Technical data
299
IDEC SmartRelay Manual
Analog inputs
Number
2 (I7 = AI1, I8 =AI2)
Range
0 ... 10 V DC
input impedance
78 k
Ω
Resolution
10 bit, normalized to
0 ... 1000
Cycle time for analog value
generation
300 ms
max. input voltage
28.8 V DC
Line length (shielded and twist-
ed)
10 m
Error limit
±1.5 % of full scale
Digital outputs
Number
4
4
Output type
Transistor,
current–sourcing
(4)
Transistor,
current–sourcing
Electrical isolation
No
No
In groups of
Control of a digital input
Yes
Yes
Output voltage
Supply voltage
Supply voltage
Output current
max. 0.3 A
max. 0.3 A
Continuous current I
th
Incandescent lamp load
(25000 switching cycles) at
Fluorescent tubes with ballast
(25000 switching cycles)
Fluorescent tubes,
conventionally compensated
(25000 switching cycles)
Fluorescent tubes, uncompen-
sated (25000 switching cycles)
Short circuit–proof and over-
load–proof
Yes
Yes
Short–circuit current limitation Approx. 1 A
Approx. 1 A
FL1D-H12SND
FL1B-M08B1S2
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com