background image

Programming IDEC SmartRelay

76

IDEC SmartRelay Manual

Closing the programming mode

Although you were shown how to exit the programming 
mode when you created your first circuit program, 
here is a reminder:
1. To return to the programming menu: 

Press 

ESC

 

2. To return to the main menu:

Press 

ESC

3. To move the '>' cursor to '

Start

':

Press 

 or 

4. To confirm 'Start':

Press 

OK

IDEC SmartRelay is back in RUN mode:

3.6.8

Deleting a block

Let us assume you want to delete the block B2 from your cir-
cuit program and connect B1 directly to Q1.

Proceed as follows:
1. Switch the IDEC SmartRelay to programming mode

(as a reminder, refer to page 50).

2. Select ‘

Edit

’:

Press 

 or 

3. Confirm ‘Edit’:

Press 

OK

4. Select ‘

Edit Prg

’:

Press 

 or 

5. Confirm ‘Edit Prg’:

Press 

OK

(If required, enter your password and confirm with 

OK

).

2003-01-27

 Mo 09:30

You can press 

 or 

 to scroll the pag-

es and to monitor the I/O states.

Q1

I1

I2

x

x

Par

B1

B2

Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com

Summary of Contents for SmartRelay FL1B-J2B2

Page 1: ...SmartRelay s place in information technology The wiring information in your IDEC SmartRelay manual is also found in the IDEC SmartRelay Product Info included with all devices For further information on programming the IDEC SmartRelay on your PC with the PC in the Online Help for WindLGC WindLGC is the programming software for PCs It runs un der Windows and helps you to get started with IDEC SmartR...

Page 2: ...ctions You can use the IDEC SmartRelay cursor keys as inputs You can use the special functions Shift register Analog amplifier Analog value monitoring and Analog differ ential trigger You can invert individual inputs Six of the basic functions are expanded with four inputs You can test your circuit program online using the PC Parameters for certain functions can also be derived from analog values ...

Page 3: ...nd systems in accordance with safety regula tions and standards Danger Warns that death serious harm to health or damage to assets will result if the respective precautionary measures are not taken Warning Warns that death serious harm to health or damage can result if the respective precautionary measures are not taken Caution Warns that harm to health or damage to assets can result if the re spe...

Page 4: ... not be ruled out Any liability and warranty for the accuracy of this information is excluded The data in this manual are reviewed at regular intervals Any corrections required are included in the subsequent editions Suggestions for improvement are welcomed Warning This device must always be used as intended for the applications described in the catalog and in the technical specifications and only...

Page 5: ... IDEC SmartRelay 22 2 3 1 Connecting the power supply 22 2 3 2 Connecting IDEC SmartRelay inputs 24 2 3 3 Connecting outputs 32 2 4 Switching on the IDEC SmartRelay Power On 35 3 Programming IDEC SmartRelay 39 3 1 Connectors 41 3 2 Blocks and block numbers 44 3 3 The way to IDEC SmartRelay starting with the circuit diagram 47 3 4 The 4 golden rules for the operation of IDEC SmartRelay 50 3 5 Overv...

Page 6: ...ronization 85 3 7 Memory space and circuit dimensions 86 4 IDEC SmartRelay functions 92 4 1 Constants and connectors Co 93 4 2 Basic functions list GF 96 4 2 1 AND 98 4 2 2 AND with Edge Detection 99 4 2 3 NAND NOT AND 100 4 2 4 NAND with Edge Detection 101 4 2 5 OR 102 4 2 6 NOR NOT OR 103 4 2 7 XOR exclusive OR 104 4 2 8 NOT Negation Inverter 104 4 3 Basics on special functions 105 4 3 1 Designa...

Page 7: ...unction switch 138 4 4 11 Seven day time switch 141 4 4 12 Twelve month time switch 146 4 4 13 Up down counter 149 4 4 14 Operating hours counter 153 4 4 15 Frequency trigger 158 4 4 16 Analog trigger 161 4 4 17 Analog differential trigger 164 4 4 18 Analog comparator 168 4 4 19 Analog value monitoring 173 4 4 20 Analog amplifier 176 4 4 21 Latching relay 178 4 4 22 Current impulse relay 179 4 4 2...

Page 8: ...artRelay memory cartridge card 205 6 1 Security function CopyProtect 207 6 2 Inserting and removing the memory cartridge card 210 6 3 Copying data from the IDEC SmartRelay to the memory cartridge card 212 6 4 Copying data from the memory cartridge card to IDEC SmartRelay 214 7 IDEC SmartRelay software 216 7 1 Connecting the IDEC SmartRelay to a PC 218 ngineering Inc 230 Ryan Way South San Francisc...

Page 9: ...vantages of using IDEC SmartRelay 236 8 4 Factory door 238 8 4 1 Requirements for a gate control system 238 8 4 2 Previous solution 239 8 4 3 Extended IDEC SmartRelay solution 241 8 5 Centralized control and monitoring of several factory doors 242 8 5 1 Requirements for a gate control system 243 8 6 Luminous rows 246 8 6 1 Requirements for a lighting system 246 8 6 2 Previous solution 247 8 6 3 Lu...

Page 10: ...A and FL1B M08D2R2 264 A 5 Technical data FL1C 12RCE and FL1B M08B2R2 267 A 6 Switching capacity and service life of the relay outputs 270 A 7 Technical data FL1B J2B2 271 B Determining the cycle time 272 C IDEC SmartRelay without display 274 D IDEC SmartRelay menu structure 277 E Type Numbers 279 Index 281 ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 418...

Page 11: ...or mechanical and apparatus engineering e g for gate control systems air conditioning systems or rainwater pumps etc IDEC SmartRelay can also be implemented for special con trol systems in conservatories or greenhouses for control signal processing and by connecting a communication mod ule e g AS Interface for distributed local controlling of ma chines and processes Special versions without operat...

Page 12: ...our choice The various IDEC SmartRelay Basic versions and expan sion modules offer you a highly flexible and adaptive system to suit your specific tasks The IDEC SmartRelay system offers you many solutions such as for small domestic installations simple automation tasks and even complex engineering tasks involving its in tegration into a bus system e g communications module AS interface Note IDEC ...

Page 13: ...utputs Q1 to Q16 Analog outputs AQ1 and AQ2 cannot be used Memory Markers M1 to M24 M8 Startup Markers Analog Memory Markers AM1 to AM6 Shift register bits S1 to S8 4 Cursor keys 16 Blank outputs X1 to X16 ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 14: ...OP indicator 10 Mechanical coding sockets 4 Module slot with cap 11 Slide 1 2 3 I7 I8 Q1 Q2 Q3 Q4 4 35 72 L1 N 4 90 55 I5 I6 I2 I3 I4 I1 Q4 Q1 Q2 35 L1 N I2 I3 I4 I1 36 RUN STOP 90 53 3 1 2 9 9 10 8 8 8 10 11 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 5 6 7 4 Q3 IDEC SmartRelay Basic e g FL1C H12RCC IDEC SmartRelay expansion module e g FL1B M08C2R2 ngineering Inc 230 Ryan Way South San Francisco CA 94080 637...

Page 15: ... Mechanical coding sockets 4 Module slot with cap 11 Slide 1 2 3 I7 I8 Q1 Q2 Q3 Q4 4 35 72 L1 N 4 90 55 I5 I6 I2 I3 I4 I1 Q4 Q1 Q2 35 L1 N I2 I3 I4 I1 36 RUN STOP 90 53 3 1 2 9 9 10 8 8 8 10 11 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 5 6 7 4 Q3 IDEC SmartRelay Basic e g FL1C H12RCE IDEC SmartRelay expansion module e g FL1B M08B2R2 ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inqui...

Page 16: ...ing earth and the shielding of analog measuring cables 2 Inputs 10 Mechanical coding sockets 7 RUN STOP indicator 11 Slide 8 Expansion interface I1 PE INPUT2x 0 10V 0 20mA 35 L M 36 RUN STOP 90 53 1 7 9 9 10 8 8 11 M1 U1 M2 U2 I2 12 4 L M 2 ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 17: ...igital module C Integrated seven day time switch DM Digital module AM Analog module CM Communications module e g AS Interface Symbols Version with display unit is equipped with 8 inputs and 4 outputs Version without display unit is equipped with 8 in puts and 4 outputs The digital module is equipped with 4 digital inputs and 4 digital outputs The analog module is equipped with 2 analog in puts The...

Page 18: ...n be operated with P or N action 24 V AC 24 V DC 8 digital 4 relays 10A FL1C H12RCC 3 3 Two groups consisting of 4 inputs each Each group must be connected to the same phase It is possible to interconnect groups with a different phase 100 240V AC DC 8 digital 4 relays 10A FL1C B12RCE 12 24 V DC 8 digital 1 4 relays 10A no display unit no keyboard FL1C B12RCA 2 24 V AC 24 V DC 8 digital 4 relays 10...

Page 19: ...ual Research FM to Approval Standard Class Number 3611 3600 3810 APPROVED for use in Class I Division 2 Group A B C D Tx Class I Zone 2 Group IIC Tx Symbol Description Supply Voltage Inputs Outputs FL1B M08B2R2 12 24 V DC 4 digital 4 relays 5A FL1B M08B1S2 24 V DC 4 digital 4 Transistor 24 V 0 3 A FL1B M08D2R2 1 1 Digital inputs can be operated either with P or with N action 24 V AC DC 4 digital 4...

Page 20: ...r Australia Recycling and Disposal IDEC SmartRelay units can be fully recycled due to their low pollutant equipment Contact a certified electronic waste disposal center for environmentally acceptable recycling and disposal of your old devices Warning Risk of personal injury and material damage In potentially explosive atmospheres there is a risk of personal in jury or damage to material if you dis...

Page 21: ...the IDEC SmartRelay with cable conductor cross sections from 1 5 mm2 to 2 5 mm2 see Chapter 2 3 Do not exceed the screw torque of the terminals The maximum torque is 0 5Nm see Chapter 2 3 Keep the cabling as short as possible If longer cables are necessary you should use shielded versions You should always route your cables in pairs i e one neutral conduc tor plus one phase conductor or signal lin...

Page 22: ...op a reverse current at the output if you have not installed a diode or similar barrier device Note IDEC SmartRelay units may only be installed and wired by skilled personnel who know and follow the general engineer ing rules and the relevant regulations and standards ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 23: ... 4 analog modules High speed optimal communication performance For optimal and high speed communication performance between IDEC SmartRelay Basic and the various modules we recommend you install the digital modules first then the analog modules example above I1 I6 I7 I8 AI1 AI2 IDEC Smart Relay Basic Q1 Q4 I9 I12 FL1B M08 Q5 Q8 I13 I16 FL1B M08 Q9 Q12 I17 I20 FL1B M08 Q13 Q16 I21 I24 FL1B M08 AI3 ...

Page 24: ...er voltage When using different power supplies the fast transient burst immunity IEC61000 4 4 will be 1 kV power sup ply A 100 to 240V AC DC module cannot be connected to the right side of a 12 24V DC 24V DC or 24V AC DC mod ule For analog input module and AS Interface communica tion module a module of any voltage can be connected to the left side To the right side however a 100 to 240V AC DC modu...

Page 25: ... cor responds with 4 subunits IDEC SmartRelay expansion modules have a width of 36 mm which corresponds with 2 subunits Note The figure below shows you an example of the installation and removal of a FL1C H12RCC and a digital module The measures shown apply to all other IDEC SmartRelay Basic versions and expansion modules Warning Always switch off power before you remove and insert a module base m...

Page 26: ...ap it on The mount ing interlock at the rear must engage IDEC SmartRelay digital module 3 On the right side of the IDEC SmartRelay Basic IDEC SmartRelay expansion module remove the connector cap 4 Place the digital module onto the DIN rail on the right hand side of the IDEC SmartRelay Basic 5 Slide the digital module towards the left until it contacts the IDEC SmartRelay Basic 1 2 3 4 5 6 ngineeri...

Page 27: ...eft In its end position the slide interlock engages in the IDEC SmartRelay Basic Repeat steps 3 through 6 to mount further expansion mod ules Note The expansion interface on the last expansion module must be covered ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 28: ...nstalled only one IDEC SmartRelay Ba sic Part A 1 Insert a screwdriver into the eyelet at the bottom of the slide interlock and move the latch downward 2 Swing the IDEC SmartRelay Basic off the DIN rail 1 2 1 2 3 4 A B ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 29: ...yelet at the bottom of the slide interlock and lever it downward 4 Swing the expansion module off the profile rail Repeat steps 1 to 4 for all other expansion modules Note If you have connected more than one expansion module it is advis able to start removal with the last module at the right hand side Make sure that the slide interlock of the module to be installed re moved is not engaged in the n...

Page 30: ...e the mounting slides on the rear side of the devices towards the outside You can now wall mount the IDEC SmartRelay by means of two mounting slides and two φ M4 screws tightening torque 0 8 to 1 2Nm Mounting slides ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 31: ...rtRelay you need to drill holes using the template shown below All dimensions in mm Bore hole for φ M4 screw Tightening torque 0 8 to 1 2 Nm IDEC SmartRelay Basic IDEC SmartRelay expansion module 53 5 0 2 35 5 0 2 n x 35 5 0 2 98 0 3 1 2 2 2 ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 32: ...ominal line voltages of 100 V AC DC and 240 V AC DC IDEC SmartRelays FL1C 12RCA FL1B M08D2R2 are suitable for a supply voltage of 24 V AC DC IDEC SmartRelays FL1C H12SND FL1B M08B1S2 are suitable for a supply voltage of 24 V DC IDEC SmartRelays FL1C 12RCE FL1B M08B2R2 are suitable for a supply voltage of 12 V AC DC or 24 V AC DC Note the information on connection in the product informa tion docume...

Page 33: ...tall a metal oxide varistor MOV Make sure that the operating voltage of the varistor MOV used lies at least 20 above the rated voltage L1 L N M M L I1 I2 I3 I4 I5 I1 I2 I3 I4 L1 N Protection with safety fuse if required recommended for FL1C H12RCE 0 8 A FL1C H12SND 2 0 A To suppress surge voltages install varis tors MOV with an operating voltage at least 20 above the rated voltage IDEC SmartRelay ...

