PS3V Switching Power Supplies

Specifications

Part no.

Item

[15W]

PS3V-015AF 

05C / 12C / 24C

[30W]

PS3V-030AF 

05

 / 12

 / 24

[50W]

PS3V-050AF 

12

 / 

24

[100W]

PS3V-100AF2

4

[150W]

P

S3V-150AF

24

Input conditions

Rated input voltage

100 to 240V AC

(Voltage range) (*1)

85 to 264V AC  (Single phase 2 wire)

Frequency

47 to 63Hz

Input current 

(at rated output)

100V: 0.32A (typ) 

230V: 0.2A (typ)

100V: 0.66A (typ) 

230V: 0.35A (typ)

100V: 1.1A (typ) 

230V: 0.6A (typ)

100V: 1.3A (typ) 

230V: 0.6A (typ)

100V: 1.9A (typ) 

230V: 0.9A (typ)

Inrush current

( Ta = 25°, 

cold start)

at 100V AC

40A typ.

18A typ.

18A typ.

18A typ.

18A typ.

at 230V AC

60A typ.

45A typ.

45A typ.

45A typ.

45A typ.

Leakage current

120V: 0.5mA max., 240V: 1mA max.

Efficiency

(TYP.)

(at rated output)

 5V

77% (100VAC)

76% (230VAC)

77% (100VAC)

77% (230VAC)

12V

82% (100VAC)

81% (230VAC)

83% (100VAC)

83% (230VAC)

84% (100VAC)

84% (230VAC)

24V

84% (100VAC)

83% (230VAC)

85% (100VAC)

84% (230VAC)

87% (100VAC)

87% (230VAC)

85% (100VAC)

88% (230VAC)

85% (100VAC)

88% (230VAC)

Power factor (TYP.) 

(at rated output)

0.98 (100V AC)

0.9 (230V AC)

0.98 (100V AC)

0.95 (230V AC)

Output conditions

Output voltage/Current

5V / 3A

5V / 6A

12V / 1.3A

12V / 2.5A

12V / 4.5A

_

24V / 0.63A

24V / 1.3A

24V / 2.3A

24V / 4.5A

24V / 6.5A

Adjustable voltage range

±10% (Front, adjustable using V.ADJ volume)

Output holding time

(at rated output)

 5V

15ms typ. (100V AC)

120ms typ. (230V AC) 18ms typ. (100V AC) 

110ms typ. (230V AC)

12V

17ms typ. (100V AC)

125ms typ. (230V AC)

24V

20ms typ. (100V AC)

130ms typ. (230V AC)

35ms typ. (100V AC)

35ms typ. (230V AC)

24ms typ. (100V AC)

24ms typ. (230V AC)

Start time

650ms max. (at rated input/output)

Rise Time

300ms max. 

(at rated input/output) 200ms max. (at rated input/output)

Constant volta

ge accurac

y

Input fluctuation

0.4% max.

Load fluctuation

1% max.

Temperature fluctuation

0.05%/°C max. (−10 to +50°C)

Ripple

(including 

noise)

−25 to −10°C

  5V: 8%p-p max. 

12V: 6%p-p max. 

24V: 4%p-p max.

  5V: 8%p-p max. 

12V: 6%p-p max. 

24V: 4%p-p max.

12V: 6%p-p max. 

24V: 4%p-p max.

24V: 4%p-p max.

-10 to 0°C

  5V: 5%p-p max. 

12V: 2.5%p-p max. 

24V: 1.5%p-p max.

  5V: 5%p-p max. 

12V: 2.5%p-p max. 

24V: 1.5%p-p max.

12V: 2.5%p-p max. 

24V: 1.5%p-p max.

24V: 1.5%p-p max.

0 to 50°C

  5V: 2.5%p-p max. 

12V: 1.5%p-p max. 

24V: 1%p-p max.

  5V: 2.5%p-p max. 

12V: 1.5%p-p max. 

24V: 1%p-p max.

12V: 1.5%p-p max. 

24V: 1%p-p max.

24V: 1%p-p max.

Supplementar

functions

Overcurrent protection

105% min. (auto reset) (*2)

Overvoltage protection

120% min.

(intermittent, auto reset) Output off at 120% min, reset when re-input

Operation indicator

LED (green)

Dielectric 

strength

Between input and output terminals

3000V AC, 1 minute

Between input and ground terminals 2000V AC, 1 minute
Between output and ground terminals 500V AC, 1 minute

Insulation resistance

100MΩ min. 500V DC megger (at 25°C, 70% RH) (between input and output terminals, between input and ground terminals)

Operating temperature

−25 to +70°C, (no freezing, output derating available)

Operating humidity

20 to 90% RH (no condensation)

Storage temperature

−25 to +75°C (no freezing)

Storage humidity

20 to 90% RH (no condensation)

Vibration resistance

10 to 55 Hz, 2G constant, 2 hours each in 3 axes

Shock resistance

200M/s

2

, 11ms, 1 shock each in 6 axes

Expected life (reference value) (*3)

8 years min. (rated input, load factor 50%, operating tempe40ºC, standard mounting)

EMC

EMI

EN61204-3 Class B

EMS

EN61204-3  (Industrial)

Safety standards

EN62368-1 (TÜV), IEC 62368-1

UL61010-1, UL61010-2-201, CSA C22.2 No.61010-1, CSA C22.2 No.61010-2-201 (Listing, SELV *all models pending)

UL62368-1, CSA C22.2 No.62368-1-14 (Recognition)

Dimensions (mm) (terminal part except 

protrusion)

50.8H×34W×65D

68.5H×34.5W×95.5D 80H×36W×99D

93H×39W×108D

95H×39W×159D

Weight (approx.)

