2: M
ODULE
S
PECIFICATIONS
2-4
W
EB
S
ERVER
CPU M
ODULE
U
SER
’
S
M
ANUAL
FC9Y-B1278
General Specifications
Normal Operating Conditions
Power Supply
Note 1:
Among relay output modules connected to the CPU module, a maximum of 54 points can be turned on simultaneously. Among
relay outputs connected beyond the expansion module, a maximum of 54 points can be turned on simultaneously. Relay outputs
exceeding these limits may not turn on correctly.
Note 2:
Maximum power consumption for individual CPU module is 3.0W (125 mA at 24V DC).
CPU Module
FC5A-D12K1E
FC5A-D12S1E
Operating Temperature
0 to 55°C (operating ambient temperature)
Storage Temperature
–25 to +70°C
Relative Humidity
10 to 95% (non-condensing, operating and storage humidity)
Pollution Degree
2 (IEC 60664-1)
Degree of Protection
IP20 (IEC 60529)
Corrosion Immunity
Atmosphere free from corrosive gases
Altitude
Operation:
0 to 2,000m (0 to 6,565 feet)
Transport:
0 to 3,000m (0 to 9,840 feet)
Vibration Resistance
When mounted on a DIN rail or panel surface:
5 to 8.4 Hz amplitude 3.5 mm, 8.4 to 150 Hz acceleration 9.8 m/s
2
(1G)
2 hours per axis on each of three mutually perpendicular axes (IEC 61131-2)
Shock Resistance
147 m/s
2
(15G), 11 ms duration, 3 shocks per axis on three mutually perpendicular axes
(IEC 61131-2)
ESD Immunity
Contact discharge: ±4 kV, Air discharge: ±8 kV (IEC 61000-4-2)
Weight
200g
Rated Power Voltage
24V DC
Allowable Voltage Range
20.4 to 26.4V DC (including ripple)
Maximum Input Current
700 mA (26.4V DC)
Maximum Power Consumption
(Note 1, 2)
CPU 7 I/O m expansion 8 I/O modules
19W (26.4V DC)
Allowable Momentary Power
Interruption
10 ms (at 24V DC)
Dielectric Strength
Between power and
terminals:
Between I/O and
terminals:
500V AC, 1 minute
500V AC, 1 minute
Insulation Resistance
Between power and
terminals:
Between I/O and
terminals:
10 M
Ω
minimum (500V DC megger)
10 M
Ω
minimum (500V DC megger)
Noise Resistance
DC power terminals:
I/O terminals (coupling clamp):
1.0 kV, 50 ns to 1 µs
1.5 kV, 50 ns to 1 µs
Inrush Current
50A maximum (24V DC)
Grounding Wire
UL1015 AWG22, UL1007 AWG18
Power Supply Wire
UL1015 AWG22, UL1007 AWG18
Effect of Improper Power Supply
Connection
Reverse polarity:
Improper voltage or frequency:
Improper lead connection:
No operation, no damage
Permanent damage may be caused
Permanent damage may be caused