Page 34: ...thin the FL1B M08C2R2 may not be connected to differ ent phases FL1C H12RCE FL1C B12RCE FL1B M08B2R2 FL1C H12SND FL1B M08B1S2 I1 I6 I7 I8 I1 I6 I7 I8 Signal status 0 5 VDC 5 VDC 5 VDC 5 VDC Input current 1 0 mA 0 05 mA 1 0 mA 0 05 mA Signal status 1 8 V DC 8 V DC 8 V DC 8 V DC Input current 1 5 mA 0 1 mA 1 5 mA 0 1 mA FL1C H12RCA FL1C B12RCA AC FL1B M08 D2R2 AC FL1C H12RCA FL1C B12RCA DC FL1B M08 ...

Page 35: ... 2 wire proximity switches used into account The level of the quiescent current of some 2 wire proximity switches is high enough to trigger a logical 1 signal at the IDEC SmartRelay input You should there fore compare the quiescent current of the proximity switches with the technical data of inputs Appendix A L1 N N L1 C ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiri...

Page 36: ... triggers The restric tions mentioned earlier do not apply to these high speed in puts Note The high speed inputs I5 and I6 are the same as in the previous versions FL1B i e a circuit program that is written in these ver sions can be transferred to the new FL1C units by means of the pro gramming software WindLGC without any changes to these fea tures Expansion modules do not have high speed inputs...

Page 37: ...1C B12RCC L M M L I1 I2 I3 I4 I5 I8 The inputs of these devices not isolated and therefore require a common reference potential chassis ground At the FL1C H12RCE FL1C B12RCE and FL1C H12SND modules you can tap ana log signals between the supply voltage and chassis ground L1 N L3 L2 N L1 I1 I2 I3 I4 I5 I6 The inputs of these devices are arranged in 2 groups each consisting of 4 inputs Differ ent ph...

Page 38: ...nput group I1 to I4 or I5 to I8 or to the inputs of a digital module M L L M U1 I2 M2 U2 I1 M1 PE L M 1 2 3 RUN STOP M M L PE PE terminal for connect ing earth and the shield ing of the analog measuring cable Earth Cable shielding DIN rail Reference current Current 0 20mA Current measurement Voltage measurement ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670...

Page 39: ... FL1C H12RCC FL1C B12RCC FL1B M08C2R2 I1 I8 N 100nF 390kΩ 390kΩ 62kΩ AC 2 wire Sensor I1 to I8 R4 100 to 240 V AC N L1 Internal Circuit Digital AC DC Input When using the AC two wire sensor ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 40: ...C B12RCA FL1B M08D2R2 I1 I8 4 3kΩ 5V 510Ω 100nF P2 AC 2 wire Sensor I1 to I8 R3 240 V AC P1 P2 Internal Circuit Internal Circuit Digital AC DC Input When using the AC two wire sensor ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 41: ...L1C B12RCE FL1C H12SND FL1B J2B2 FL1B J2B2 I1 I8 3 3kΩ 2kΩ 100nF M Internal Circuit Digital DC Input I7 I8 U1 U2 M M1 M2 38kΩ 5V 38kΩ 10nF Internal Circuit Analog Input 0 10V Max 125Ω 125Ω 10nF I1 I2 M1 M2 Internal Circuit Analog Input 0 20mA ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 42: ...utputs You can connect various loads to the outputs e g lamps fluorescent lamps motors contactor relays etc For informa tion on the properties required for the loads connected to the these units refer to Appendix A Connecting This is how you connect the load Protection with automatic circuit breaker max 16 A characteristics B16 e g Power circuit breaker 5SX2 116 6 if required 1 2 Q1 Q2 1 2 Q5 Q6 1...

Page 43: ...liary load voltage supply is not necessary because IDEC SmartRelay supplies the load voltage Requirements for transistor outputs The load connected to IDEC SmartRelay must have the fol lowing characteristics The maximum switched current is 0 3 A per output Connecting This is how you connect the load to a IDEC SmartRelay with transistor outputs Q1 Q2 M M Q5 Q6 M M load Load 24 V DC 0 3 A max load n...

Page 44: ...C H12RCE FL1C B12RCE FL1B M08B2R2 FL1B M08C2R2 FL1B M08D2R2 Relay Output FL1C H12SND FL1B M08B1S2 Transister Output Source 27kΩ 47kΩ 24V 2 1 Q1 Q4 Internal Circuit Internal Circuit 24V 10kΩ 10nF 10nF M Q1 Q4 Internal Circuit Internal Circuit ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 45: ...elay at the time of power fail ure All possible reaction of IDEC SmartRelay are described on the following page Note After power up the FL1C performs initialization After completing initialization the FL1C is ready to start to run During initialization a sandglass is displayed on the CPU module with display or the LED is lit red on the CPU module without display Initialization time regardless of e...

Page 46: ...t 0028 Par 0300 0 123456789 1 0123456789 2 01234 I Before power off After power on No program in memory or empty with program IDEC SmartRelay in RUN mode or empty with program or empty with program Program in memory With stored program from IDEC SmartRelay IDEC SmartRelay in RUN mode with a program copied from the memory cartridge card in IDEC SmartRelay With stored pro gram from IDEC SmartRelay w...

Page 47: ...ridge card IDEC SmartRelay adopts the operational state it had prior to POWER OFF Versions without display unit FL1C B12 automatically change from STOP to RUN LED changes from red to green 4 If you have enabled retentivity at least for one function or a function is permanently retentive the current values are retained at POWER OFF Note When a power failure occurs while you are entering a circuit p...

Page 48: ... parameter assignment mode not FL1C B12 LED is green only FL1C B12 Action of IDEC SmartRelay The inputs data are not fetched The circuit program is not ex ecuted The relay contacts are per manently open or the transis tor outputs are switched off Action of IDEC SmartRelay IDEC SmartRelay reads the status of the inputs IDEC SmartRelay uses the circuit program to calculate the status of the outputs ...

Page 49: ... in this manual relate only to the creation of circuit programs on the actual IDEC SmartRelay because the programming software WindLGC already con tains an extensive Online Help See also Chapter 7 Note IDEC SmartRelay versions without display unit i e the FL1C B12RCE FL1C B12RCA and FL1C B12RCC units do not have an operator panel and display unit They are primarily designed for use in small machin...

Page 50: ... next step we shall create a circuit program based on a simple conventional circuit which you can enter directly in IDEC SmartRelay in the third step It will take you only a few pages of this manual store your first executable circuit program in the IDEC SmartRelay unit With a suitable hardware switches etc you will then be able to carry out first tests ngineering Inc 230 Ryan Way South San Franci...

Page 51: ...ly the analog mod ules FL1B J2B2 has the inputs at the bottom Each output is identified by the letter Q plus a number In the figure you can see the output terminals at the bottom L M I13I14I15I16 Q11 Q9 Q12 Q10 RUN STOP L M A 3 RUN STOP L M I1 I2 I3 I4 I5 I6 Q1 Q2 Q3 Q4 AI1 AI2 L M I9 I10I11I12 Q7 Q5 Q8 Q6 RUN STOP M3U3AI4M4U4 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 PE INPUT 2x 10 V 20 mA ...

Page 52: ...og Input AIx can only represent the connector that is actually capable of handling analog signals IDEC SmartRelay s connectors The term connector refers to all connections and states in IDEC SmartRelay The I O status can be 0 or 1 Status 0 means that the input does not carry a voltage Status 1 means that the input car ries voltage We have introduced hi lo and x connectors to make it easier for you...

Page 53: ...nputs FL1C H12RCC FL1C B12RCC FL1C H12RCA FL1C B12RCA Two groups I1 I4 and I5 I8 I9 I24 AI1 AI8 FL1C H12RCE FL1C B12RCE FL1C H12SND I1 I6 I7 I8 AI1 AI2 I9 I24 AI3 AI8 Outputs Q1 Q4 Q5 Q16 none lo Logical 0 signals off hi Logical 1 signals on x An existing connection that is not used ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 54: ...ox When you create the circuit program you interconnect the blocks To do so simply select the connection you require from the Co menu The menu name Co is an abbreviation of the term Connector Logic operations The most elementary blocks are the logic operations AND OR These special functions offer you a significantly higher per formance Current impulse relay Up down counter On delay Softkey In Chap...

Page 55: ...SmartRelay uses these block numbers to indicate the block interconnections Hence these numbers primarily rep resent a help for your orientation in the circuit program 1 B2 I3 Q1 B1 x x View of the IDEC Smart Relay display A further block is connected at this point Input This connector is not required Block Output Block number as signed by IDEC SmartRelay I1 I2 I3 1 B1 B2 B2 1 B3 Q1 B1 B1 I4 I5 I6 ...

Page 56: ...uit layout To do so however you need to know how IDEC SmartRelay has named the blocks Note We advise you to create an organizational program chart You will find this a valuable help when you create the circuit program be cause you can enter all block numbers assigned by IDEC SmartRe lay in this chart By using the WindLGC software to program the IDEC SmartRelay you can directly create a function ch...

Page 57: ...t with IDEC SmartRelay In IDEC SmartRelay you create a circuit logic by intercon necting blocks and connectors The load E1 is switched on and off by means of the switches S1 OR S2 AND S3 Relay K1 picks up when the condition S1 OR S2 AND S3 is met K1 S1 K1 S2 E1 S3 S1 S3 I3 x Q1 1 I1 I2 x L 1 N Wiring of the inputs Circuit program in IDEC SmartRelay Wiring of the outputs ngineering Inc 230 Ryan Way...

Page 58: ...t S3 is interconnected in series to output Q1 and to a further circuit element A series connec tion corresponds with the AND block Step 2 S1 and S2 are connected in parallel A parallel circuit corresponds with the OR block Unused inputs The circuit program automatically assigns the unused con nectors a status that ensures proper functioning of the rele vant block If you like you can label unused c...

Page 59: ...Relay S3 to connector I3 of IDEC SmartRelay The output of the AND block controls the relay at output Q1 The load E1 is connected to output Q1 Wiring example The following figure shows you the wiring based on the FL1C H12RCC B12RCC L1 N S 3 S 2 S 1 L1 N N L1 I1 I2 I3 I4 1 2 Q1 Input wiring Output wiring Load ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 418...

Page 60: ... the Start command on the main menu to set RUN mode When the system is in RUN you can return to parameter assignment mode by pressing the ESC key When parameter assignment mode is open and you want to return to programming mode select the Stop command from the parameter assignment menu and confirm Stop Prg prompt with Yes To do so move the cursor to Yes and confirm with OK For more details on oper...

Page 61: ...o exit programming mode You select a connector block when the cursor appears as solid square Press or to select a connector or a block Confirm with OK Press ESC to return to the previous step Rule 4 Planning Before you start to create a circuit program you should either first create design on paper or program IDEC SmartRelay directly using WindLGC IDEC SmartRelay can only save complete and faultle...

Page 62: ...efer to Appendix D Program Card Clock Start Edit Clear Prg Password Card Card CopyProtect OK OK ESC ESC IDEC SmartRelay Set Clock S W Time Sync ESC OK Main menu Programming menu Transfer menu Real time clock menu Parameter assignment menu Stop Set Param Set Clock Prg Name ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 63: ...s you the mes sage Switch the IDEC SmartRelay to programming mode by pressing the ESC This will take you to the main menu of the IDEC SmartRelay The first character in the first line is the cursor Press and to move the cursor up and down Move it to Pro gram and confirm with OK IDEC SmartRelay opens the programming menu No Program Press ESC Program Card Clock Start IDEC SmartRelay s main menu Edit ...

Page 64: ...t your circuit program Note Because we have not yet saved a password for the circuit program in IDEC SmartRelay you can directly enter editing mode When you select Edit Prg after you have saved a password protected circuit program you are prompted to enter a password and to con firm it with OK You can only edit the program after you have en tered the correct password see Chapter 3 6 5 Edit Prg Edi...

Page 65: ...y K1 is at output Q1 is controlled by means of an OR block Circuit program S1 is connected to the I1 and S2 to the I2 input connector of the OR block The corresponding layout of the circuit program in IDEC SmartRelay K1 S1 K1 S2 E1 The load is switched on with S1 OR S2 IDEC SmartRelay interprets this parallel circuit as an OR logic because S1 OR S2 switches on the output I1 I2 x Q1 1 ngineering In...

Page 66: ...ircuit program input Let us now write the circuit program starting at the output and working towards the input IDEC SmartRelay initially shows the output L1 N I4 I5 I6 I7 I8 Q1 Q2 Q3 Q4 L1 N S1 S2 L N I1 I1 I3 I1 I1 I1 I1 I1 I2 1 2 1 2 1 2 1 2 Q1 The first IDEC SmartRelay output ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 67: ...but instead as a flashing solid square IDEC SmartRelay of fers you here various options Select GF basic functions by pressing the key until GF appears and confirm with OK IDEC SmartRelay now shows the first block from the list of basic functions Q1 The cursor indicates your current position in the circuit program Q1 Co The cursor is displayed as a solid square You can now select a con nector or a ...

Page 68: ... number The only thing left to do is to interconnect the block inputs This is how it is done Press OK Select the Co list Press OK 1 B1 Q1 The solid square cursor is still posi tioned on the block 1 B1 Q1 B1 1 Q1 The display now shows Block number Your complete circuit program layout 1 B1 Q1 Co The display now shows 1 B1 Q1 x The display now shows ngineering Inc 230 Ryan Way South San Francisco CA ...

Page 69: ...the input of the OR block The cursor jumps to the next input of the OR block Now you connect input I2 to the input of the OR block You already know how to do this 1 Switch to editing mode Press OK 2 To select the Co list Press or 3 To confirm the Co list with Press OK 4 To select I2 Press or 5 To apply I2 Press OK 1 Q1 I1 B1 1 B1 Q1 1 Q1 I1 I1 B1 Your complete circuit program in IDEC SmartRelay up...

Page 70: ...diting mode Press OK 2 To select the Co list Press or 3 To accept the Co list Press OK 4 To select x Press or 5 To apply x Press OK IDEC SmartRelay returns to output Q1 1 B1 Q1 1 Q1 I1 I1 B1 I2 I2 The display now shows Your circuit program layout in IDEC SmartRelay up to now 1 Q1 I1 B1 I2 Q1 B1 x The display now shows This is the layout of your circuit program ngineering Inc 230 Ryan Way South San...

