Technical data
IDEC SmartRelay Manual
296
Input current at
Signal 0
Signal 1
< 0.03 mA
> 0.08 mA
< 0.03 mA
> 0.08 mA
Delay time at
0 to 1: 100 V AC
: 240 V AC
: 100 V DC
: 240 V DC
1 to 0: 100 V AC
: 240 V AC
: 100 V DC
: 240 V DC
typ. 50 ms
typ. 30 ms
typ. 25 ms
typ. 15 ms
typ. 65 ms
typ. 105 ms
typ. 95 ms
typ. 125 ms
typ. 50 ms
typ. 30 ms
typ. 25 ms
typ. 15 ms
typ. 65 ms
typ. 105 ms
typ. 95 ms
typ. 125 ms
Line length (unshielded)
100 m
100 m
Digital outputs
Number
4
4
Output type
Relay outputs
Relay outputs
Electrical isolation
Yes
Yes
Dielectric Strength
(between power/input
terminals and output terminals)
2,500 V AC, 1minute
500 V DC, 1 minute
2,500 V AC, 1minute
500 V DC, 1 minute
In groups of
1
1
Control of a digital input
Yes
Yes
Continuous current I
th
max. 10 A per relay max. 5 A per relay
Surge current
max. 30 A
max. 30 A
Incandescent lamp load
(25000 switching cycles) at
230/240 V AC
100/120 V AC
1000 W
500 W
1000 W
500 W
Fluorescent tubes with ballast
(25000 switching cycles)
10 x 58 W
(at 230/240 V AC)
10 x 58 W
(at 230/240 V AC)
FL1D-H12RCC
FL1D-B12RCC
FL1B-M08C2R2
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com