IDEC EB3P-ZN Installation Download Page 3

 

Installations of IDEC 

Intrinsically Safe System 

Type EB3P-ZN Buzzers. 

 

 
 
 
 
 

The  EB3P-ZN  buzzer  has  been  certified  by  the  equipment 

certification test on condition that the buzzer is used in combination 

with  the  EB3L  and  EB3L-N  lamp  barrier  or  equipment  that  has 

equivalent intrinsically safe characteristics and ratings. 

All  intrinsically  safe  systems  must  have  “EB3P-ZN”  in  the  part 

number. The EB3P-ZN buzzer can be located in a hazardous area if 

connected to EB3L and EB3L-N Lamp Barrier.   

  This  buzzer  can  secure  intrinsically  safe  performance  when  set 

according to the instruction manual No.B-1738 and the   

application  requirements  below.   

 

 

 

Warning  notices  are  used  to  emphasize  that  improper  operation 
may cause severe personal injury or death. 
□In product security 

Do not disassemble, repair, or modify the EB3P-ZN, otherwise it 
may cause loss of the product safety. 

Be sure to turn the power off before wiring. 

 
□Explosion-proof safety 

 

Install the EB3P-ZN in hazardous area and place an intrinsically 
safe associated apparatus in non-hazardous area.     

 

Use the EB3P-ZN  in zone 1 and zone2. Do not  use  it  in zone 
0. 

 

Be  sure  to  use  the  EB3P-ZN  with  connecting  to  an 
intrinsically  safe  associated  apparatus,  otherwise  explosion 
may result. 

The  intrinsically  safe  associated  apparatus  needs  to  be  ATEX 
certified  and  satisfy  the  “Connection  conditions  of  the  IS 
associated  apparatus.”  To  use  apparatuses  without  above 
conditions may cause explosion. 

Check  if  the  operating  environment  is  within  the  specification 
range before use. 

 
 
 
Caution notices are used where  inattention  might cause personal 
injury or damage to equipment. 
 
□Product safety 

 

Be sure to use within the specification range for safety. 

 

Do  not  use  the  damaged  product,  otherwise  it  may  cause 
injury or fire hazard. 

 
 
 
 
 
 
 

Product type Number

 

EB3P-ZUN12CN 

Continuous sound 

EB3P-ZUN12FN 

Intermittent sound 

 

Explosion Protection Specification

 

 

Installation

 

Install the buzzer on the enclosure in a φ30mm hole. Fix the 
product at the back with an installation ring. 

Complete the installation securely so that the terminal part of 

the buzzer achieves IP20 or higher.   

The buzzer does not have an adjustment item. 

 

 

 

 

 

 

 

 

 

Please make sure the buzzer is mounted on the enclosure that 

satisfies the following requirements. 

 

Buzzer maintenance and inspection

 

Turn the power of the intrinsically safe associated apparatus off 

before doing maintenance and inspection for buzzers. Confirm if 

the installation environment is in the specification range, the 

protection degree is IP20 or over, and the product is connected to 

proper safe related apparatus. Replace the products immediately 

if the buzzer or the intrinsically safe associated apparatus is 

defected. 

 

Connection conditions of the IS associated apparatus

 

Please make sure the buzzer is connected to IS associated apparatus (barrier) that satisfies the following requirements.   

Item 

Connection conditions of    the IS 

associated apparatus(barrier) 

EB3L-N lamp barrier 

Note

 

Explosion-proof construction 

ia or ib 

ia 

Group 

IIC 

IIC 

IS circuit maximum voltage 

Uo

13.2V 

Uo=13.2V 

IS circuit maximum current

   

Io

14.2mA 

Io=14.2mA 

IS circuit maximum   
electric power

   

Po

46.9mW 

Po=46.9mW 

IS circuit maximum values of 
the external capacitance

 

Co

260nF 

Co=470nF 

IS circuit maximum values of 
the external inductance

 

Lo

80mH 

Lo=87.5mH 

 

Note

1-channel in separate wiring 

Notice for wiring to the EB3L-N lamp barrier

 

Connect to the EB3L-N with 1-channel in separate wiring. 16-channel in common wiring is not available. 

The value of the external capacitance (Cw) of intrinsically safe associated circuit and the external inductance (Lw) are as follows: 

Cw 

 210nF 

= Co

470nF -    Ci

260nF

 

  Lw 

 7.5mH 

= Lo

87.5mH – Li

80mH

 

Wiring diagram for the EB3L-N

except for common wiring model

and buzzers 

 

Connect “+” of a buzzer to the terminal “P” and    “-”    to the terminal “N” of the EB3L-N. 

 

Note: Be sure to wire each channel independently. Common wiring is not available. 

 

 

 

 

 

 

 

Wiring diagram for the EB3L-N(common wiring model only) and buzzers 

 

Connect “+” of a buzzer to the terminal “P” and    “-”    to the terminal “N” of the EB3L-N. 

