background image

 

2

Noise S

p

ecifica

tions

 

Electrostatic Discharge 

ESD-3 (RH-1) : Level 3 
Contact ±6 kV / Air ± 8 kV 
(IEC/EN61000-4-2) 

Electromagnetic Field 

AM80% 
10 V/m    80 MHz to 1000 MHz 
3 V/m      1.4 GHz to 2.0 GHz 
1 V/m      2.0 GHz to 2.7 GHz 
(IEC/EN61000-4-3) 

Fast Transient 
Burst Withstandability 

Common mode: Level 3 
Power supply: ±2 kV 
Communication line: ±1 kV 
(IEC/EN61000-4-4) 

Surge Immunity 

HG2G-S#22*F-%: 

500V b24V-0V,   
1kV b24V-FG, 0V-FG 

HG2G-S#21*F-%: 

500V b12V-0V,   
1kV b12V-FG, 0V-FG 

(IEC/EN61000-4-5) 

Conducted Radio 
Frequency Immunity 

0.15 to 80MHz  80%AM (1kHz)  3V 
(IEC/EN61000-4-6) 

Radiated Emission 

IEC/EN61000-6-4 

*1 Protection degree of the front surface after mounting. Operation not guaranteed under 

certain environments. 

*2 Protection against certain types of oil materials are not guaranteed under Type 13.

 

 

4

 

Installation 

 

Operating Environment 

For designed performance and safety of the HG2G, do not install the HG2G in the following 
environments: 
 

 

Where dust, briny air, or iron particles exist. 

 

Where oil or chemical splashes for a long time. 

 

Where oil mist is filled. 

 

Where direct sunlight falls on the HG2G. 

 

Where strong ultraviolet rays fall on the HG2G. 

 

Where corrosive or combustible gasses exist. 

 

Where the HG2G is subjected to shocks or vibrations. 

 

Where condensation occurs due to rapid temperature change. 

 

Where high-voltage or arc-generating equipment (electromagnetic contactors or circuit 
protectors) exists in the vicinity. 

 

 

Ambient Temperature 

 

The HG2G is designed to install on a vertical plane so that natural air-cooling is provided. 
Keep as much space as possible around the HG2G. Allow 100mm minimum clearance 
above and below the HG2G. 

 

Do not install the HG2G where the ambient temperature exceeds the rated operating 
ambient temperature range. When mounting the HG2G in such locations, provide a forced 
air-cooling fan or air-conditioner to keep the ambient temperature within the rated 
temperature range. 

 

 

Panel Cut-out Dimensions 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
Place the HG2G in a panel cut-out and fasten with the attached mounting clips at four places to 
a specified torque of 0.12 to 0.17 N

m uniformly. 

Do not tighten excessively, otherwise the HG2G may warp and cause wrinkle on the display, or impair 
the waterproof characteristics. 
 
 

 

If the mounting clips are tightened obliquely to the panel, the HG2G may fall off the panel. 

 

When installing the HG2G into a panel cut-out, make sure that the gasket is not twisted. 
Especially when re-installing, take special care because any twists in the gasket will impair 
the waterproof characteristics. 

 

5

 

Notes for Operation 

 

The screen becomes blank when the backlight is burnt out; however, the touch panel 
remains enabled. Incorrect touch panel operation will occur when operating the touch panel   
when the backlight appears to be turned off but is actually burnt out. Note that this erroneous 
operation may result in damage. 

 

At temperatures over the rated operating temperature, the clock accuracy is affected. Adjust 
the clock before use. 

 

For applications which require clock accuracy, adjust the clock periodically. 

 

When more than one button is pressed at the same time, due to the detection characteristics 
of an analog type touch panel, only the gravity center of the pressed area is sensed and the 
unit assumes that only one button is pressed. Thus, when more than one button is pressed 
simultaneously, the resulting operation is not guaranteed. 

 

Do not install the HG2G in areas subjected to strong ultraviolet rays, since ultraviolet rays 
may impair the quality of the LCD. 

