background image

SX5A AS-Interface 

258 

 

 

www.idec.com

PLCs

Operator Interfaces

Automation Software

Power Supplies

Sensors

Communication & Networking

Communication & Networking

 Specifi cations

Models

SX5A-SWN40S02

SX5A-SWN40K02N

SX5A-SWM22KS2N

SX5A-SWM43KS2N

LED Indicators

PWR

AS-Interface power: Green LED

AUX

External auxiliary power U (

AUX

): Green LED

IN

4 yellow LEDs

2 yellow LEDs

4 yellow LEDs

OUT

2 yellow LEDs

3 yellow LEDs

FAULT

Error indication: Red LED

ON: Communication error or address 0

Flash: Sensor power supply or output is overloaded

Address 

Assignment

Addressing Method

Remove the protection cap from the addressing port on the I/O module. Connect the hand-held programming device (SX9Z-

ADR1N) to the addressing port on the I/O module using the programming device cable (SX9Z-CN1), then the I/O module 

stops communication through the AS-Interface line. Change slave addresses using the programming device.

Certifi cation

AS-International Association

Standards

UL/c-UL, CE

Summary of Contents for SX5A Series

Page 1: ...tors IEC62026 2 compliant Repeater No address setting required The AS Interface network can be extended up to 300 m IP65 protection Easy connection to AS Interface flat cables Part Numbers SX5A AS Interface Communication Terminals Terminal I O Specifications Part Numbers Applicable Base Module order separately Input Points Input Output Points Output IP67 I O Module Connector 4 NPN SX5A SWN40S02 SX5A...

Page 2: ...ect the programming device to slave SX9Z CN1 Programming Device AC Adapter Charge the programming device SX9Z ADPT AC input voltage 100 to 240V AC SwitchNet Addressing Port Adapter Connect the programing device cable to SwitchNet contacts LA9Z SNADP AS Interface Flat Cable Branch Connector Branch AS Interface flat cable to AS Interface flat cable SX9Z CF1 T branch Connector Branch AS Interface flat c...

Page 3: ...60529 Attach SX9Z CAP1 protection caps on unused I O connectors Connection Method Insulation displacement technology for flat cables yellow black M12 connector for I O Weight 100g 150g Mounting Method Screw mounting on base module Input Input Points Signals 4DC inputs 2 and 3 wire sensors NPN 4DC inputs 2 and 3 wire sensors PNP 2DC inputs 2 and 3 wire sensors PNP 4DC inputs 2 and 3 wire sensors PNP...

Page 4: ...T 2 yellow LEDs 3 yellow LEDs FAULT Error indication Red LED ON Communication error or address 0 Flash Sensor power supply or output is overloaded Address Assignment Addressing Method Remove the protection cap from the addressing port on the I O module Connect the hand held programming device SX9Z ADR1N to the addressing port on the I O module using the programming device cable SX9Z CN1 then the I...

Page 5: ... no freezing Degree of Protection IP20 EN60529 Connection Method Removable terminal block Applicable wire size 2 5mm2 14 AWG Weight 150g Mounting Method DIN rail mounting Input Input Points Signals 4 DC inputs 2 and 3 wire sensors NPN 4 DC inputs 2 and 3 wire sensors PNP Input Power Supplied from AS Interface line default internal switch set to INT Supplied from an external 12 to 24V DC PELV inter...

Page 6: ... LEDs FAULT Error indication Red LED ON Communication error or address 0 Flash Sensor power supply or output is overloaded INT Input power supplied from AS Interface line Green LED Address Assignment Addressing Method Connect the hand held programming device SX9Z ADR1N to the addressing port on the I O module using the program ming device cable SX9Z CN1 then the I O module stops communication thro...

Page 7: ...UX AUX AUX AUX Sensor Sensor 1 FAULT 2 4 3 5 1 4 3 2 5 1 4 3 2 5 1 4 3 2 5 AUX AUX PE NC OUT2 OUT OUT2 NC PE NC OUT3 OUT OUT3 NC PE NC OUT1 OUT OUT1 OUT2 M12 1 connector For 3 wire sensor Connect to protective ground on control panel 4 inputs Load PNP output sensor AS i EXT IN I INT EXT UEXT Input Port Power Selector Switch Position 4 inputs IN1 IN4 I IN INT AS i PWR FAULT For 3 wire sensor NPN ou...

Page 8: ...3 Label for user Auxiliary Voltage Terminal Assignment Input Terminal Assignment AS Interface Terminal Assignment I 1 I 2 I 3 I 4 IN1 IN2 IN3 IN4 I 1 I 2 I 3 I 4 1 2 3 4 IN FAULT INT PWR ADDR SX5A SSN40K0N AS i AS i Output Terminal Assignment Label for user Input Terminal Assignment AS Interface Terminal Assignment Input Port Power Selection Power for input ports and connected sensors can be suppl...

Page 9: ...ication Networking Dimensions SX5A SWN40S02 SX5A SWN40K02N SX5A SWM22KS2N Base module is separately ordered SX5A SWM43KS2N Base module is separately ordered 118 73 5 34 5 60 36 18 7 4 150 34 5 73 5 4 18 7 60 36 SX5A B3FF SX5A B2FF 112 118 77 5 4 48 12 PE 112 150 77 5 4 48 12 PE SX5A SSN40S0N SX5A SSN40K0N SX5A SSM43KSN 22 5 105 102 3 102 All dimensions in mm ...

Page 10: ...Current 60mA per segment 120mA total Operating Temperature 0 to 55 C no freezing Storage Temperature 25 to 75 C no freezing Operating Humidity 30 to 95 RH no condensation Degree of Protection IP65 Insulation Resistance 5 MΩ minimum 500V DC megger Dielectric Strength 1000V AC 1 minute Applicable Wire AS Interface flat cable Weight Approx 170g Dimensions 60W x 118 5H x 22 5D mm Mounting Screw mountin...

Page 11: ...to the programming device cable and insert the addressing port adapter into the addressing port on the communication block Address Assignment for SwitchNet Turn off the power to the SwitchNet control unit and open the lid of the address ing port Connect the programming device cable SX9Z CN1 to the hand held programming device SX9Z ADR1N and attach the SwitchNet addressing port adapter LA9Z SNADP t...

Page 12: ...y recharged using AC adapter Operation Time 8 hours or 250 read write operations after full charge Charging Time Approx 14 hours Operating Temperature 0 to 55 C Storage Temperature 25 to 85 C no freezing Degree of Protection IP20 Weight Approx 275g Communication Specifications AS Interface Version 2 1 Operation Slave address assignment and data read write compatible with the 62 slave mode Connectio...