Page 71: ...o the relevant position e g Confirm with OK Now press or to invert this input Next press ESC You can review your first circuit program by pressing or to move the cursor through the circuit program We shall now exit circuit programming mode This is how it is done Return to the programming menu Press ESC 1 B1 Q1 I2 I3 x I1 1 B1 Q1 I2 I3 1 Q1 I2 B1 I3 x x I1 I1 The display now shows Your circuit prog...

Page 72: ...ove the cursor to Edit Name Press or 4 To accept Edit Name Press OK Press and to list the alphabet from A a to Z z num bers and special characters either in ascending or descend ing order You can select any letter number or character To enter a space character simply movie the cursor with to the next position This character is the first one in the list Examples Press once to select an A four times...

Page 73: ...nment mode 3 6 5 Password You can protect a circuit program from unauthorized access by assigning it a password To assign a password A password may have a maximum length of 10 characters and consists only of uppercase letters A to Z Directly at the IDEC SmartRelay the password can be assigned edited or deactivated only in the Password menu In the programming menu 1 Move the cursor to Password Pres...

Page 74: ...g the name of the circuit program Select New and enter 3 Select A Press 4 To move to the next letter Press 5 Select A Press The display now shows 6 To confirm the password Press OK Your circuit program is now protected with the password AA and you are returned to the programming menu Old No Password New Old No Password New AA ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General In...

Page 75: ...tected memory cartridge card you first need to assign a password to this new program see Chapter 6 1 Changing the Password You need to know the current password in order to change it In the programming menu 1 Move the cursor to Password Press or 2 To confirm the Password Press OK Select Old and enter your old password in our case AA by repeating steps 3 through 6 as described earlier The display n...

Page 76: ...r cur rent password in our example ZZ same as if you were changing it In the programming menu 1 Move the cursor to Password Press or 2 To confirm the Password Press OK Select Old and enter your current password under as de scribed in steps 3 to 5 Confirm your entries with OK The display shows Clear the password by leaving the input box blank 3 To confirm the blank password Press OK The password is...

Page 77: ... to accelerate progress in our further exercises and examples Password Wrong Password When the user inputs the wrong password and confirms the input with OK IDEC SmartRelay does not open editing mode but returns to the programming menu This repeats it self over and again until you input the correct password ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 418...

Page 78: ... 01234 Q 0 123456789 1 0123456 M 0 123456789 1 0123456789 2 01234 ESC Key Display field of the IDEC SmartRelay in RUN mode Date and current time of day only for versions with realtime clock This element flashes if the date and time are not set Inputs I1 to I9 Inputs I10 to I19 Inputs I20 to I24 Outputs Q1 to Q9 Outputs Q10 to Q16 Markers M1 to M9 Markers M10 to M19 Markers M20 to M24 4 cursor keys...

Page 79: ...123456 I 0 123456789 1 0123456789 2 01234 Input output status is 1 inverted Input output status is 0 not inverted In this example only the inputs I1 I15 Q8 and Q12 are set high I 0 123456789 1 0123456789 2 01234 L1 N S1 S2 1 I1 I2 Q1 Q 0 123456789 1 0123456 Let us examine this using our ex ample When switch S1 is closed the status at input I1 is hi IDECSmartRelaycomputes the output states by means...

Page 80: ...shall use the first circuit program as a basis for the sec ond with some slight modifications Let us take a first look at the circuit diagram for the second circuit program In IDEC SmartRelay this is the circuit program layout You can see the OR block and the output relay Q1 we have already used in the first circuit program The only difference is the new off delay block L1 N S1 S2 K1 K1 E1 You alr...

Page 81: ...main menu select Program 3 On the Programming menu select Edit confirm with OK Next select Edit Prg and confirm with OK If required enter your password at the prompt and con firm with OK You can now modify the current circuit program Adding a block to a circuit program Move the cursor to the B in B1 B1 is the number of the OR block We now insert the new block at this position Confirm with OK Q1 B1...

Page 82: ...use to start the off delay time In our example the OR block B1 triggers the off delay You reset the time and the output with a signal at the reset input Set the off de lay time at parameter T of the input Par Q1 SF The SF list contains the special function blocks Trg Par Q1 When you select a special or basic function block IDEC SmartRelay shows you the rele vant function block The solid square cur...

Page 83: ... parameters in the parameter assignment window To change the time value Press and to position the cursor Press and to modify the value at the relevant posi tion Confirm your entries with OK x B1 Par Q1 B2 This is what the display should now show B2 R T 00 00s T The block pa rameter B2 is a time function means The parameter is shown and can be modified in the parameter assignment mode R means Reten...

Page 84: ...ter assignment mode 1 Move the cursor to the protection mode Press or 2 Select the protection mode Press or The display should now show 3 Confirm your entries with OK Enabling disabling retentivity To decide whether you want to retain your current data after a power failure or not 1 Move the cursor to the retentivity setting Press or 2 Select the retentivity setting Press or T 12 00m B2 R T 12 00m...

Page 85: ... or and retentivity R or settings are only shown in the displays where these can ac tually be changed Verification of the circuit program This program branch for Q1 is now completed IDEC Smart Relay shows you the output Q1 You can once again view the circuit program on the display Use the keys to browse the circuit program i e press or to move from block to block and to move between the inputs at ...

Page 86: ... 3 6 8 Deleting a block Let us assume you want to delete the block B2 from your cir cuit program and connect B1 directly to Q1 Proceed as follows 1 Switch the IDEC SmartRelay to programming mode as a reminder refer to page 50 2 Select Edit Press or 3 Confirm Edit Press OK 4 Select Edit Prg Press or 5 Confirm Edit Prg Press OK If required enter your password and confirm with OK 2003 01 27 Mo 09 30 ...

Page 87: ...ectly at the output 3 6 9 Deleting block groups Let us assume you want to delete the blocks B1 and B2 from the following circuit program corresponds with the circuit program in Chapter 3 6 7 Proceed as follows 1 Switch the IDEC SmartRelay to programming mode as a reminder refer to page 50 2 To select Edit Press or 3 To confirm Edit Press OK 4 To select Edit Prg Press or 5 To confirm Edit Prg Press...

Page 88: ...rrecting typing errors Programming errors can be corrected easily in IDEC Smart Relay Provided editing mode is not yet closed you can revert by one step by pressing ESC If you have already configured all inputs simply reconfig ure the faulty input 1 Move the cursor to the faulty position 2 Change to editing mode Press OK 3 Enter the correct input circuit You can only replace a block with a block t...

Page 89: ...o Program Press OK 3 Move the cursor to Clear Prg Press or 4 Confirm Clear Prg Press OK To cancel deletion of the circuit program leave the cursor at No and press OK Program Card Clock Start IDEC SmartRelay opens the main menu Edit Clear Prg Password IDEC SmartRelay changes to the programming menu Clear Prg No Yes ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 ...

Page 90: ... conversion You can enable or disable automatic Summertime winter time conversion in programming mode by calling the Clock menu command 1 Switch the IDEC SmartRelay to programming mode 2 You are now in the main menu and want to select the Clock menu command Press or 3 Confirm Clock Press OK 4 Move the cursor to S W Time Press or 5 Confirm S W Time Press OK Password ZZ To prevent unintentional dele...

Page 91: ...sired conversion Press or What is shown on the display EU represents the start and end of European summer time UK represents the start and end of summertime in the United Kingdom US represents the start and end of summertime in the United States AUS represents the start and end of Australian summer time AUS TAS represents the start and end of Australian Tasmanian summertime NZ represents the start...

Page 92: ...K Last Sunday in March 01 00 02 00 Last Sunday in October 02 00 01 00 60 Min US First Sunday in April 02 00 03 00 Last Sunday in October 02 00 01 00 60 Min AUS Last Sunday in October 02 00 03 00 Last Sunday in March 03 00 02 00 60 Min AUS TAS First Sunday in October 02 00 03 00 Last Sunday in March 03 00 02 00 60 Min NZ First Sunday in October 02 00 03 00 Third Sunday in March 03 00 02 00 60 Min C...

Page 93: ...tem PressOK The display shows Let us assume you want to configure the following parame ters Start of summertime 31st of March end of summer time 1st of November time difference of 120 minutes This is how you can enter your data Press or to move the solid square cursor Press or to change the value at the cursor position On Off S W Time On EU MM DD 01 01 01 01 000min 0 Cursor solid square Month MM a...

Page 94: ...DEC SmartRelay indicates that summertime wintertime conversion is enabled and that user defined parameters have been set Note To disable summertime wintertime conversion in this menu you merely confirm Off with OK 0 MM DD 03 31 11 01 120 min 31 March 1 November Time difference of 120 min On Off S W Time On ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183...

Page 95: ...ic synchronization function is displayed in the bottom row The default setting is Off disabled Enabling synchronization You want to enable synchronization 1 Move the cursor to On Press or 2 Confirm On Press OK IDEC SmartRelay shows the following display When synchronization is enabled IDEC SmartRelay trans mits the time of day to the expansion modules once daily af ter each transition to RUN mode ...

Page 96: ...tation is based on the maximum number of bytes a circuit program may contain The total number of bytes used can be determined by adding up the num ber of bytes used for the relevant function blocks Retentive memory Rem In this area IDEC SmartRelay stores process variables which need to be retentive e g the hours counter value Blocks with optional retentivity use this memory area only if this funct...

Page 97: ...f and on the timer current value of the On delay FB is sometimes reset as shown in Fig 2 Other FBs are shown below Function blocks whose timer current value is sometimes reset Off delay On delay On Off delay Retentive on delay Inter val time delay relay Pulse output Edge triggered interval time delay relay Operating hours counter Asynchronous pulse generator Stairwell Light Switch Dual function sw...

Page 98: ...s Blocks REM 2000 130 60 Function Program memory Rem memory 1 Basic functions AND 12 AND with Edge Detection 12 NAND NOT AND 12 NAND with Edge Detection 12 OR 12 NOR NOT OR 12 XOR exclusive OR 8 NOT Negation 4 Special functions Times On delay 8 3 Off delay 12 3 On Off delay 12 3 Retentive on delay 12 3 Interval time delay relay Pulse output 8 3 Edge triggered interval time delay relay 16 4 Asynchr...

Page 99: ...ll deny ac cess to this list If memory space is fully occupied optimize your circuit pro gram or install a second IDEC SmartRelay Counter Up down counter 24 5 Operating hours counter 24 9 Frequency trigger 16 Analog Analog trigger 16 Analog differential trigger 16 Analog comparator 24 Analog value monitoring 20 Analog amplifier 12 Others Latching relay 8 1 Current impulse relay 12 1 Message texts ...

Page 100: ...tion Memory area Bytes Blocks REM B1 OR 12 1 B2 AND 12 1 B3 Seven day time switch 20 1 B4 On delay 1 1 Configured with retentivity 8 1 3 B5 Stairwell Light Switch 12 1 0 B6 AND 12 1 Resources used by the circuit program 76 6 3 Memory space limits in IDEC SmartRe lay 2000 130 60 Still available in IDEC SmartRelay 1924 124 57 Q1 x I2 B1 B2 B3 x B4 20 No 1 No 2 No 3 I1 Par B5 B6 Par Q2 I3 I4 x REM By...

Page 101: ...ceed as follows 1 Switch the IDEC SmartRelay to programming mode as a reminder refer to page 50 2 Select Edit Press or 3 Accept Edit Press OK 4 Select Memory Press or 5 Accept Memory Press OK The display now shows Free Memory Byte 1924 Block 124 Rem 57 ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 102: ...ts show the elements available in IDEC SmartRelay Usually this includes all connectors basic functions and special functions the IDEC SmartRelay knows This includes all the blocks you have created in IDEC SmartRelay by the time you call the BN list If not all is shown IDEC SmartRelay does not show all elements if No further blocks may be added This is either an indication of insufficient memory sp...

Page 103: ... the I7 and I8 inputs are interpreted as digital values and those at the AI1 and AI2 inputs are inter preted as analog values The inputs of a connected analog module are numbered according to the already existing an alog inputs Special functions whose inputs should only be connected to analog inputs are offered in programming mode when you select the input signal i e the analog inputs AI1 AI8 Anal...

Page 104: ...ext is of significance to a circuit program Memory Markers Memory Markers are identified by the letters M or AM These are virtual outputs which output the value of their in puts IDEC SmartRelay provides 24 Memory Markers M1 M24 and 6 Analog Memory Markers AM1 AM6 L M I13I14I15I16 Q11 Q9 Q12 Q10 RUN STOP L M A 3 RUN STOP L M I1 I2 I3 I4 I5 I6 Q1 Q2 Q3 Q4 AI1 AI2 L M I9 I10I11I12 Q7 Q5 Q8 Q6 RUN STO...

Page 105: ... circuit pro gram The content of shift register bits can only be modified by means of the Shift register special function see Chapter 4 4 25 Cursor keys Up to four cursor keys are available to you namely C C C and C C Cursor Cursor keys are pro grammed for the circuit program in the same ways as other inputs You can set the cursor keys in the corresponding dis play while the system is in RUN see C...

Page 106: ... programming example is found in Chapter 3 6 3 The GF list contains the basic function blocks you can use for your circuit program The following basic functions are available View in the circuit diagram View in IDEC SmartRelay Name of the basic function Series circuit with make contact AND see page 98 AND with Edge Detec tion see page 99 Parallel circuit with break contact NAND NOT AND see page 10...