 

Only one buzzer can be connected to a set of eight circuits. 

(Two buzzers can be connected to a 16-channel common wiring model which consists of two eight-circuit commons.) 

Note: Pilot lights and illuminated switches cannot be connected to the common circuit that already has a buzzer connected. 

 

 

 

 

 

 

 

 

Specific conditions of use

 

 

The buzzer must be mounted partly or completely within an enclosure according to EN60079-11. 

The buzzer enclosure cap is made of aluminium, ignition hazards due to impact and friction need to be avoided 
according to EN60079-0 clause 8.3 

The buzzer must be connected with intrinsically safe parameters specified in the certificate.

 

                                 

                                                                                                 

           

   

 

 
 
 
 
 
 

Applicable 

standards 

EN60079-0:2012 
EN60079-11:2012 
EN60079-26:2007

 

Explosion 

protection 

Ex ia IIC T6 

Operating 

temperature 

-20

 to 60

℃ 

(no freezing) 

Operating 

humidity 

45 to 85%RH

 

(no condensation) 

Protection 

degree 

IP20 or higher 

mounted on the enclosure

 

Withstand 

voltage 

IS terminal 

 unfilled part 

AC500V 5mA

 

 

IS rating 

Ui=13.2V , Ii=14.2mA , Pi=46.9mW , 

Ci=260nF , Li=80mH     

Enclosure Material 

 

Metal: with less than 7.5% of magnesium 

(steel plate, aluminum, etc.) 

Plastic:  required  to  attach  a  caution  plate 

for antistatic 

Degree of Protection 

IP20 or higher 

Wiring in the 

enclosure 

Cross section of the electric wire 

0.3

2

 or over 

Draw. No. B-1738-2

   

Apr. 01, 2015

 

 

    Warning 

 

 

    Caution

 

Lamp 
Barrier 

Lamp 
Barrier 

Manufacturer.IDEC CORP. 
2-6-64 Nishimiyahara Yodogawa-ku, Osaka 532-0004, Japan 
EU Authorized Representative : IDEC Elektrotechnik GmbH 
Heselstücken 8, 22453 Hamburg, Germany             

2015.04 

 

 

Summary of Contents for EB3P-ZN

Page 1: ...e inattention might cause personal injury or damage to equipment On product safety When wiring make sure of correct polarities When wiring the EB3L N lamp barriers separate from wiring the power supply line When the EB3P ZN buzzer howls due to the noise connect a linear filter with a rated current higher than the EB3L N rated current to the power line of EB3L N lamp barrier Certificate Certificati...

Page 2: ...さい ブザーは防爆性能保 持のための調整項目はありません ブザーを取り付ける容器は 以下の条件を満足すること を確認してください 本安関連機器 バリア との接続条件 ブザーと接続する本安関連機器 バリア は以下の防爆性能を満足していること 項目 本安関連機器 バリア の接続条件 EB3L N形ランプバリア注 防爆構造 iaまたはib ia グループ IIC IIC 本安回路最大電圧 Uo 13 2V Uo 13 2V 本安回路最大電流 Io 14 2mA Io 14 2mA 本安回路最大電力 Po 46 9mW Po 46 9mW 本安回路許容キャパシタンス Co 260nF Co 470nF 本安回路許容インダクタンス Lo 80mH Lo 87 5mH 注 EB3L Nの各パラメータはチャンネルセパレート配線条件となります EB3L N形ランプバリアとの接続時の注意事項 EB3L Nと...

Page 3: ...ed Connection conditions of the IS associated apparatus Please make sure the buzzer is connected to IS associated apparatus barrier that satisfies the following requirements Item Connection conditions of the IS associated apparatus barrier EB3L N lamp barrier Note Explosion proof construction ia or ib ia Group IIC IIC IS circuit maximum voltage Uo 13 2V Uo 13 2V IS circuit maximum current Io 14 2m...

Page 4: ...的IS关联设备符合以下要求 项目 IS关联设备的连接条件 EB3L N指示灯安全栅 注 防爆标志 ia或ib ia 分类 IIC IIC IS 电路最大电压 Uo 13 2V Uo 13 2V IS电路最大电流 Io 14 2mA Io 14 2mA IS电路最大功率 Po 46 9mW Po 46 9mW IS电路外部电容最大值 Co 260nF Co 470nF IS电路外部电感最大值 Lo 80mH Lo 87 5mH 注 各电路单独接线 EB3L N指示灯安全栅布线的注意事项 清用单独的连接线连接EB3L N 不能在公共接线上使用 本质安全关联电路的外部电容 Cw 和外部电感 Lw 值如下 Cw 210nF Co 470nF Ci 260nF Lw 7 5mH Lo 87 5mH Li 80mH EB3L N的布线图 除普通布线机型外 和蜂鸣器 将蜂鸣器的 连接至端子 P 将 连接...

Reviews: