29
INSTALLATION
IMAX XTRA EL
-
Installation & Servicing
28 IMAX XTRA EL WITH EXTERNAL CONTROLS
VIA SWITCHED LIVE, 0-10V INPUT OR OPENTHERM
EXTERNAL CONTROLS - VIA OPENTHERM
EXTERNAL CONTROLS - VIA 0-10V INPUT
EXTERNAL CONTROLS - VIA SWITCHED LIVE
Note that the boiler requires a 2 minute pump overrun period.
The boiler warranty will be invalid if this is not provided.
It is recommended that the pump overrun functionality is
achieved by connecting the pump or pump control to the
boiler CH Pump connections (see diagram), although this
functionality can be replicated with external controls (for
example a Building Management System).
If the CH Pump connection is used and the electrical current
draw is 1.3A inductive or less then the pump may be connected
directly into the CH Pump connection.
If the current draw is more than this then an external relay or
contactor should be operated by the CH Pump connection, with
the external relay then powering the pump.
0-10+
0-10-
DHW+
DHW-
OWC+
OWC-
OT+
OT-
PW
M
GND
INT
INT
LOCKOUT
LOCKOUT
BURNER ON
BURNER ON
N
L NO
L NC
N
L
L
N
LIVE OUT
CH CALL
LIVE OUT
DHW/CH2 CALL
HEAT
DEMAND
23
0v
50
Hz
MAINS
IN
230v
50Hz
DHW/
CH2
PUMP/
VALVE
CH/
BOI
LER
PUMP
VOLTS
FREE
CONTACTS
INTER/
LOCK
PUMP
CONTROL
0-10v
INPUT
TANK
SENSOR
OUTSI
DE
SENSOR
OPEN
THERM
pump
control
supply
switched
live
0-10+
0-10-
DHW+
DHW-
OWC+
OWC-
OT+
OT-
PW
M
GND
INT
INT
LOCKOUT
LOCKOUT
BURNER ON
BURNER ON
N
L NO
L NC
N
L
L
N
LIVE OUT
CH CALL
LIVE OUT
DHW/CH2 CALL
HEAT
DEMAND
23
0v
50
Hz
MAINS
IN
230v
50Hz
DHW/
CH2
PUMP/
VALVE
CH/
BOI
LER
PUMP
VOLTS
FREE
CONTACTS
INTER/
LOCK
PUMP
CONTROL
0-10v
INPUT
TANK
SENSOR
OUTSI
DE
SENSOR
OPEN
THERM
0-10V
0 10
pump
control
supply
0-10+
0-10-
DHW+
DHW-
OWC+
OWC-
OT+
OT-
PW
M
GND
INT
INT
LOCKOUT
LOCKOUT
BURNER ON
BURNER ON
N
L NO
L NC
N
L
L
N
LIVE OUT
CH CALL
LIVE OUT
DHW/CH2 CALL
HEAT
DEMAND
23
0v
50
Hz
MAINS
IN
230v
50Hz
DHW/
CH2
PUMP/
VALVE
CH/
BOI
LER
PUMP
VOLTS
FREE
CONTACTS
INTER/
LOCK
PUMP
CONTROL
0-10v
INPUT
TANK
SENSOR
OUTSI
DE
SENSOR
OPEN
THERM
opentherm
master
- +
pump
control
supply
INST
ALLA
TION