Page 107: ... break contact NOR NOT OR see page 103 Double changeover contact XOR exclusive OR see page 104 Break contact NOT negation inverter see page 104 View in the circuit diagram View in IDEC SmartRelay Name of the basic function ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 108: ...le of the AND logic 1 2 3 4 Q 0 0 0 0 0 0 0 0 1 0 0 0 1 0 0 0 0 1 1 0 0 1 0 0 0 0 1 0 1 0 0 1 1 0 0 0 1 1 1 0 1 0 0 0 0 1 0 0 1 0 1 0 1 0 0 1 0 1 1 0 1 1 0 0 0 1 1 0 1 0 1 1 1 0 0 1 1 1 1 1 Circuit diagram of a series circuit with several make contacts Symbol in IDEC SmartRelay ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 109: ...nly 1 if all inputs are 1 and if at least one input was low in the previous cycle At an unused block input x x 1 Timing diagram for the AND with Edge Detection Symbol in IDEC SmartRelay 1 3 Q 2 1 2 3 4 5 6 7 8 9 10 4 Cycle ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 110: ... x 1 Table of the NAND logic 1 2 3 4 Q 0 0 0 0 1 0 0 0 1 1 0 0 1 0 1 0 0 1 1 1 0 1 0 0 1 0 1 0 1 1 0 1 1 0 1 0 1 1 1 1 1 0 0 0 1 1 0 0 1 1 1 0 1 0 1 1 0 1 1 1 1 1 0 0 1 1 1 0 1 1 1 1 1 0 1 1 1 1 1 0 Symbol in IDEC SmartRelay Parallel circuit with multiple break contacts in the circuit diagram ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 111: ...ion is only 1 if at least one input is 0 and if all inputs were 1 in the previ ous cycle At an unused block input x x 1 Timing diagram for the NAND with Edge Detection Symbol in IDEC SmartRelay 1 3 Q 2 1 2 3 4 5 6 7 8 9 10 4 Cycle ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 112: ...k input x x 0 Table of the OR logic 1 2 3 4 Q 0 0 0 0 0 0 0 0 1 1 0 0 1 0 1 0 0 1 1 1 0 1 0 0 1 0 1 0 1 1 0 1 1 0 1 0 1 1 1 1 1 0 0 0 1 1 0 0 1 1 1 0 1 0 1 1 0 1 1 1 1 1 0 0 1 1 1 0 1 1 1 1 1 0 1 1 1 1 1 1 Symbol in IDEC SmartRelay Circuit diagram of a parallel circuit with several make contacts ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 113: ...1 status At an unused block input x x 0 Table of the NOR logic 1 2 3 4 Q 0 0 0 0 1 0 0 0 1 0 0 0 1 0 0 0 0 1 1 0 0 1 0 0 0 0 1 0 1 0 0 1 1 0 0 0 1 1 1 0 1 0 0 0 0 1 0 0 1 0 1 0 1 0 0 1 0 1 1 0 1 1 0 0 0 1 1 0 1 0 1 1 1 0 0 1 1 1 1 0 Symbol in IDEC SmartRelay Circuit diagram of a series circuit with several break contacts ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiri...

Page 114: ...antage of the NOT block for example The IDEC Smar tRelay does not require break contacts You simply use a make contact and the NOT block to convert these into a break contact Table of the NOT logic 1 2 Q 0 0 0 0 1 1 1 0 1 1 1 0 1 Q 0 1 1 0 Symbol in IDEC SmartRelay The XOR in a circuit diagram shown as series circuit with 2 changeover contacts Symbol in IDEC SmartRelay A break contact in the circu...

Page 115: ...ontain timer functions retentive functions and various parameter assignment op tions which allow you to adapt the circuit program to suit your own requirements This section provides you with a brief overview of input des ignations and with some particular background information on SFs The SFs in particular are described in Chapter 4 4 ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 G...

Page 116: ...of a function Cnt Count This input is used for counting pulses Fre Frequency Frequency signals to be evaluated are applied to this in put Dir Direction This input determines the direction of count for example En Enable This input enables a block function When this input is 0 other signal from the block will be ignored Inv Invert A signal at this input inverts the output signal of the block Ral Res...

Page 117: ...es and specify whether a message is to be acknowledged in RUN 4 3 2 Time response Parameter T At some of the SFs it is possible to configure a time value T When you preset this time note that your input values are based on the timebase set Note Always specify a time T in 0 02 s The time T is not defined for T 0 02 s Timebase _ _ _ _ s seconds seconds 1 100 seconds m minutes minutes seconds h hours...

Page 118: ...is 5 s day 4 3 3 Backup of the real time clock Because the internal real time clock of a IDEC SmartRelay is backed up it continues operation after a power failure The ambient temperature influences the backup time At an ambient temperature of 25 C the typical backup time is 80 hours 4 3 4 Retentivity The switching states and counter values of SFs can be set retentive This means that current data a...

Page 119: ... of signal lies within the typical range of this sensor IDEC SmartRelay always converts the electrical signals at the analog input into digital values from 0 to 1000 A voltage of 0 to 10V at input AI is transformed internally into range of values from 0 to 1000 An input voltage exceeding 10V is shown as internal value 1000 Because you can not always process the range of values from 0 to 1000 as pr...

Page 120: ...chnical data 30 to 70 C 0 to 10 V DC i e 0 to 1000 in IDEC SmartRelay Actual value internal value gain offset thus 30 0 A B i e offset B 30 70 1000 A 30 i e gain A 0 1 Example 2 A pressure sensor converts a pressure of 1000 mbar into a voltage of 0 V and a pressure of 5000 mbar into a voltage of 10 V Actual value internal value gain offset thus 1000 0 A B i e offset B 1000 5000 1000 A 1000 i e gai...

Page 121: ...1000 mbar 3700 mbar 5000 mbar 0 6 75 10 0 675 1000 4 4 4 1000 1000 1000 1000 3700 5000 0 5 10 0 500 1000 0 01 0 01 0 01 0 0 0 0 5 10 0 5 10 0 500 1000 1 1 1 0 0 0 0 500 1000 0 5 10 0 500 1000 10 10 10 0 0 0 0 5000 10000 0 5 10 0 500 1000 0 01 0 01 0 01 5 5 5 5 10 15 0 5 10 0 500 1000 1 1 1 500 500 500 500 1000 1500 0 5 10 0 500 1000 1 1 1 200 200 200 200 300 800 0 10 0 1000 10 10 10000 10000 10000...

Page 122: ...converts into a logical 1 An example of the program code found in Chapter 3 6 3 The table also specifies whether the relevant function can be set retentivity Rem The following SFs are available View in IDEC SmartRelay Name of the special function Rem Times On delay see page 116 REM Off delay see page 120 REM On Off delay see page 122 REM Retentive on delay see page 124 REM Interval time delay rela...

Page 123: ...e 131 REM Random generator see page 133 Stairwell Light Switch see page 135 REM Dual function switch see page 138 REM Seven day time switch see page 141 Twelve month time switch see page 146 View in IDEC SmartRelay Name of the special function Rem ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 124: ...er see page 158 Analog Analog trigger see page 161 Analog differential trigger see page 164 Analog comparator see page 168 Analog value monitoring see page 173 Analog amplifier see page 176 View in IDEC SmartRelay Name of the special function Rem Fre ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 125: ... REM Current impulse relay see page 179 REM Message texts see page 182 Softkey see page 189 REM Shift register see page 193 REM View in IDEC SmartRelay Name of the special function Rem P En Par Q ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 126: ...alog amplifier actual value Ax see Chapter 4 4 20 and Counter actual value Cnt see Chapter 4 4 13 Select the required function by means of the block number The timebase is adjustable Please note the following listing Symbol in IDEC SmartRelay Wiring Description Input Trg You start the on delay with a negative edge 1 to 0 transition at input Trg Trigger Parameter T represents the time after which t...

Page 127: ...n the example returns a value that lies out of the valid range the value is rounded up or down to the next valid value Timebase max value min resolution Accuracy s seconds 99 99 10 ms 10 ms m minutes 99 59 1s 1 s h hours 99 59 1 min 1 min Timebase max value min resolution Accuracy ms 99990 Number of ms 10 ms s 5999 Number of s 1 s m 5999 Number of min 1 min B12 R T 04 10h B12 R T B006s ngineering ...

Page 128: ... block and its timebase is shown 3 Press to move the cursor to the B of the shown block and then press to select the required block number 4 Press to move the cursor to the block s timebase and press to select the required timebase The view in parameter assignment mode example T 04 10h B12 R T 04 10h B12 R B12 R B12 R T 04 10h T 04 10h Press twice B12 R T B006s B12 R T B006m T 04 10h T 04 10 Ta 02...

Page 129: ... expiration of this time the output follows the input with on delay The time is reset when the status at input Trg returns to 0 be fore the time T has expired The output is reset to 0 when the signal at input Trg is 0 If retentivity is not set output Q and the expired time are re set after a power failure Trg T T Q Ta expires The bold section of the timing diagram is also shown in the On delay ico...

Page 130: ...Ay see Chapter 4 4 18 Analog trigger actual value Ax see Chapter 4 4 16 Symbol in IDEC SmartRelay Wiring Description Input Trg You start the off delay time with a negative edge 1 to 0 transition at input Trg Trig ger Input R A signal at input R resets the on delay time and the output Parameter T is the time that expires af ter which the output is switched off 1 to 0 transition of the output signal...

Page 131: ...s to hi The actual time Ta in IDEC SmartRelay is retriggered at the 1 to 0 transition of Trg The output remains set Output Q is reset to 0 with off delay when Ta reaches the value config ured at T Ta T The time Ta is retriggered with a one shot at input Trg You can set input R Reset to reset the time Ta and the out put before Ta has expired If retentivity is not set output Q and the expired time a...

Page 132: ...negative edge 1 to 0 tran sition at input Trg Trigger triggers the off delay time TL Parameter TH is the time after which the output is set hi output signal transition 0 to 1 TL is the time after which the output is reset output signal transition 1 to 0 Retentivity No retentivity R The status is retentive Output Q Q is set when the configured time TH has expired and Trg is still set It is reset on...

Page 133: ...0 be fore the time TH has expired A 1 to 0 transition at input Trg triggers the time TL If the status at input Trg is 0 at least for the duration of the signal TL the output is set to 0 on expiration of the time TL the output follows the input with off delay The time is reset when the signal at input Trg changes to 1 again before the time TL has expired If retentivity is not set output Q and the e...

Page 134: ...e Ax Ay see Chapter 4 4 18 Analog trigger actual value Ax see Chapter 4 4 16 Analog amplifier actual value Ax see Chapter 4 4 20 and Up down counter actual value Cnt see Chapter 4 4 13 Symbol in IDEC Smart Relay Wiring Description Input Trg A signal at input Trg Trigger triggers the on delay time Input R A signal at input R resets the on delay time and the output Parameter T represents the on dela...

Page 135: ...Trg triggers the current time Ta Output Q is set when Ta T A further signal at input Trg does not influence the time Ta The output and the time Ta are reset with the next 1 signal at input R If retentivity is not set output Q and the expired time are re set after a power failure Trg T Q R T Ta expires The bold section of the timing diagram is also shown in the symbol of the retentive on delay ngin...

Page 136: ...igger triggers the time for the Inter val time delay relay function Parameter The output is switched off af ter the time T has expired output signal transition 1 to 0 Retentivity No retentivity R The status is retentive Output Q A signal at input Trg sets Q If the input signal 1 output Q remains set for the time Ta Trg Q T Ta is expiring The bold section of the timing dia gram also appears in the ...

Page 137: ... Output Q is reset to lo pulse output when Ta reaches the value preset at T Ta T The output is immediately reset if there is a 1 to 0 transition at input Trg before the specified time has expired If retentivity is not set output Q and the expired time are re set after a power failure ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 138: ...he times for the edge triggered interval time delay relay Input R A signal at input R resets the current time Ta and the out put Parameter The interpulse width TL and the pulse width TH are con figurable N determines the number of pulse pause cycles TL TH Range of values 1 9 Retentivity No retentivity R The status is retentive Output Q Q is set after TL has expired and reset after TH has ex pired ...

Page 139: ... TL TH has expired Ta is reset and the pulse pause cycle is restarted If retentivity is not set output Q and the time are reset after a power failure Preset of the Par parameter View in programming mode example Press Trg N 2 Q TL TH TL TH TL TH TL TH Timing diagram for the sample configuration B25 1 R TL 02 00s TH 03 00s Protection mode and retentivity Interpulse width Pulse width B25 2 N 1 Number...

Page 140: ...0 IDEC SmartRelay Manual View in parameter assignment mode example B25 TL 02 00s TH 03 00s Ta 01 15s Current pulse width TL or TH ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 141: ... reset the asynchronous pulse generator Input INV Input INV can be used to in vert the output signal of the active asynchronous pulse generator Parameter You can configure the pulse width TH and the interpulse width TL Retentivity No retentivity R The status is retentive Output Q Q is set and reset cyclically according to the pulse pause ratio TH and TL En Inv TH Q TL TH TL TH TL TH ngineering Inc...

Page 142: ...Time High and TL Time Low parameters Input Inv can be used to invert the output signal provided the block is enabled with a signal at input EN If retentivity is not set output Q and the expired time are re set after a power failure ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 143: ... En Enable triggers the on delay time of the random generator A negative edge 1 to 0 tran sition at input En Enable triggers the off delay time of the random generator Parameter The on delay is set at ran dom to a value between 0s and TH The off delay is set at ran dom to a value between 0s and TL Output Q Output Q is set when the on delay has expired and if En is still set It is reset when the of...

Page 144: ... expired A 1 to 0 transition at input EN triggers a random on delay time between 0s and TL The output is reset after the off delay time has expired pro vided input En remains lo at least for the duration of this time The time is reset if the signal at input En changes to 1 again before the off delay time has expired The time expired is reset after a power failure En Q TL TH T is busy The bold sect...

Page 145: ...rg A signal at input Trg Trigger triggers the off delay time for the Stairwell Light Switch Parameter T represents the off delay time of the output output sig nal transition 1 to 0 T determines the triggering time for the pre warning T L determines the length of the pre warning signal Retentivity No retentivity R The status is retentive Output Q Q is reset after the time T has expired A warning si...

Page 146: ...ing period T L A further one shot at input Trg during Ta retriggers the time Ta If retentivity is not set output Q and the expired time are re set after a power failure Preset of the Par parameter Note the defaults specified in Chapter 4 3 2 Note All times must have the same timebase View in programming mode example Press B9 1 R T 60 00s Protection mode and retentivity Off delay time B9 2 T 05 00s...

Page 147: ...nctions IDEC SmartRelay Manual 137 View in parameter assignment mode example B9 1 T 60 00s Ta 06 00s Current value of T ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 148: ...arameter T represents the time after which f the output is reset output signal transition 1 to 0 TL represents the time during which the output must be set to enable the permanent lighting function T represents the preset time for the start of the off warning signal T L represents the length of the off warning period Retentivity No retentivity R The status is retentive Output Q A signal at Trg swi...

