IDEC SmartRelay Manual
217
IDEC SmartRelay functions
4.4 Special functions list - SF
Symbol in
IDEC SmartRelay
iring
Description
Input A/M
Set the mode of the controller:
1: automatic mode
0: manual mode
Input R
Use the input R to reset the output A . As long as this
input is set, the input A/M is disabled.
Output A is set to 0.
Input PV
Analog value: process variable, influences the output
Parameter
SP: set-value assignment
Range of values:
-10,000 to 20,000
C: gain
Range of values:
00.00 to 99.99
TI: integral time
Range of values:
00:01m to 99:59 m
Dir: action direction of the controller
Range of values:
or -
M : value from A with manual mode
Range of values:
0 to 1,000
Min: minimum value for PV
Range of values:
-10,000 to 20,000
Max: maximum value for PV
Range of values:
-10,000 to 20,000
A: gain
Range of values:
-10.00 to 10.00
B: offset
Range of values:
-10,000 to 10,000
p: number of decimals
Range of values:
0, 1, 2, 3
Output A
This special function has an analog output (
manipulated variable). This output can only be
connected with analog inputs, analog memory
markers, analog outputs or network analog outputs.
Range of values for A :
0 to 1,000