135g

190g

230g

380g

510g

Terminal screw (horizontal type)

M3

M3.5

*1)  Not subjected to safety standards. Output delay also available.
*2)  If overload continues for over 30 seconds, the internal elements may be damaged.  

PS3V-015AF is equipped with a  thermal shutdown function. When thermal shutdown operates, auto reset does not function until the temperature inside the power 
supply drops. 

*3) Calculation of the expected life is based on the actual life of the aluminum electrolytic capacitor.  

The expected life depends on operating conditions.

5

Summary of Contents for PS3V

Page 1: ...Switching Power Supplies PS3V Compact Reliable Power Supplies Flexible installation allows mounting in four directions ...

Page 2: ...ilities such as buildings Operates in temperatures ranging from 25 to 70 C Ideal for use in various storage facilities such as freezers and refridgerators Warehouse storage Compact Operating Temperature Push in connection As a manufacturer of factory automation products we provide total solutions and related PLCs HMI products One step wiring Safe and effiecient push in connection Push in models av...

Page 3: ...rage Car facilities Logistics and transport facilities Agricultural facilities Energy related facilities others QR codes are printed on the product enabling easy access to the latest instruction manuals Safety Standards Mounting examples When PS3V 030AF is mounted standard mount with PS9Z 3E3C mounting bracket Direct mount DIN rail mount When PS3V 050AF is mounted standard mount with PS9Z 3E3B mou...

Page 4: ...PS3X L shaped mounting brackets PS9Z 3N3B cannot be used L shaped mounting bracket is not available for PS3V 150AF PS9Z 3N3B L shaped mounting brackets cannot be used for PS3V 150AF Part no configuration DIN rail End clip Tools Specify the Ordering no when ordering Name Part No Ordering No Package quantity Remarks 35mm DIN rail BAA1000 BAA1000PN10 10 Material Aluminum Weight 200g Length 1 000mm En...

Page 5: ...x 12V 2 5 p p max 24V 1 5 p p max 12V 2 5 p p max 24V 1 5 p p max 24V 1 5 p p max 0 to 50 C 5V 2 5 p p max 12V 1 5 p p max 24V 1 p p max 5V 2 5 p p max 12V 1 5 p p max 24V 1 p p max 12V 1 5 p p max 24V 1 p p max 24V 1 p p max Supplementary functions Overcurrent protection 105 min auto reset 2 Overvoltage protection 120 min intermittent auto reset Output off at 120 min reset when re input Operation...

Page 6: ... 85 100 264 0 10 20 30 40 50 60 70 80 90 100 85 90 264 0 20 40 60 80 100 Input Voltage VAC 85 100 264 0 20 40 60 80 100 Output Current Input Voltage VAC Output Current Input Voltage VAC Output Current PS3V 015AF 030AF PS3V 050AF Areas indicated with may take time for the output voltage to stabilize Overcurrent detection Detection L N INPUT Control Line filter Switching Fuse Rectifier Rectifier V A...

Page 7: ...F Note Note the terminal arrangement when wiring AC L AC N V V V ADJ LED AC L AC N V V V ADJ LED AC L AC N V V V ADJ LED AC L AC N V V V ADJ LED AC L AC N V V V ADJ LED V V AC L AC N V V V ADJ LED V AC L AC N V V V V ADJ LED AC L AC N V V V V ADJ LED AC L AC N V V V V V V V ADJ LED PS3V 050AF PS3V 030AF PS3V 100AF PS3V 100AF Horizontal terminal type Push in terminal type Note 15W is not available ...

Page 8: ... Depth 6mm max 2 M3 Depth 6mm max 8 2 9 5 Terminal Centers 17 10 5 80 34 5 2 M3 95 5 68 5 101 2 M3 36 5 15 70 7 5 Input terminal centers Depth 6mm max 5 0 Output terminal centers Depth 6mm max 80 45 5 23 5 55 99 17 5 7 74 36 2 M3 2 M3 104 5 7 5 Input terminal centers 5 0 Output terminal centers Depth 6mm max Depth 6mm max 108 49 93 12 5 76 10 18 14 77 19 39 3 M3 113 5 2 M3 7 5 Input terminal cente...

Page 9: ...lectric Facilities for General Use When using the product follow the following precautions Precautions on switching power supplies This product is for industrial or general electronic equipment such as communication measurement and industrial electronic equipment Do not use for devices that may cause malfunction or may harm the body or threaten human life Make sure that the input voltage and outpu...

Page 10: ... supplies operate normally when voltage returns to normal PS3X 030 050 100 150 The output is turned off or intermittent operation when an overvoltage is applied When the output voltage has dropped due to an overvoltage turn the input off and after one minute turn the input on again Insulation Dielectric test When performing an insulation dielectric test short the input between AC and output betwee...

Page 11: ...al disasters Warranty Accessories and wiring for Push in terminals Wire size and recommended ferrules Push in terminal type only Ferrules with insulated covers Applicable Wire Stranded Wire Wire Strip Length mm Part No Ordering No AWG mm2 For 1 wire 18 0 75 12 S3TL H075 16WW 17 1 0 12 S3TL H10 16WY 16 1 5 12 S3TL H15 16WR For 2 wires 18 0 75 21 S3TL J075 19WWS Recommended tools Optional See page 4...

Page 12: ...spections We ask that you implement inspections for IDEC products you purchase without delay as well as thoroughly keep in mind management maintenance regarding handling of the product before and during the inspection 4 Warranty 1 Warranty period The warranty period for IDEC products shall be five 5 years after purchase or delivery to the specified location However this shall not apply in cases wh...