Page 149: ...rior to the expiration of the off delay time T T to reset Q for the duration of the off warning signal T L A further signal at Trg always resets T and the output Q If retentivity is not set output Q and the expired time are re set after a power failure Preset of the Par parameter Note the defaults specified in Chapter 4 3 2 Note T T and T L must all have the same timebase View in programming mode ...

Page 150: ...ter assignment mode example B5 2 T 30 00s T L 20 00s Start of the off warning period T T Off warning time B5 1 T 60 00s TL 10 00s Ta 06 00s Current value of the time TL or T ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 151: ...Timing diagram three examples Cam No1 Daily 06 30 h to 08 00h Cam No2 Tuesday 03 10 h to 04 15h Cam No3 Saturday and Sunday 16 30 h to 23 10h Symbol in IDEC SmartRelay Wiring Description Cam parameters No1 No2 No3 At the Cam parameters you set the on and off times of the Seven day time switch for each Cam switch Here you also configure the days and the time of day Output Q Q is set when the config...

Page 152: ...e cam3 takes priority over cam2 whereas cam2 takes priority over cam1 The switching state of the Seven day time switch is deter mined by the status of all three cams Parameter assignment screen form View of the parameter assignment screen form for example for Cam1 Weekday The suffix of D Day has the following meaning M Monday T Tuesday W Wednesday T Thursday F Friday S Saturday S Sunday The upperc...

Page 153: ... position of the on time 5 Set the on time Modify the value at the respective position using the keys and Move to the cursor to the various posi tions using the keys and At the first position you can only select the value means No on off times set 6 Press to move the cursor to the first position of the off time 7 Set the off time in same way as in step 5 8 Confirm your entries with OK The cursor i...

Page 154: ...ires three cams Here are the parameter assignment screen forms of the cams No 1 2 and 3 based on the timing diagram shown ear lier Cam1 Cam No1 must set the output of the Seven day time switch daily from 05 30 h to 07 40 h Cam2 Cam No2 must set the output of the Seven day time switch every Tuesday from 03 10 h to 04 15 h B1 1 D MTWTFSS On 05 30 Off 07 40 B1 2 D T On 03 10 Off 04 15 ngineering Inc ...

Page 155: ...ven day time switch switch every Saturday and Sunday from 16 30 h to 23 10 h Result B1 3 D SS On 16 30 Off 23 10 Q 1 1 2 3 1 1 1 1 1 3 Cam Monday Tuesday Wednesday Thursday Friday Saturday Sunday ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 156: ... time The off date iden tifies the day on which the output is reset again The first val ue identifies the month the second the day For MM you can select a placeholder so that the on and off time is set for a specific day each month Symbol in IDEC SmartRelay Wiring Description Cam parameter At the Cam parameter you configure the on off times for the cam of the Twelve month time switch Output Q Q is...

Page 157: ...nth time switches with corresponding on times The outputs are then logically linked by means of an OR block Result B1 MM DD On 03 01 Off 04 04 On time March 1 Off time April 4 B2 MM DD On 07 07 Off 11 19 In addition On time July 7 Off time November 19 On Off B1 B2 March 1 at 00 00 h April 4 at 00 00 h November 19 at 00 00 h July 7 at 00 00 h ngineering Inc 230 Ryan Way South San Francisco CA 94080...

Page 158: ...n time is the first and off time the second day each month B12 DD On 10 Off 20 Each month from the 10th through to the 20th B13 DD On 25 Off 05 In the next month from the 25th through the 5th ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 159: ...cription Input R A signal at input R resets both the internal count value and the output to zero Input Cnt The function counts the 0 to 1 transitions at input Cnt 1 to 0 transitions are not counted Use inputs I5 I6 for high speed counting only FL1C H12RCE FL1C B12RCE and FL1C H12SND max 2 kHz any other input or circuit component for counting low frequency signals 5 Hz Input Dir You set the directi...

Page 160: ...ed time are re set after a power failure Q is set or reset depending on the current value at Cnt and the set thresholds See the calculation rule below Parameter On On threshold Range of values 0 999999 Off Off threshold Range of values 0 999999 Retentivity for internal counter value Cnt No retentivity R The status is retentive Output Q Q is set or reset depending on the current value at Cnt and th...

Page 161: ...e Chapter 4 4 20 and Up down counter actual value Cnt Select the required function by means of the block number For information on parameter defaults refer to Chapter 4 4 1 Note The system scans the counter limit value cyclically Thus if the pulse frequency at the fast inputs I5 I6 is faster than the cycle time the special function might not switch until after the spec ified limit value is exceede...

Page 162: ...ut of the valid range the value is rounded to the next valid value The view in parameter assignment mode example B3 R On 001234 Off 000000 B3 R On 123456 Off B021 or B3 On 001234 Off 000000 Cnt 000120 B3 On 123456 Off B021 Cnt 000120 or Current count value ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 163: ...ed value MI at the counter for the duration of the time to go MN Input En En is the monitoring input IDEC SmartRelay scans the on time of this input Input Ral A positive edge at input Ral Re set all resets both the Operating hours counter OT and the out put and sets the configured val ue MI at the counter to for the duration of the time to go MN That is output Q 0 measured operating time OT 0 and ...

Page 164: ...al to be preset in hour units Range of values 0000 9999 h OT Total operating time Range of values 00000 99999 h Q 0 When R is selected Q 1 if MN 0 Q 0 if R 1 or Ral 1 When R En is selected Q 1 if MN 0 Q 0 if R 1 or Ral 1 or En 0 Output Q The output is set when the time to go MN 0 The output is reset When Q 0 R En if R 1 or Ral 1 or En 0 When Q 0 R if R 1 or Ral 1 ngineering Inc 230 Ryan Way South ...

Page 165: ...r ating hours counter OT continues the count With a signal at the reset input Ral you reset output Q and set the preset value of MI at the counter for the duration of MN The Operating hours counter OT is reset to zero Depending on your configuration of parameter Q the output is either reset with a signal at input R or Ral Q 0 R or when a reset signal is set hi or the En signal is set lo Q 0 R En P...

Page 166: ...continues the count as long as En 1 irrespective of the status at the reset input R The counter limit of OT is 99999 h The Operating hours counter stops when it reaches this val ue In programming mode you can set the initial value of OT The counter starts operation at any value other than zero MN is automatically calculated at the START based on the MI and OT values Example MI 100 OT 130 the resul...

Page 167: ...martRelay Manual 157 View in parameter assignment mode B16 MI 0100h MN 0017h OT 00083h Time interval Time to go Total operating hours ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 168: ...ts I5 I6 for high speed counting only FL1C H12RCE FL1C B12RCE and FL1C H12SND max 2 kHz any other input or circuit com ponent for counting low fre quency signals 5 Hz Parameter On On threshold Range of values 0000 9999 Off Off threshold Range of values 0000 9999 G_T Time interval or gate time during which the input pulses are measured Range of values 00 05 s 99 99 s Output Q Q is set and reset at ...

Page 169: ...culation rule If the On threshold Off threshold then Q 1 if fa On Q 0 if fa Off If the On threshold Off threshold then Q 1 if On fa Off Preset of the Par parameter Note The system scans the counter limit value once per interval G_T View in programming mode example Q Off 5 fa 9 fa 10 fa 8 fa 4 G_T Fre On 9 fa Input frequency B15 1 On 0009 Off 0005 Parameter protection mode On threshold Off threshol...

Page 170: ...urns the current frequency in parameter fa in Hz View in parameter assignment mode example Note fa always represents the total pulses measured per time unit G_T B15 2 G_T 01 00s Time interval for pulses example B15 On 0009 Off 0005 fa 0010 On threshold Off threshold Q 1 fa On ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 171: ...analyzed at input Ax Use the analog inputs AI1 AI8 the Analog Memory Markers AM1 AM6 the block num ber of a function with analog output Parameter A Gain Range of values 00 00 10 00 B Zero offset Range of values 10 000 On On threshold Range of values 20 000 Off Off threshold Range of values 20 000 p Number of decimals Range of values 0 1 2 3 Output Q Q is set or reset by the threshold triggers ngin...

Page 172: ...on The function fetches the analog signal at input Ax Ax is multiplied by the value of the A gain parameter and the value at parameter B offset is added to product i e Ax gain offset actual value of Ax Output Q is set or reset depending on the set thresholds See the calculation rule below Calculation rule If the On threshold Off threshold then Q 1 if the actual value Ax On Q 0 if the actual value ...

Page 173: ...ew in parameter assignment mode example View in the message text example B3 1 On 04000 Off 02000 Parameter protection mode On threshold Off threshold B3 2 A 01 00 B 00000 p 2 Gain Offset Decimals in the message text B3 On 04000 Off 02000 Ax 05000 On threshold Off threshold Q 1 AX On 050 00 Ax when p 2 Q 1 AX On ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670...

Page 174: ...t input Ax Use the analog inputs AI1 AI8 the Analog Memory Markers AM1 AM6 the block num ber of a function with analog output Parameter A Gain Range of values 00 00 10 00 B Zero offset Range of values 10 000 On On Off threshold Range of values 20 000 Differential value for calculating the off parameter Range of values 20 000 p Number of decimals Range of values 0 1 2 3 Output Q Q is set or reset d...

Page 175: ...unctional description The function fetches the analog signal at input Ax Ax is multiplied by the value of the A gain parameter and the value at parameter B offset is added to product i e Ax gain offset actual value of Ax Output Q is set or reset depending on the set On threshold and difference value The function automatically calcu lates the Off parameter Off On whereby may be positive or negative...

Page 176: ... B Preset of the Par parameter The gain and offset parameters are used to adapt the sen sors to the relevant application View in programming mode example Press View in parameter assignment mode example B3 1 On 04000 02000 Parameter protection mode On Off threshold Differential value for the on off threshold B3 2 A 01 00 B 00000 p 2 Gain Offset Decimals in the message text B3 On 04000 02000 Ax 0500...

Page 177: ...IDEC SmartRelay functions IDEC SmartRelay Manual 167 Press B3 Off 02000 Off threshold ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 178: ...ce you want to analyze at the inputs Ax and Ay Use the analog inputs AI1 AI8 the Analog Memory Markers AM1 AM6 the block num ber of a function with analog output Parameter A Gain Range of values 00 00 10 00 B Zero offset Range of values 10 000 On On threshold Range of values 20 000 Off Off threshold Range of values 20 000 p Number of decimals Range of values 0 1 2 3 Output Q Q is set or reset depe...

Page 179: ... the analog values from the inputs Ax and Ay Ax and Ay are each multiplied by the value of the A gain pa rameter and the value at parameter B offset is then added to the relevant product i e Ax gain offset actual value Ax or Ay gain offset actual value Ay The function forms the difference between the actual values Ax Ay Output Q is set or reset depending on difference of the ac tual values Ax Ay a...

Page 180: ...ontrol system the supply Tv and return line temperatures Tr are to be compared for example with a sen sor at AI2 A control signal is to be triggered for example heater On when the difference between the supply and return line tem peratures is greater than 15 The control signal is reset when the difference is less than 5 C The process variable of the temperature is to be shown in parameter assignme...

Page 181: ... 30 to 70 C 0 to 10 V DC 0 to 1000 0 C 300 Offset 30 Range of values 30 to 70 C 100 1000 Gain 100 1000 0 1 On threshold 15 C Threshold 15 Off threshold 5 C Threshold 5 B3 1 On 00015 Off 00005 Protection mode On threshold Off threshold B3 2 A 00 10 B 00030 p 0 Gain Offset Decimals in the message text if used B3 1 On 00015 Off 00005 On threshold Off threshold ngineering Inc 230 Ryan Way South San Fr...

Page 182: ...comparator out put is longer than the on delay time With off delay output Q is only reset if the pulse width of the triggering signal at in put Trg is longer than the off delay time Using this method you will obtain a virtual hysteresis and re duce the input response to short signals Function block diagram B3 2 Ax 00010 Ay 00020 00030 Temperature values Q 1 differential value On Ax 00010 Ay 00020 ...

Page 183: ... saves the analog val ue at input Ax Aen to memory and starts monitoring of the ana log range Aen Input Ax You apply the analog signal to be monitored at input Ax Use the analog inputs AI1 AI8 the Analog Memory Markers AM1 AM6 the block number of a function with analog output Parameter A Gain Range of values 00 00 10 00 B Zero offset Range of values 10 000 Difference value for the Aen on off thres...

Page 184: ...red to as Aen Both the analog actual values Ax and Aen are multiplied by the value at parameter A gain and parameter B offset is then added to the product i e Ax gain offset Actual value Aen when input En chang es from 0 to 1 or Ax gain offset Actual value Ax Output Q is set when the signal at input En 1 and if the ac tual value at input Ax is out of range of Aen Output Q is reset when the actual ...

Page 185: ...ew in programming mode Press View in parameter assignment mode example B3 1 00000 Parameter protection mode Differential value for the on off threshold B3 2 A 00 00 B 00000 p 0 Gain Offset Decimals in the message text B3 00010 Aen 00020 Ax 00005 Q 1 Ax is out of the range of Aen ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 186: ...l in IDEC SmartRelay Wiring Description Input Ax You apply the analog signal to be amplified at input Ax Use the analog inputs AI1 AI8 the Analog Memory Markers AM1 AM6 the block number of a function with analog output Parameter A Gain Range of values 00 00 10 00 B Zero offset Range of values 10 000 p Number of decimals Range of values 0 1 2 3 Output AQ This special function has an an alog output ...

Page 187: ...t i e Ax gain offset actual value Ax The actual value Ax is output at AQ Preset of the Par parameter The gain and offset parameters are used to adapt the sen sors to the relevant application View in programming mode example View in parameter assignment mode example B3 A 02 50 B 00300 p 0 Gain Offset Decimals in the message text B3 AQ 00250 ngineering Inc 230 Ryan Way South San Francisco CA 94080 6...

