IDEC SmartRelay installation and wiring
2.3 iring IDEC SmartRelay
IDEC SmartRelay Manual
26
2.2.4
Labeling IDEC SmartRelay
The rectangular areas on the IDEC SmartRelay modules are intended for labeling.
In the case of expansion modules, you can use the rectangular areas for labeling the inputs
and outputs, for example. In this connection, you can enter a delta factor of 8 for the inputs
or 4 for the outputs if the Base Module already has 8 inputs or 4 outputs.
2.3
iring IDEC SmartRelay
ire IDEC SmartRelay using a screwdriver with a 3 mm blade.
ou do not need to wire ferrules for the terminals. ou can use conductors fulfilled the
following re uirements:
Cross-sections of up to the following thicknesses:
1 2.5 mm
2
2 1.5 mm
2
for each second terminal chamber
Conductor material: Cu
Insulation temperature rating: 75 C
Tightening tor ue: 0.5 Nm to 0.6 Nm or 4.5 in-lbf to 5.3 in-lbf.
Recommended ferrules
Ferrules order No.
For 1-cable connection
Cross-section
mm
2
A G
Phoenix Contact
Ferrule type No.
NIC HIFU
Blade Terminals
type No.
NIC HIFU
Insulated Pin Terminals
type No.
0.3
22
AI0,5-10 H
BT1.25-10-1
-
0.5
20
AI0,5-10 H
TGN-TC-1.25-11T
0.75
18
AI0,75-8G
1.25
18
AI1,5-8B
BT1.25-10-1
BT2-9-1
2.0
16
AI2,5-8BU
BT2-9-1
-
Recommended
crimping tool
CRIMPFO A 3
NH1
NH61
NH11
NH32
NH65