Safety Interlock Switch with Guard Locking
Conforming to Standard:
EN1088, IEC 60947-5-1, UL508
Safety Classification and Reliability Data:
Mechanical Reliability B10d
ISO 13849-1
EN 62061
Safety Data - Annual Usage
PFHd
Proof Test Interval (Life)
MTTFd
2.5 x 10
6
operations at 100mA load
up to PLe / Cat.4 depending upon system architecture
up to SIL3 depending upon system architecture
8 cycles per hour / 24 hours per day / 365 days
3.44 x 10
-8
35 years
356 years
Solenoid Voltage (by part number)
24V ac/dc or 110V. ac or 230V. ac +/- 10% (12W.)
LED 2 Supply Voltage
24V dc +/- 10%
Safety Contacts 11/12 21/22
Utilization Category AC15 A300 3A.
Thermal Current (Ith) 5A
Auxiliary Contact 33/34 (selectable with LED2)
230V.ac/dc 0.5A. maximum.
Auxiliary Contact 43/44
230V.ac/dc 0.5A. maximum.
Rated Insulation Voltage
600VAC
Rated Impulse Withstand Volt
2500VAC
Travel for Positive Opening
10mm
Man. Actuation Frequency
2 cycle/sec
Actuator entry minimum radius
175mm Standard 100mm Flexible
Case Material
Glass Filled Polyester or Stainless Steel 316
Actuator Material
Stainless Steel 316
Enclosure Protection
IP67 (Plastic) IP69K (Stainless Steel)
Operating Temperature
-25°C to 55°C
Holding Force
1400N. (Max.).
Vibration
IEC 68-2-6, 10-55Hz+1Hz,
Excursion: 0.35mm, 1 octave/min
Conduit Entry
Various (See Sales Part Numbers)
Fixing
4 x M5
The guard is locked closed until the solenoid is energized. The solenoid can only be energized when the
auxiliary contacts (A) of contactors K1 and K2 are closed.
When the lock release button is pushed the locking mechanism is released and the switch contacts 11-12 and
21-22 are opened. These contacts are in series with contactor coils of K1 and K2 and will prevent re-start whilst
the guard is open.
If after pressing the Stop button either contactor K1 or K2 stays closed the motor will stop but the solenoid
cannot be energized or the guard opened.
LED 1 provides visual indication of solenoid power applied.
LED 2 provides visual indication of guard locked and machine able to start.
System is shown with machine stopped, guard closed and locked, and the solenoid able to be energised.
Application Example: Dual Channel non monitored.
The above system can be enhanced by alternatively connecting the switch
circuits 11-12 and 21-22 to an SCR-3 Safety Relay to monitor for wiring short
circuits.
This provides Dual Channel monitoring and a check of the contactor feedback
circuits through the auxiliary contacts (A) of K1 and K2.
The SCR-3 monitors the switch and the contactors K1 and K2 and provides it’s
own self-monitoring via force guided internal relays.
System is shown with machine stopped, guard closed and locked, and the
solenoid able to be energised.
Application Example: Dual Channel monitored.
IDEM SAFETY SWITCHES Ltd., 2 Ormside Close, Hindley Industrial Estate, Hindley Green, Wigan, WN2 4HR UK. Tel: +44 (0)1942 257070 Fax.: +44 (0)1942 257076
IDEM (USA) 4416 Technology Drive, Fremont, CA 94538 Tel:510-445-0751 Fax:1866-431-7064 email:
Web:
www.idemsafety.com
Doc: 102547
Oct. 2013
Information with regard to UL 508:
Type 1 Enclosures.
Intended for same polarity use and
one polymeric conduit connection.
Electrical Rating: A300. 48W5.
Max. Switching Current / Volt / Amp:
120V. 6A. (720VA break) PF 0.38
240V. 3A. (720VA break) PF 0.38