Page 188: ...urrent status of the output signal is retained after a power failure Symbol in IDEC SmartRelay Wiring Description Input S You set output Q with a sig nal at input S Input R You reset output Q with a signal at input R If S and R 1 the output is reset Parameter Retentivity No retentivity R The status is retentive Output Q Q is set with a signal at input S and reset with a signal at input R Sn Rn Q C...

Page 189: ...tput Q with a sig nal at input S Input R You reset output Q with a signal at input R Parameter Selection RS R input priority or SR S input priority Retentivity No retentivity R The status is retentive Output Q Q is set with a signal at Trg and reset with the next signal at Trg if S and R 0 Trg Q R S The bold printed section of the timing diagram is also shown in the symbol for the current impulse ...

Page 190: ...e the output is set hi You reset the current impulse relay with a signal at input R i e the output is set lo Status diagram RS or SR Triggering signal is effective because S and R 0 Par Qn 1 S R Trg Qn 0 0 0 0 0 0 0 0 0 1 1 0 0 1 0 0 0 0 1 0 1 0 0 1 0 0 1 0 1 0 0 1 1 RS 0 1 1 0 0 RS 0 1 1 0 1 0 SR 0 1 1 0 1 SR 0 1 1 0 1 1 1 0 0 0 1 1 0 0 0 1 0 1 0 1 0 0 1 0 1 0 1 0 1 1 0 0 1 1 1 0 0 1 1 RS 1 1 1 0...

Page 191: ...rrent impulse relay and output Q are reset if you have not enabled retentivity View in programming mode This special function is not available in parameter assign ment mode Note If Trg 0 and Par RS the special function Current impulse relay corresponds with the special function Latching relay see Chapter 4 4 21 B29 R Par RS B29 R Par SR Press or ngineering Inc 230 Ryan Way South San Francisco CA 9...

Page 192: ...arameter Text Input of the message text Par Parameter or actual value of another al ready programmed function see Visible parameters or process variables Time Display of the continu ously updated time of day Date Display of the continu ously updated date EnTime Display of the time of the 0 to 1 transi tion of the signal at input En EnDate Display of the date of the 0 to 1 transi tion of the signal...

Page 193: ...ges from 1 to 0 the message text is output until it is acknowledged with OK When En 1 you can not acknowledge the message text When multiple message text functions are triggered with En 1 the message text that has the highest priority is shown 0 lowest 30 highest This also means that a newly ac tivated message text is shown only if its priority is higher than that of previously activated message t...

Page 194: ...tor 2 3000 hours MAINTENANCE Motor 5 STOP AT 10 12 Action Display field of the IDEC SmartRelay in RUN mode Press Press Example Message text with priority 30 Example Message text with priority 10 Date and current time of day only for versions with real time clock B33 Priority 00 Quit Off means The parameters and actual values in an active message text can be edited Priority Status of the acknowledg...

Page 195: ... Edge triggered interval time de lay relay Ta TH TL Asynchronous pulse generator Ta TH TL Random generator TH TL Stairwell Light Switch Ta T T T L Dual function switch Ta T TL T T L Seven day time switch 3 on off day Twelve month time switch On Off Counter Up down counter Cnt On Off Operating hours counter MI Q OT Frequency trigger fa On Off G_T Analog Analog trigger On Off A B Ax Analog different...

Page 196: ...ou must keep the ESC key pressed at least for one second Press and to select the relevant line you can only se lect lines that contain parameters Press OK to change the parameter Use the keys and Analog value monitoring A B Ax Aen Analog amplifier A B Ax Miscellaneous Latching relay Current impulse relay Message texts Softkey On Off Shift register Special function Parameter or process vari able vi...

Page 197: ... select a line for the message text Press or to select the relevant type of message text Text Par Time Confirm with OK Further entries are required when Text or Par are select ed Press or to select the letter to be displayed in the text To move the cursor from one position to the other press or The list of available characters is here the same as for the circuit program name The character set is f...

Page 198: ...K to open the editing mode Press or to select the blocks to be displayed and the corresponding parameters Press or to select the block or parameter you want to view Select the parameter by pressing OK Press ESC to exit the parameter assignment mode and to apply your changes Par B01 T ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 199: ...confirmed in parameter assignment mode Parameter Programming mode Selecting the function for pushbutton action for the du ration of one cycle or for switching action Start On or off state initial ized at the first start of the program if retentiv ity is disabled Retentivity No retentivity R The status is retentive Parameter assignment mode RUN mode Switch Switches the mo mentary pushbutton or swit...

Page 200: ...tion Off was selected at the Switch pa rameter and confirmed with OK in parameter assignment mode If retentivity is not set output Q is initialized after a power fail ure according to your configuration at the Start parameter Preset of the Par parameter View in programming mode example 1 Select the SoftkeyE function 2 Select input En and confirm with OK The cursor is now positioned below Par 3 Cha...

Page 201: ...elay shows the following display Let us assume you want to set Switch On 1 Change to the editing mode Confirm with OK the cursor is now positioned on Off 2 To change from Off to On Press or 3 Confirm your entries with Press OK B33 On Off Start On The status is not retentive Switch function Q is set in the first cycle after the program start B33 On Off Start Off The status is not retentive Switch f...

Page 202: ...tRelay functions 192 IDEC SmartRelay Manual B33 Switch On The momentary pushbutton switch is here switched on ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 203: ... function Input Trg A positive edge 0 to 1 transi tion at input Trg Trigger starts the special function 1 to 0 transitions are irrelevant Input Dir The signal at input Dir deter mines the shifting direction for the shift register bits S1 S8 an Dir 0 Shift up S1 S8 Dir 1 Shift down S8 S1 Parameter Shift register bit that deter mines the value at output Q Possible settings S1 S8 Retentivity No reten...

Page 204: ... is shifted to S7 the previous value at S7 is shifted to S6 etc Output Q returns the value of the configured shift register bit If retentivity is disabled the shift function restarts at S1 or S8 after a power failure When enabled retentivity always ap plies to all shift register bits Note The special function shift register can be used only once in the cir cuit program Timing diagram Trg In Q Dir ...

Page 205: ...eter View in programming mode Press This special function is not available in parameter assign ment mode B3 R Q S8 Retentivity enabled Preset B3 R Q S7 etc You can select S8 S1 ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 206: ... programming mode the author of the circuit program also sets the parameters We have added the parameter assignment mode to allow the editing of parameters without having to modify the circuit program This feature is available for the user to edit param eters without having to change to programming mode for example The advantage The circuit program remains pro tected but can be adapted by the user...

Page 207: ...llowing applies to earlier device versions up to 0BA2 You open parameter assignment mode by pressing ESC OK IDEC SmartRelay changes to parameter assignment mode and opens the parameter assignment menu 2003 01 27 Mo 09 00 ESC Press Stop Set Param Set Clock Prg Name ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 208: ...Set Param For information on the various parameters refer to the Chapters 5 1 1 to 5 1 3 Set clock The Set Clock command is only executed if your IDEC SmartRelay is equipped with a real time clock FL1C J12RC You set the real time clock of IDEC SmartRelay by means of the Set Clock command For details refer to Chapter 5 2 Prg Name This menu command only allows you to read the name of your circuit pr...

Page 209: ...arameters are for example The delay times of a time relay The switching times cams of time switch Counter thresholds The monitoring time for hour counters The trigger thresholds Each one of the parameters is identified by its block number Bx and the shortname of the parameter Examples T is a configurable time MI is a configurable time interval Note WindLGC also allows you to assign names to blocks...

Page 210: ...signment menu 3 Now select the desired parameter Press or 4 Select the parameter you want to edit and press OK Stop Set Param Set Clock Prg Name B9 1 Press ESC No Param T 60 00s Ta 06 00s Block number Display number for functions with several displays The value set at parameter T Time The current time in the IDEC SmartRelay No parameters for editing Press ESC to return to the parameter assignment ...

Page 211: ... in RUN you can also change the timebase s seconds m minutes h hours This does not apply if the time parameter rep resents the result of another function for an example see Chap ter 4 4 1 In this case you can neither change the value nor the timebase The current time is reset to zero when you change the timebase Current value of a time T View of a time T in parameter assignment mode You can change...

Page 212: ...d represents the result of another func tion in the example this is B21 see Chapter 4 4 13 Current value of an hour counter View of an hour counter parameter in parameter assignment mode You can edit the configured time interval MI B1 1 Off 10 00 D M W F On 09 00 B3 On 001234 Off 000000 Cnt 000120 B3 On 123456 Off B021 Cnt 000120 or Current count value B16 MI 0100h MN 0017h OT 00083h Time interval...

Page 213: ...gger View of the parameter of a frequency trigger in parameter assignment mode You can change the on off threshold B15 On 0009 Off 0005 fa 0010 On threshold Off threshold Process variable ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 214: ...5 To change the value Press or 6 To set the correct TOD repeat steps 4 and 5 7 To set the correct date repeat steps 4 and 5 8 To confirm your entries Press OK To set the TOD and the date in programming mode 1 Select programming mode ESC Stop see Chap ter 3 6 1 2 On the main menu select Clock Press or and then press OK 3 Go to the clock menu and select Set Clock Press or and the press OK You can no...

Page 215: ...ing circuit programs Reproducing circuit programs Write and test your circuit program at the office and then transfer it to a IDEC SmartRelay in the switching cabinet IDEC SmartRelay is supplied with a hood The memory car tridge card is supplied separately Note You do not need a module to backup the circuit program in your IDEC SmartRelay The IDEC SmartRelay circuit program is automatically stored...

Page 216: ...ed in IDEC Smart Relay devices of the FL1C generation When the IDEC SmartRelay system detects such an old memory cartridge card the message Unknown Card Press ESC is output to the display Vice versa an FL1C memory cartridge card can not be used in IDEC SmartRelay devices of the FL1B family Upward compatibility of circuit programs Circuit programs written for the previous versions FL1B can only be ...

Page 217: ...cute this circuit program in IDEC SmartRelay the pro tected memory cartridge card must remain inserted during RUN i e the circuit program stored on the memory cartridge card can not be copied to other IDEC SmartRelay devices Over and above that a protected circuit program is write protected A circuit program with password protection is no longer pro tected after the correct password has been enter...

Page 218: ...d command Press or 3 To apply you entry in Card Press OK 4 Move the cursor to CopyProtect Press or 5 To apply CopyProtect Press OK IDEC SmartRelay shows the following display The current protection setting is shown in the bottom line This function is disabled by default No disabled Password Protection Editing Copying Deleting Yes Yes Yes Yes Yes with password Yes Yes with password Yes No No Yes Ye...

Page 219: ... the circuit program itself must be copied separately from the IDEC SmartRelay to the memory cartridge card can also be done initially You can always change the No status security function disabled to Yes security function enabled A status change from Yes security function enabled to No se curity function disabled is only possible if the memory cartridge card does not contain a circuit program No ...

Page 220: ...rtridge card IDEC SmartRelay outputs the message No Program A removal of the memory cartridge card during RUN will lead to imper missible operating states Always heed the following warning Warning Do not touch the open slot of the memory cartridge card neither with your fingers nor with a metallic or conductive object The memory cartridge card socket may be under voltage if the polarity is reverse...

Page 221: ...ory cartridge removal tool MT 101 and pull the memo ry cartridge straight out Inserting a memory cartridge card The entry of the memory cartridge card slot is chamfered on its bottom right The edge of the memory cartridge card is chamfered accordingly This encoding prevents you from inserting the memory cartridge card the wrong way round Insert the memory cartridge card into the slot and push it i...

Page 222: ...o select the Card command Press or 4 Press OK The transfer menu opens 5 Move the cursor to IDEC SmartRelay Card if re quired Press or 6 Press OK IDEC SmartRelay now copies the circuit program to the memory cartridge card When IDEC SmartRelay has finished copying it automati cally returns you to the main menu Program Card Clock Start IDEC SmartRelay main menu Card Card CopyProtect IDEC SmartRelay P...

Page 223: ...forget to replace the cap If power fails while IDEC SmartRelay is copying the circuit program repeat the process after Power On Note The password X of a protected circuit program in IDEC SmartRelay also applies to the copied program version on your memory car tridge card ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 224: ... the copied program in the IDEC SmartRelay is also protected with the same password Automatic copying during the startup of IDEC SmartRelay Proceed as follows 1 Switch off the power supply to the IDEC SmartRelay POWER OFF 2 Remove the slot cover 3 Insert the memory cartridge card into the relevant slot 4 Switch on the power supply to the IDEC SmartRelay IDEC SmartRelay copies the program from the ...

Page 225: ...m the memory cartridge card to IDEC SmartRelay 1 Insert the memory cartridge card 2 Switch the IDEC SmartRelay to programming mode ESC Stop 3 Move the cursor to Card Press or 4 Press OK The transfer menu opens 5 Move the cursor to Card IDEC SmartRelay Press or 6 Press OK IDEC SmartRelay copies the circuit program from the mem ory cartridge card to IDEC SmartRelay When IDEC Smar tRelay has finished...

Page 226: ...ircuit programs Easy configuration of blocks Transferring the circuit program from the IDEC SmartRelay to the PC and from the PC to IDEC SmartRelay Reading the values of the hour counter Setting the TOD Summertime wintertime conversion Online test Display of status changes and process vari ables of IDEC SmartRelay in RUN mode Status of a digital I O markers shift register bits and cursor keys The ...

Page 227: ... a high degree of freedom and comfort for creating your circuit program WindLGC V4 0 This is the current version of WindLGC You will find all the functions and the functionality of the devices described in this manual in the version 4 0 and later Note Please note that the SmartRelay ladder programming is slightly different from PLC programming In the case of a PLC the output result on each line is...

Page 228: ...ollow the instructions on the screen when you install the driver for the converter Make sure you specify the correct Windows OS version when you select the driver Switching IDEC SmartRelay to PC IDEC SmartRelay mode 1 Switch the IDEC SmartRelay with without display to STOP from your PC refer to the WindLGC Online Help or select the ESC Stop command on a device with dis play and confirm the entry w...

Page 229: ...d with WindLGC is password protected both the circuit program and the password are downloaded to IDEC SmartRelay The password prompt is enabled at the end of the data transfer The upload of a password protected program created in IDEC SmartRelay is only possible after the correct password is entered in WindLGC ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 ...