 

Use WindO/I-NV2 version 4.10 or later for the 12V DC power type HG2G operator interfaces. 
If an older version of configuration software is used to download the system program, an 
incorrect product Type No.is displayed on the system information screen. 

 

6

 

Wiring 

 

Turn off the power supply before wiring. 

 

Make the wiring as short as possible and run all wires as far away as possible from 
high-voltage and large-current cables. Follow all the procedures and precautions when 
wiring the HG2G. 

 
 

 

Power Supply Terminals 

Pin assignment is shown in the following table. 
 

 

 

Power supply   
HG2G-S#22*F-% : 24V DC
HG2G-S#21*F-% : 12V DC

- Power 

supply 

0V 

 

Functional Earth 

 

 

Use applicable cables for wiring and recommended ferrules (made by Phoenix Contact) as 
follows: 

 

Applicable cable 

AWG18 to AWG22 

Recommended  
Pressure Terminal 

AI 0,34-8 TQ 
AI 0,5-8 WH 
AI 0,75-8 GY 
AI 1-8 RD 
AI-TWIN 2 x 0,5-8 WH 
AI-TWIN 2 x 0,75-8 GY 
AI-TWIN 2 x 1-8 RD 

Tightening Torque 

0.5 to 0.6 N

 

 

For power supply wiring, twist the wires as close as possible and make the power supply 
wiring as short as possible. 

 

Separate the HG2G power supply wiring from the power lines of I/O devices and motor 
equipment. 

 

Ground the functional ground terminal to make sure of correct operation. 

 

HG2G operator interfaces operate on 12 or 24V DC depending on the model. Make sure 
that the correct voltage is supplied to the HG operator interface.   

 
 

7

 

Dimensions 

 

 

All Dimensions in mm      

 

Display (5.7 inch STN LCD) 

Touch Panel (Analog resistance membrane method) 

Status LED 

Serial Interface 1 

Serial Interface 2 

O/I Link Interface 

Ethernet Interface 

Terminating Resistor Selector SW (for RS422/485 interface) 

Battery Holder Cover 

Mounting Clip Position 

Gasket 

 

Panel 

Mounting 

Clip 

HG2G 

B

 

A: 121

+2

 

 
B: 153

+2

 

 

Panel Thickness: 1.6 to 5 
Dimensions in mm 

-0 

-0 

Summary of Contents for MICRO/I HG2G Series

Page 1: ...sion See instruction sheet for safety instructions Caution Battery may explode if mistreated Do not recharge disassemble or dispose of in fire Warning Explosion Hazard Batteries must only be changed in an area known to be Non Hazardous For Indoor Use Only Pollution Degree 2 Environment in an area that is dry and free of contaminates Avertissement Risque d explosion La substitution de composants pe...

Page 2: ...Operation The screen becomes blank when the backlight is burnt out however the touch panel remains enabled Incorrect touch panel operation will occur when operating the touch panel when the backlight appears to be turned off but is actually burnt out Note that this erroneous operation may result in damage At temperatures over the rated operating temperature the clock accuracy is affected Adjust th...

Page 3: ... Dedicated connector The HG2G Operator Interface can be connected to an O I Link Unit for 1 N communication with a PLC This allows high speed communication with the PLC host Ethernet interface EEE802 3 standard compliant 10 100Base T No Name O Function 1 TPO OUT Send Data 2 TPO OUT Send Data 3 TPI IN Receive Data 4 NC No Connection 5 NC No Connection 6 TPI IN Receive Data 7 NC No Connection 8 NC N...

Page 4: ...ears on the screen 2 Press the Adjust Contrast at the bottom of the Maintenance Screen The Adjust Contrast Screen appears 3 Press the or at the bottom the Adjust Contrast Screen to adjust the contrast to the optimal setting 4 Press the X to close the Adjust Contrast Screen The Maintenance Screen is not displayed in System Mode To adjust the contrast in System Mode use the and buttons located at th...

Reviews: