25
8
Wiring
●
Turn off the power supply before wiring.
●
Make the wiring as short as possible and run all wires as far away as possible from
high-voltage and large-current cables. Follow all the procedures and precautions when
wiring the HG4G/3G, HG2G-5F.
●
Separate the HG4G/3G, HG2G-5F power supply wiring from the power lines of I/O
devices and motor equipment.
●
Ground the functional earth terminal to make sure of correct operation.
8.1 Power Supply Terminal
・
Pin assignment is shown in the following table.
+
Power supply 24V DC (+24V)
-
Power supply 0V (0V)
Functional Earth (FE)
・
Use applicable cables for wiring and recommended ferrules (made by Phoenix Contact)
as follows.
Type No.
HG4G/3G
HG2G-5F
Applicable cable
AWG18 to AWG22
AWG14 to AWG22
Recommended
Pressure Terminal
AI 0,34-8 TQ
AI 0,5-8 WH
AI 0,75-8 GY
AI 1-8 RD
AI-TWIN 2 x 0,5-8 WH
AI-TWIN 2 x 0,75-8 GY
AI-TWIN 2 x 1-8 RD
(Phoenix Contact)
AI 0,34-12 TQ
AI 0,5-12 WH
AI 0,75-12 GY
AI 1-12 RD
AI 1,5-12 BK
AI 2,5-12 BU
AI-TWIN 2 x 1,5-12 BK
(Phoenix Contact)
Tightening Torque
0.5 to 0.6 N
・
m
0.5 to 0.6 N
・
m