Page 230: ...it diagram and com pared it with the IDEC SmartRelay solutions You can find solutions for the following tasks Page Stairway or corridor lighting system page 222 Automatic door page 226 Ventilation system page 233 Factory gate page 238 Central controlling and monitoring of several factory gates page 242 Luminous rows page 246 Service water pump page 250 ngineering Inc 230 Ryan Way South San Francis...

Page 231: ...sponsibility We refer to the relevant national standards and system related installation reg ulations Although you have four inputs available for logic operations basic functions see Chapter 4 2 the following figures will only show a maximum of three inputs for reasons of clarity You program this fourth input and assign parameters just like the other three inputs Errors can not be ruled out and th...

Page 232: ...off in order to save energy 8 1 2 Previous solution The two conventional options for switching the lights With a pulse relay With an automatic stairway lighting switch The wiring of both these lighting systems is identical Components used Momentary switches Automatic stairway lighting switch or pulse relay Lights Distribution box Push buttons Distribution with Current impulse relay or automatic st...

Page 233: ...eaning the stairway The switch for permanent lighting is usually located on the auto matic stairway lighting switch and may be difficult or impos sible to access 8 1 3 Lighting system with IDEC SmartRelay A IDEC SmartRelay system allows you to replace the auto matic stairway lighting switch or the Current impulse relay You can also implement both functions timed off delay and Current impulse relay...

Page 234: ...ary functions are entered directly in IDEC SmartRelay Current impulse relay with IDEC SmartRelay Output Q1 is toggled with a pulse signal at input I1 Automatic stairway lighting switch with IDEC SmartRelay Output Q1 is set for the duration of 6 minutes with a pulse signal at input I1 L1 N I1 I3 I6 I7 I8 Q1 Q2 Q3 Q4 L N PE I4 I5 I1 I2 I3 I1 I2 I3 Lamps Switches I1 Q1 x Switch Lamps I1 Q1 T 06 00m M...

Page 235: ... flashing function that indicates that the light is about to be switched off automatically You can integrate various central functions Central off Central on panic button Control of all lamps or individual circuits by means of a daylight control switch Controlling by means of an integrated timer e g permanent lighting only until 24 00 h disabled at specific times Automatically switching off the pe...

Page 236: ...ared When the doorway is cleared the door must close auto matically with a short delay The door is usually driven by a motor that is equipped with a slip coupling This prevents people from being squeezed in and injured The control system is connected to the mains via a master switch B1 B2 Q1 S1 S2 Outside inside Motion detector Limit switch closed Limit switch open Motion detector Master switch Mo...

Page 237: ...ast for a minimum time K4 enables the closing motion 8 2 3 Door control system with IDEC SmartRelay IDEC SmartRelay can simplify this circuit considerably You only need to connect the motion sensors limit switches and the contactor relays to the IDEC SmartRelay K1 K2 K2 K1 K3 K3 S2 S1 K3 B1 B2 K3 K4 K4 B2 K3 B1 S2 L1 N Auxiliary circuit Open Close Open door Waiting time ngineering Inc 230 Ryan Way...

Page 238: ...S1 break contact limit switch close S2 break contact limit switch open B1 make contact infrared motion sensor outside B2 make contact infrared motion sensor inside L1 N I4 I5 I6 I7 I8 Q1 Q2 Q3 Q4 K1 K2 B1 B2 S2 S1 L1 N I1 I2 I3 1 2 1 2 1 2 1 2 Open Close ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 239: ...Relay functions You can use the off delay function to replace the latching relay and the on delay The block dia gram below illustrates this simplification 1 1 1 I4 I3 Q2 Q1 RS I1 I2 1 I4 T 4s x x Q1 Q2 Open Close 1 1 1 I4 I3 I1 I2 x Q2 Q1 x 10 s Q1 Q2 Open Close Close Motion detector Limit switch Door open Limit switch Door closed ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 Gener...

Page 240: ...EC Smar tRelay to warn of the closing of the door You can enable opening of the door time and direc tion dependent i e opening only during business hours and opening only from the inside after closing time 8 2 5 Extended solution with FL1C H12RCC Wiring the IDEC SmartRelay extended solution L1 N I4 I5 I6 I7 I8 K1 K2 B1 B2 S2 S1 L1 N S3 H1 Q1 Q2 Q3 Q4 I1 I2 I3 1 2 1 2 1 2 1 2 Open Close Buzzer ngin...

Page 241: ...00 Cam1 Day Mo Fr On 09 00 Off 19 00 Cam2 Day Sa On 08 00 Off 14 00 Motion detector B1 Motion detector B2 Actuate motor for opening Open Close Close output Limit switch Door open Control switch Door open Actuate motor for closing Limit switch Door closed Open output Motion detector B1 Motion detector B2 Control switch Close door ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General...

Page 242: ... nently open or The motion detectors indicate that somebody is ap proaching the door and The door has not yet fully opened limit switch at I4 Actuating the motor for closing Output Q2 is set to close the door when The control switch at I6 is actuated the door is perma nently closed or The motion detectors indicate that there is nobody near the door and The door has not yet fully closed limit switc...

Page 243: ...equipped with an exhaust fan and a fresh air fan Both fans are monitored by means of a flow sensor An excess atmospheric pressure may never develop in the room The fresh air fan must only be switched on if safe func tioning of the exhaust fan is signaled by the flow sensor A warning lamp indicates failure of a fan Fresh air fan Flow sensor Flow sensor Exhaust fan ngineering Inc 230 Ryan Way South ...

Page 244: ...an monitoring system also requires an evaluating circuit with several switching de vices This evaluating circuit can be replaced by a single IDEC SmartRelay unit Wiring of an air conditioning system with FL1C H12RCC K1 K5 K5 S1 S0 K3 K2 L1 N S2 K1 v S2 H1 K4 S3 v K5 H2 K2 K4 Auxiliary circuit Exhaust air Fresh air Operation Error L1 N I1 I3 I6 I7 I8 Q1 Q2 Q3 Q4 K1 K2 S1 L1 N S2 S3 v v H1 H2 S0 I4 ...

Page 245: ...amp Block diagram of the IDEC SmartRelay solution The block diagram of the air conditioning system with IDEC SmartRelay x I1 Q3 I2 Q1 Q2 Q1 I3 x I2 x T 10 s x T 10 s x x x I3 I4 Q1 Q2 Q3 Exhaust fan On Error Off Exhaust fan Exhaust air flow sensor Fresh air flow sensor Fresh air fan Exhaust fan Exhaust air flow sensor Fresh air fan Error Off ngineering Inc 230 Ryan Way South San Francisco CA 94080...

Page 246: ...t is possible to switch off of the fans by means of a se quential circuit These functions can be implemented without additional switchgear Block diagram of the extended IDEC SmartRelay solution The fans at Q1 and Q2 are switched on and off by means of the following circuit x T 10 s T 30 s Q1 Q2 I2 Q3 x x I3 I2 T 10 s T 10 s x x x I3 I4 Q3 I1 Q2 On Fault Off Exhaust air flow sensor Q1 exhaust fan E...

Page 247: ...Q4 are always closed when the system is in operation Relay Q4 does not drop off unless there is a power failure or a fault in the system This contact can be used for remote monitoring for example Q3 Q4 Error Messege ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 248: ...se The porter can monitor the operation of the gate at the same time The gate is normally fully opened or fully closed The gate motion can be interrupted at any time An indicator lamp is switched on five seconds before the gate starts moving and when the gate is in motion A safety pressure bar prevents harm to persons and ob jects from getting trapped or damaged when the gate is closing Safety pre...

Page 249: ...control system with FL1C H12RCC K1 K5 K3 S1 S0 K3 K2 L1 N K1 H1 K4 S5 p K6 K6 K1 S2 S2 K3 K2 K4 K5 S5 p S1 K3 K1 S4 S3 Open Close Indicator lamp Open Close Auxiliary circuit L1 N I4 I5 I6 I7 I8 Q1 Q2 Q3 Q4 K1 K3 S4 S3 L1 N S1 S2 S0 S5 p S5 p H1 I1 I2 I3 1 2 1 2 1 2 1 2 Open Close Indicator lamp ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 250: ...ate motion provided it is not already moving in the other direction The gate is stopped by means of the STOP pushbutton or the rel evant limit switch A safety bar furthermore interrupts the closing motion of the gate T 5 s T 5 s x x x x Q1 Q3 Q2 I3 I4 I3 I6 I5 I1 I2 Q2 Q1 TH TL 2 s Inv lo I2 I1 Start push button CLOSED Start push button OPEN STOP push button Gate is open CLOSE push button CLOSE pu...

Page 251: ...n the safety bar is actuated x x I6 x Q2 I3 I4 x I1 Q2 T 5 s Q1 T 5 s x Q2 I3 I6 I5 I2 Q1 Q3 TH TL 2 s Inv lo Safety bar STOP pushbutton Gate is open OPEN pushbutton CLOSE pushbutton STOP pushbutton Safety bar Gate is closed Open Signal lamp Close ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 252: ...atehouse It must also be possible for a member of staff to open and close the gate locally For each gate we are going to use one FL1C H12RCC and one communication module The modules and the master are interconnected by means of a bus system This chapter describes a gate control system The structures of the other gate control systems are identical 1 2 1 2 1 2 Door I Door II Door III 1 Safety bar 2 ...

Page 253: ... or GATE CLOSED status is indicated An indicator lamp is switched on five seconds before the gate starts moving and when the gate is in motion A safety pressure bar prevents harm to persons and ob jects from getting trapped or damaged when the gate closes Wiring of the gate control system with FL1C H12RCC and CM AS Interface N L1 N I3 I4 I5 I6 I7 I8 K1 K2 L1 S0 S1 S2 S3 S4 S5 S6 p S6 p I2 I1 Q1 Q2...

Page 254: ...utton S3 make contact CLOSE pushbutton S4 break contact position sensor GATE IS OPEN S5 break contact position sensor GATE IS CLOSED S6 break contact Safety bar Master control system Q5 position sensor GATE IS OPEN Q6 position sensor GATE IS CLOSED I9 external pushbutton OPEN GATE I10 external pushbutton CLOSE GATE ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800...

Page 255: ...pective limit switch Closing of the gate is also interrupted by the safety bar Gate is open Open gate Open gate Gate is open Open gate by hand Gate is open Close gate by hand Gate is closed Safety bar Gate is closed Close Closed Safety bar Gate is closed Safety bar Gate is open Gate is closed Open Close Indica tor lamp Close gate Open gate ngineering Inc 230 Ryan Way South San Francisco CA 94080 6...

Page 256: ...e way the room is used 8 6 1 Requirements for a lighting system The various luminous rows are switched on and off local ly If there is sufficient daylight the rows on the window side of the room are automatically switched off by means of a daylight control switch The lights are switched off automatically at 20 00 h Local manual operation of the lighting must be possible at all times Luminous rows ...

Page 257: ...red Pushbuttons S1 to S4 Daylight control switch B1 Timer E1 Interval time delay relays K1 and K2 Pulse switches K3 to K6 with central OFF function Disadvantages of the previous solution A substantial amount of switchgear needs to be installed to implement the necessary functions Due to the large number of mechanical components high wear and tear and maintenance expenditure is to be ex pected The ...

Page 258: ...ontact momentary pushbutton B1 make contact daylight control switch L1 N I6 I7 I8 Q1 Q2 Q3 Q4 L1 N E2 E3 E4 B1 lx E5 S1 S2 S3 S4 I4 I5 I1 I2 I3 1 2 1 2 1 2 1 2 Luminous rows 1 Luminous rows 2 Luminous rows 3 Luminous rows 4 ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 259: ...an install a smaller and space saving distribution cabinet Fewer devices are required The lighting system can be easily modified Additional switching times can be set as required se quential circuit for the off pulses at the end of the day The function of the daylight control switch can be easily applied to all lamps or to a modified group of lamps x T 1s I5 T 1s x I5 I1 I2 I3 I4 x x Off pulse tri...

Page 260: ...stem is operated The rainwater is collected in a reservoir From the reservoir a pumping station supplies a respective line system From there it can be tapped in the same way as normal drinking water If the reservoir should run dry it can be topped up with drinking water S1 S2 S3 S4 M1 K4 Rainwater supply line Drinking water supply line Pressure switch Control in the distribution box Pressure tank ...

Page 261: ...tion The pump and a solenoid valve are controlled by means of a pressure switch and 3 float switches which are installed in the rainwater reservoir The pump must be switched on when the pressure level in the boiler drops below minimum After the operating pressure is reached the pump is switched off again after a tracking time of a few seconds has expired The tracking time prevents oscillation of t...

Page 262: ...ay if the power consumption of the AC motor exceeds the capacity of the output relay Q1 The power consumption of a solenoid valve is usually low enough to allow direct controlling K1contactor relay Y1solenoid valve S1 make contact pressure switch S2 make contact float switch S3 break contact float switch S4 break contact float switch L1 N I4 I5 I6 I7 I8 Q1 Q2 Q3 Q4 K1 Y1 S4 S3 L1 N S1 S2 p I1 I2 I...

Page 263: ...ich can only be implemented in a conventional circuitry by add ing further switchgear e g Enabling the pump at specific times Indication of imminent or existing water shortage Reporting of system faults I2 Q2 I1 I3 I4 x T 20 s x Q1 I3 Pressure switch Float switch for dry run protection OFF Float switch for dry run protection ON Float switch for drin king water supply ON Float switch for drinking w...

Page 264: ...domestic and commercial housing installations Exam ples Domestic security systems IDEC SmartRelay switch es on a lamp at regular intervals or opens and closes the shutters while you are on holiday Central heating IDEC SmartRelay runs the circulation pump only when water or heating is actually required Refrigerating systems IDEC SmartRelay can defrost refrigerating systems at regular intervals to s...

Page 265: ...l applications for the IDEC SmartRelay If you know of one why not write to us We will collect all the suggestions made and distribute as many of them as we can No matter whether your IDEC SmartRelay circuit is particularly complex or simple simply write to us We shall be delighted to receive all your sugges tions ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 6...

