Technical Data
26
HR9Z-B2202 8/2020
Electrical Characteristics
Supply
Electromagnetic Compatibility (EMC)
Common Reference Potential
Terminal B2 is provided to obtain a common reference potential for 24 VDC signals.
Safety-Related Inputs
Characteristic
Value
Supply voltage AC
24 VAC (-15 ... 10 %)
Supply voltage DC
24 VDC (-20 ... 20 %)
Nominal input power AC
5 VA (24 VAC)
Nominal input power DC
2 W (24 VDC)
Frequency range AC
50 ... 60 Hz
Overvoltage category
II
Pollution degree
2
Insulation voltage
300 V
Impulse withstand voltage
4 kV
Characteristic
Value
Conducted and radiated emissions as per IEC CISPR 11 Group 1/class B
Usage in environment as per IEC/UL 60947-1
Environment B
Characteristic
Value
Number of inputs, positive supplied (each with 1 control
output DC+ (S11, S21) and 2 inputs CH+ (S12–S13, S22–
S23)), dual-channel
2
Output voltage at DC+
>15 VDC
Input voltage at CH+
0 ... 24 VDC (+20 %)
Switching voltage for activation of CH+
>15 VDC
Switching voltage for deactivation of CH+
<5 VDC
Input current
5 mA
Maximum wire resistance
500 Ω