1942 257070     Fax.: +44 (0)1942  257076 

IDEM (USA)  4416 Technology Drive, Fremont, CA 94538   Tel:510-445-0751  Fax:1866-431-7064  email:  

[email protected]

  Web: 

www.idemsafety.com

 

Doc: 102547 
Oct.  2013 

Information with regard to UL 508:   

Type 1 Enclosures.   
Intended for same polarity use and  
one polymeric conduit connection. 
Electrical Rating:   A300.  48W5.         
Max. Switching Current / Volt / Amp:   
120V. 6A. (720VA break)  PF 0.38 
240V. 3A. (720VA break)  PF 0.38 