IDEC SmartRelay Manual
297
Technical data
A.8 Technical data: FL1F-B12RCE/H12RCE, FL1F-M08B2R2
Notice: For fluorescent lamps with capacitors, you must consider the technical data of
fluorescent lamp ballasts. If the current exceeds the maximum allowed surge current,
appropriate contactor relays must switch the flourescent lamps.
Line length (shielded and twisted)
Max. 10 m
- -
Error limit
± 1.5% at FS
- -
Digital outputs
Number
4
4
Output type
Relay outputs
Relay outputs
Electrical isolation
Yes
Yes
In groups of
1
1
Control of a digital input
Yes
Yes
Continuous current I
th (per terminal)
Recommended range of
application ≥ 100 mA at 12 VAC/
VDC
Max. 10 A per relay
Recommended range of
application ≥ 100 mA at
12 VAC/VDC
Max. 5 A per relay
Surge current
Max. 30 A
Max. 30 A
Incandescent lamp load
(25000 switching cycles) at
1000 W
1000 W
Fluorescent tubes with ballast
(25000 switching cycles)
10 x 58 W
10 x 58 W
Fluorescent tubes, conventionally
compensated (25000 switching
cycles)
1 x 58 W
1 x 58 W
Fluorescent tubes, uncompensated
(25000 switching cycles)
10 x 58 W
10 x 58 W
Derating
None; across the entire
temperature range
None; across the entire
temperature range
Short circuit-proof cos 1
Power protection B16, 600 A
Power protection B16, 600
A
Short circuit-proof cos 0.5 to 0.7
Power protection B16, 900 A
Power protection B16, 900
A
Parallel output circuits for power
increase
Not permitted
Not permitted
Protection of output relay
(if desired)
Max. 16 A,
characteristic B16
Max. 16 A,
characteristic B16
Switching rate
Mechanical
10 Hz
10 Hz
Ohmic load/lamp load
2 Hz
2 Hz
Inductive load
0.5 Hz
0.5 Hz
FL1F-B12RCE
FL1F-H12RCE
FL1F-M08B2R2