Technical data
IDEC SmartRelay Manual
310
A.8 Technical data: FL1D-K2B2
FL1D-K2B2
Power supply
Input voltage
24 V DC
Permissible range
20.4 ... 28.8 V DC
Power consumption
25 ... 50 mA
Voltage failure buffering
typ. 5 ms
Power loss at 24 V
0.6 ... 1.2 W
Electrical isolation
No
Reverse polarity protection
Yes
Ground terminal
for connecting ground and shielding of
the analog measuring line.
Analog outputs
Number
2
Input range
0 ... 10 V DC
Load resistor
5 k
Ω
Resolution
10 bit, normalized to 0 ... 1000
Cycle time for analog value output depending on installation (typ. 50 ms)
Electrical isolation
No
Line length
(shielded and twisted)
10 m
Error limit
±2.5 % of full scale
Short circuit protection
Yes
Response at short-circuit
affected output = 0 V
neighboring output reverts
Overload protection
Yes
Response at overload
affected output = 0 V
neighboring output reverts