PS3V Switching Power Supplies
Warranty
IDEC warranties the PS3V switching power supplies for a period of five
years from the date of shipment.
Scope
In the event of a failure caused by our responsibility within the above
period, we will replace the product. However, if the product is used
under the following conditions, the warranty may not apply even within
the warranty period.
1. Average operating temperature (ambient temperature of switching
power supply) is 40°C maximum.
2. The load is 60% maximum.
3. Input voltage is the rated input voltage.
4. Standard mounting style
If we are responsible for a failure that occurs during the warranty
period described at left, we will repair the product or replace it with an
alternative product.
Please note that we will not be liable for any damage caused by
the failure of the delivered product. In addition, please note that the
warranty does not apply to the following cases.
1. Inappropriate handling, or operation beyond the specifications.
2. Modification or repair by other than IDEC.
3. Failure caused by reasons other than the switching power supply.
4. Failure caused by natural disasters.
Warranty
Accessories and wiring for Push-in terminals
Wire size and recommended ferrules
(Push-in terminal type only)
Ferrules with insulated covers
Applicable Wire
(Stranded Wire)
Wire Strip
Length
(mm)
Part No.
(Ordering No.)
AWG
mm
2
For 1
wire
18
0.75
12
S3TL-H075-16WW
17
1.0
12
S3TL-H10-16WY
16
1.5
12
S3TL-H15-16WR
For 2
wires
18
0.75
21
S3TL-J075-19WWS
Recommended tools
(Optional. See page
4
for details)
Name
Part No. (Ordering No.)
Crimping tool
S3TL-CR06D
Auto-adjust stripping tool
S3TL-ST06
Insulated screwdriver
S3TL-D04-25-75
Note) Use a flat blade screwdriver with a blade size of 0.4×2 to 2.5 mm.
0.4mm
2.5mm
Wiring procedure
Wiring
(1) Insert the solid wire or stranded wire with
ferrule into the terminal entrance.
* If the shape of the ferrule becomes trapezoidal
after the clamping, insert the ferrule with the long
side of the clamped part parallel to the pusher.
* When inserting stranded wires directly, make sure
that the pusher in pressed down and there are no
loose wires.
Note) When inserting a ferrule terminal with two
wires, insert the insulated cover part vertically to
the pusher.
Insulated cover part
(2) After wiring, tug lightly to make sure that the wire is properly
connected.
Removing the wire
(1) Press the pusher using a insulated
screwdriver.
(2) Remove the wire by pressing the pusher.
Pusher
11