Page 266: ...55 mm Approx 90 g on a 35 mm profile rail 4 module widths or wall mounting Climatic conditions Ambient temperature Horizontal installation Vertical installation Low temperature to IEC 60068 2 1 High temperature to IEC 60068 2 2 0 55 C 0 55 C Storage shipping 40 C 70 C Relative humidity IEC 60068 2 30 From 10 to 95 no condensation Air pressure 795 1080 hPa Pollutants IEC 60068 2 42 IEC 60068 2 43 S...

Page 267: ...charge Electromagnetic fields IEC 61000 4 3 Field strength 10 V m HF currents on cables and cable shielding IEC 61000 4 6 10 V Burst pulses IEC 61000 4 4 Severity 3 2 kV supply and sig nal lines High energy surge pulse applies only to FL1C H12RCC IEC 61000 4 5 Severity 3 1 kV power lines symmetrical 2 kV power lines asymmetrical Safety to IEC VDE Clearance and creep age distance rating IEC 60664 I...

Page 268: ...0 V DC 240 V DC 10 40 mA 10 25 mA 5 25 mA 5 15 mA 10 30 mA 10 20 mA 5 15 mA 5 10 mA Voltage failure buffering 100 V AC 240 V AC typ 10 ms typ 20ms typ 10 ms typ 20ms Power loss at 100 V AC 240 V AC 100 V DC 240 V DC 1 1 4 6W 2 4 6 W 0 5 2 9 W 1 2 3 6 W 1 1 3 5W 2 4 4 8 W 0 5 1 8 W 1 2 2 4 W Backup of the real time clock at 25 C typ 80 h 4 Accuracy of the real time clock typ 2 s day Digital inputs ...

Page 269: ...ctrical isolation Yes Yes In groups of 1 1 Control of a digital input Yes Yes Continuous current Ith max 10 A per relay max 5 A per relay Incandescent lamp load 25000 switching cycles at 230 240 V AC 100 120 V AC 1000 W 500 W 1000 W 500 W Fluorescent tubes with ballast 25000 switching cycles 10 x 58 W at 230 240 V AC 10 x 58 W at 230 240 V AC Fluorescent tubes convention ally compensated 25000 swi...

Page 270: ...n B16 900A Derating none across the en tire temperature range none across the en tire temperature range Parallel output circuits for power increase Not permitted Not permitted Protection of output relay if desired max 16 A characteristic B16 max 16 A characteristic B16 Switching rate Mechanical 10 Hz 10 Hz Ohmic load lamp load 2 Hz 2 Hz Inductive load 0 5 Hz 0 5 Hz FL1C H12RCC FL1C B12RCC FL1B M08...

Page 271: ...e mains frequency Power consumption from 24 V DC 30 55 mA 0 3 A per output 30 45 mA 0 3 A per output Voltage failure buffering Power loss at 24 V 0 7 1 3 W 0 8 1 1 W Backup of the real time clock at 25 C Accuracy of the real time clock Digital inputs Number 8 4 Electrical isolation No No Input voltage Signal 0 Signal 1 L 5 V DC 8 V DC L 5 V DC 8 V DC ngineering Inc 230 Ryan Way South San Francisco...

Page 272: ...100 m Analog inputs Number 2 I7 and I8 Range 0 10 V DC input impedance 76 kΩ max input voltage 28 8 V DC Line length shielded and twist ed 10 m Digital outputs Number 4 4 Output type Transistor current sourcing Transistor current sourcing Electrical isolation No No In groups of Control of a digital input Yes Yes Output voltage Supply voltage Supply voltage Output current max 0 3 A max 0 3 A FL1C H...

Page 273: ...circuit current limitation Approx 1 A Approx 1 A Derating none across the en tire temperature range none across the en tire temperature range Short circuit proof cos 1 Short circuit proof cos 0 5 to 0 7 Parallel output circuit for power increase Not permitted Not permitted Protection of output relay if desired Switching rate Mechanical Electrical 10 Hz 10 Hz Ohmic load lamp load 10 Hz 10 Hz Induct...

Page 274: ...AC 24 V DC 40 100 mA 20 75 mA 40 100 mA 20 75 mA Voltage failure buffering typ 5 ms typ 5 ms Power loss 24 V AC 24 V DC 0 9 2 7 W 0 4 1 8 W 0 9 2 7 W 0 4 1 8 W Backup of the real time clock at 25 C typ 80 h typ 80 h Accuracy of the real time clock typ 2 s day Digital inputs Number 8 optional P action or N action 4 optional P action or N action Electrical isolation No No Input voltage Signal 0 Sign...

Page 275: ...utput type Relay outputs Relay outputs Electrical isolation Yes Yes In groups of 1 1 Control of a digital input Yes Yes Output voltage Output current Continuous current Ith max 10 A per relay max 5 A per relay Incandescent lamp load 25000 switching cycles at 1000 W 1000 W Fluorescent tubes with ballast 25000 switching cycles 10 x 58 W 10 x 58 W FL1C H12RCA FL1C B12RCA FL1B M08D2R2 ngineering Inc 2...

Page 276: ...rt circuit proof cos 1 Power protection B16 600A Power protection B16 600A Short circuit proof cos 0 5 to 0 7 Power protection B16 900A Power protection B16 900A Parallel output circuits for power increase Not permitted Not permitted Protection of output relay if desired max 16 A characteristic B16 max 16 A characteristic B16 Switching rate Mechanical 10 Hz 10 Hz Electrical Ohmic load lamp load 2 ...

Page 277: ...g 12 V DC 24 V DC typ 2 ms typ 5 ms typ 2 ms typ 5 ms Power loss 12 V DC 24 V DC 0 3 1 7 W 0 4 1 8 W 0 3 1 7 W 0 4 1 8 W Backup of the real time clock at 25 C typ 80 h Accuracy of the real time clock typ 2 s day Electrical isolation No No Digital inputs Number 8 4 Electrical isolation No No Input voltage L Signal 0 Signal 1 5 V DC 8 V DC 5 V DC 8 V DC Input current at Signal 0 Signal 1 1 0 mA I1 I...

Page 278: ...r 2 I7 I8 Range 0 10 V DC input impedance 76 kΩ max Input voltage 28 8 V DC Line length shielded and twisted 10 m Digital outputs Number 4 4 Output type Relay outputs Relay outputs Electrical isolation Yes Yes In groups of 1 1 Control of a digital input Yes Yes Output voltage Output current FL1C H12RCE FL1C B12RCE FL1B M08B2R2 ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General I...

Page 279: ...mitation Derating none across the en tire temperature range none across the en tire temperature range Short circuit proof cos 1 Power protection B16 600A Power protection B16 600A Short circuit proof cos 0 5 to 0 7 Power protection B16 900A Power protection B16 900A Parallel output circuits for power increase Not permitted Not permitted Protection of output relay if desired max 16 A characteristic...

Page 280: ...rs solenoid coils motors 0 1 0 2 0 3 0 4 0 5 2 4 6 8 10 Switching cycles million 12 24 V AC DC 100 120 V AC 230 240 V AC 120 V DC 240 V DC Switched current A Maximum 10 A Maximum 10 A Maximum 10 A Maximum 0 2 A Maximum 0 2 A 0 1 0 2 0 3 0 4 0 5 3 2 1 0 6 0 7 0 8 0 9 1 0 Switching cycles million 12 24 V AC DC 100 120 V AC 230 240 V AC 120 V DC 240 V DC Switched current A Maximum 2 A Maximum 3 A Max...

Page 281: ...d terminal for connecting ground and shielding of the analog measuring line Analog inputs Number 2 Type Unipolar Input range 0 10 V DC input impedance 76 kΩ or 0 20 mA input impedance 250 Ω Resolution 10 bit normalized to 0 1000 Cycle time for analog value generation 50 ms Electrical isolation No Line length shielded and twisted 10 m Encoder supply voltage none Error limit 1 5 Interference frequen...

Page 282: ... This test program is created in IDEC SmartRelay and returns a value during its execution in parameter assignment mode from which the current cycle time is derived Test program 1 Create the test program by linking an output to a fre quency trigger and connecting the trigger input with an inverted marker 2 Configure the frequency trigger as shown below A pulse is generated in each program cycle due...

Page 283: ...nal at each program execution Thus one logic level high or low width is exactly equivalent to the length of one cycle Hence a pe riod lasts 2 cycles The frequency trigger indicates the ratio of periods per 2 sec onds which results in the ratio of cycles per second B1 1 On 1000 Off 0000 B1 2 G_T 02 00s Press B1 On 1000 Off 0000 fa 0086 fa total of measured pulses per timeba 1 period 1 pulse 2 cycle...

Page 284: ...s less switch cabinet space than conventional hardware Substantial benefits with regard to flexibility and prime costs compared to stand alone electronic switchgear Of advantage even for applications in which merely two or three conventional switching devices can be replaced Very easy to use Access protected Compatible to IDEC SmartRelay versions with display Offers the option to read data by mean...

Page 285: ...d by means of buttons This is why the FL1C B12 versions have other startup characteristics Startup characteristics If there is no circuit program in the IDEC SmartRelay or on the inserted memory cartridge card IDEC SmartRelay re mains in STOP If there is a valid circuit program in IDEC SmartRelay mem ory the IDEC SmartRelay automatically switches from STOP to RUN when power is switched on The circ...

Page 286: ...ent data WindLGC see Chapter 7 provides an online test for reading the current data of all functions while the system is in RUN If your IDEC SmartRelay without display holds a protected memory cartridge card you can not read the current data unless you enter the correct password for your the circuit program The circuit program is otherwise deleted from IDEC SmartRelay memory when you remove the me...

Page 287: ...rt menu Parameter assign ment menu Parameter setting Chapter 5 1 1 cont Clock date setting Chapter 5 2 Display of the program name See Main menu Main menu ESC Stop See Programming menu See Transfer menu See Clock menu See Start menu Programming menu ESC Stop Program Editing the program Chapter 3 6 cont Editing the program name Chapter 3 6 4 Show available memory space Chapter 3 7 Deleting the prog...

Page 288: ...rcuit program from IDEC SmartRelay to the memory cartridge card Chapter 3 6 Copying the program from the memory cartridge card to IDEC SmartRelay Chapter 6 4 Setting the program copy protection Chapter 6 1 Clock menu ESC Stop Clock Setting the time date Chapter 5 2 Setting the summertime wintertime Chapter 3 6 12 cannot be used Start menu RUN max 10 message texts Date time Inputs Outputs Markers C...

Page 289: ...0 240V AC DC 8 4 Yes Yes FL1C B12RCC FL1C H12RCA 24V AC DC 8 4 Yes Yes FL1C B12RCA FL1C H12RCE 12 24V DC 8 I1 I8 2 I7 I8 4 Yes Yes FL1C B12RCE FL1C H12SND 24V DC 8 I1 I8 2 I7 I8 4 Tr Yes Expansion Module FL1B M08B2R2 12 24V DC 4 4 FL1B M08B1S2 24V DC 4 4 Tr FL1B M08C2R2 100 240V AC DC 4 4 FL1B M08D2R2 24V AC DC 4 4 FL1B J2B2 12 24V DC 2 AS Interface Module FL1B CAS2 AS Interface Voltage LON WORKS ...

Page 290: ... incl Hardware Software Manual FL9Y LP1CDW PC Cable Down load Up load Cable FL1A PC1 Memory cartridge Brown FL1C PM3 User s Manual FL1C User s Manual English FL9Y B827 Mounting Clip 5 pieces FL1B PSP1PN05 Removal Tool Memory Cartridge Removal Tool MT 101 ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Page 291: ...ing 76 block groups 77 inserting 71 number 44 assigning 45 BN 92 C Cap 16 Card See memory cartridge card CE label 10 Certification 9 Character set 62 Circuit diagram 47 Circuit program 86 deleting 79 input 56 Circuit program name assigning 62 Circuit programs archiving 205 reproduce 205 Closing the programming mode 76 CM See Communications module Co 92 93 Communications module 1 2 AS Interface 2 7...

Page 292: ... Edge detection 99 101 Edge triggered interval time delay relay 128 Editing 71 Example Air conditioning system 233 Automatic door 226 Factory door 238 factory door controlling 242 monitoring 242 lighting corridor 222 stairway 222 Luminous rows 246 Service water pump 250 exclusive OR 104 Expansion modules 2 Analog module 2 43 Communications module 2 Digital module 43 digital module 2 Operating stat...

Page 293: ...ay 178 LCD 4 5 LED 276 Levels 95 List BN 92 Co 92 93 GF 92 96 SF 92 Logic module 1 Logical inputs 106 M Memory areas 86 free 91 limitation 86 requirements 88 space 86 Memory cartridge card CopyProtect 208 IDEC SmartRelay Card 212 copying 214 Enabling the security function 209 inserting 211 removing 211 Security function 207 Memory Markers 94 Menu Main menu 52 Parameter assignment menu 52 Programmi...

Page 294: ...gital outputs 93 P Parameter 199 Set Param 198 Inputs 107 selecting 200 setting 196 T 107 Parameter assignment 73 Parameter assignment menu 52 197 Parameter assignment screen form 142 184 Parameter protection 109 Parameters modifying 201 parameters showing hiding 74 Password assigning 63 changing 65 deactivating 66 wrong 67 PC cable 218 USB 218 PC IDEC SmartRelay 218 Planning 51 Power supply Conne...

Page 295: ...atus transitions 26 Simulation 216 Size of a circuit 86 Softkey 189 Software 216 Special functions 105 112 Analog amplifier 176 Analog comparator 168 Analog differential trigger 164 Analog trigger 161 Analog value monitoring 173 Asynchronous pulse generator 131 Current impulse relay 179 Dual function switch 138 Edge triggered interval time delay relay 128 Frequency trigger 158 Interval time delay ...

Page 296: ...RCC 258 FL1C H12RCE 267 FL1C H12SND 261 general 256 The 272 Time Accuracy of 107 Time response 107 Timebase 73 107 116 Timer 1 accuracy 108 Timing inaccuracy 108 Transistor outputs 33 Trigger Analog differential trigger 164 Analog trigger 161 Frequency trigger 158 Twelve month time switch 146 Type Numbers 279 U Unused connectors 48 unused connectors 42 Unused inputs 48 Up down counter 149 Upward c...

Page 297: ...Index IDEC SmartRelay Manual 287 X XOR 104 Z Zero offset 109 Manual No FL9Y B827 0 ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste ...

Reviews: