Enabling Switches
General
Information
Safety
Precautions
General Information
•
In order to avoid electric shock or
fi
re, turn power off before installation,
removal, wire connection, maintenance or inspection of switch.
•
Follow
specification
when installing. Improper electrical load may damage
switch, cause electric shock, or
fi
re.
•
Use proper wire diameter to meet voltage and current requirements. Using
improper wires or incomplete soldering may cause
fi
re due to abnormal heat
generation.
Installation
Precautions
HE2B
•
M3 nut is inside the rubber cover.
•
If the panel is not level when mounting an enabling switch, the waterproof
feature cannot be guaranteed.
HE3B
•
The rubber boot has a tab to be used for orientation. When making a position-
ing hole in a panel, do not make a hole in the rubber boot, or the waterproof
feature cannot be guaranteed. When the positioning hole is not on the panel,
remove the tab, but do not make a hole in the rubber boot.
•
When tightening the locking ring, secure the
fl
ange to prevent the enabling
switch from rotating. In applications where the enabling switch is to be
rotated, mount the switch in a recess on the panel as shown.
HE2B/HE3B
Mounting Panel Positioning
Projection
•
A change in internal air pressure may cause the rubber boot to expand and
shrink on an enabling switch that has the rubber boot sealed. This may affect
the performance of the switch. Periodically check to ensure that the enabling
switch is operating correctly.
Anti-rotation Ring
Locking Ring
Wiring
Precautions
HE1B/HE2B/HE3B
•
Applicable wire size is 0.5mm
2
(20AWG) (maximum) / 1 line.
•
When soldering the terminal, solder at a temperature of 260°C within 3
seconds. Use non-corrosive liquid rosin as soldering
fl
ux.
HE1G
•
Wire Stripping Information
•
Recommended Torque
cover
base
base
cover
base
(M4 screw x 3)
Rubber Boot & Base
A
1.2±0.1Nm
Connector & Grip Switch
B
4.0±0.3Nm
Connector
C
4.0±0.3Nm
Terminal Screw
D
0.5±0.6Nm
Do Not Remove
E
•
Applicable Wire Size:0.14 to 1.5mm
2
(24 - 16AWG, one wire per terminal)
Use
Precautions
HE2B/HE3B/HE1G
•
To ensure the highest level of reliability connect both contacts to a monitoring
device such as a safety relay.
HE1B/HE2B/HE3B
•
When installing the enabling switch ensure that it cannot be accidently
activated. For example, a protrusion from a teaching pendant could cause the
enabling switch to be activated by the weight of the teaching pendant.
L3
L1
Cable Gland
ø15.875
L3
L2
Base
Terminal No.
See Drawing
Above
Recommended
Torque
Ov
erv
iew
X S
er
ie
s E
-
Sto
ps
Do
or
Int
erlo
ck
Sw
itc
hes
Enab
lin
g S
w
itc
hes
Ba
rri
ers
AS
-In
te
rfac
e S
afet
y at
W
ork
Wire Length
Terminal
Number
1-4
Terminal
Number
5-8
L1, L2 (mm)
L1=40mm
L2=27mm
L3 (mm)
L3=6mm