Accuracy

Line Voltage:

108.0 - 132.0VAC

1.0%

+/- 1 digit

Peak Voltage

151.0 - 185.0VAC

1.0%

+/- 1 digit

Frequency:  

45.0 - 85.0Hz

1.0%

+/- 1 digit

Voltage Drop:

0.1% -  2 0 . 0 % 

1.0%

+/- 1 digit

Ground-Neutral Voltage:  0.0 - 24.0 VAC 

1.0% 

+/- 1 digit

Impedances: 

0.01 - 9.99

1.0%

+/- 1 digit 

GFCI Trip Time : 

1mS - 7000mS

1.0%

+/- 1 digit

SureTest

®

Circuit Analyzer

1. Menu Structure 
2. Menu Buttons 
3. Display
4. GFCI Test Button
5. AFCI Test Button

Menu Structure

The measurements taken by the SureTest model ST-2D are organized into a
simple menu.  The first measurement in each menu selection is listed on the
face of the unit.  To the right of each menu is the unit of measure for the
tests performed within that menu.  The grid, and up and down arrows are
representative of how the display will indicate the units position within the
menu.  The grid has four regions (one for each menu selection).  When the
unit is in the line voltage menu, the first section of the grid will be shaded in
on the display to indicate that the unit is in the first menu selection.  When
the unit is in the Voltage Drop menu, the second section of the grid of the
grid will be shaded in on the display to indicate that the unit is in the sec-
ond menu selection.  This follows for the Ground-Neutral Voltage and Line
Impedance menus as well.

Additional tests are located in the sub-menu for each of these menu selec-
tions.  An up arrow indicates that the unit is in the main menu, and a down
arrow indicates that the unit is in a sub-menu.  This will be displayed just
under the menu grid on the unit’s display.  Using the menu grid and menu
level indication will help the user step through the menu as indicated by the
menu structure listed on the face of the unit.

Menu Buttons

The SureTest model ST-2D uses two buttons to navigate through the mea-
surement menu.  The down arrow button 

(↓

) moves the unit forward to the

next menu selection.  If the SureTest is on the last menu selection (Line
Impedance), pressing the down arrow button returns the unit to the first
menu selection (Line Voltage).  

The side arrow button (

→ 

) moves the unit through all the measurements

within the menu selection.  If the SureTest is in the last measurement of the
menu selection, pressing the side arrow button returns the unit to the first
measurement.

The quick reference guide at the end of this manual lists all of the available
measurements in the SureTest menu.  

Display

The graphical LCD on the SureTest ST-2D indicates the value of the measure-
ment function, the test being performed and the position within the menu
structure.

1. Test results
2. Measurement Icon
3. Menu Structure Icon

Measurement Icon

The measurement icon is located on the right-hand side of
the display.  The icon consists of the measurement symbol
and text to describe which test is being measured.  For exam-
ple, the following icon indicates that the numerical value dis-
played is the True RMS line voltage.  

3

3

#61-155

GFCI

AFCI

Line Voltage (V)

Voltage Drop (%)

G-N Voltage (V)

Line Impedance (    )

 RMS

True

S

u

r

e

e

T

s

t

2
4
5

1

V

RMS

4

Sold by:

http://www.TWAcomm.com

Toll Free: (877) 892-2666

Summary of Contents for SureTest 61-154

Page 1: ...155 will also test arc fault circuit interrupter AFCI test to ensure that AFCI breakers protecting the circuit have been installed correctly and are operating properly This test is performed sepa rat...

Page 2: ...tes that the unit is in a sub menu This will be displayed just under the menu grid on the unit s display Using the menu grid and menu level indication will help the user step through the menu as indic...

Page 3: ...icon It consists of a grid and either an up or down arrow The grid on the display has four regions that correspond to each of the menu selections as listed on the face of the unit The appropriate regi...

Page 4: ...the circuit To determine what may be causing the problem turn off the loads on the circuit and re check If the test results do not change than the problem may be within the circuit If the test result...

Page 5: ...voltage on the branch load on the circuit drop circuit Undersized wire Check code for length of run requirements and re wire if necessary High resistance Locate high connection within resistance the c...

Page 6: ...ry gauge wire High resistance Locate high 0 01 connection within resistance foot of 10 the circuit or at connection device gauge wire the panel and repair replace Neutral 0 48 High Too much load Redis...

Page 7: ...the GFCI may be at the receptacle or at the panel To activate the GFCI test press the GFCI button GFCI from anywhere with in the measurement menu The actual current being bled from hot to neutral will...

Page 8: ...he receptacle and make a note of the results See the section on Line Impedance Testing for details Remove the SureTest and plug it into the isolated ground adapter Attach the alligator clip to the cen...

Page 9: ...ire is sized per code and measure the current on the branch circuit The reading may not decrease at all from the last receptacle to the first This would indicate that the problem could be at the first...

Page 10: ...ES INC will at its option replace or repair the defective unit subject to verification of the defect or malfunction This warranty does not apply to defects resulting from abuse neglect accident unauth...

Reviews: